Overview

The “Rate of frequency change protection” function is used to detect a frequency change quickly, and prevent the system from not secure states caused by unbalance between the generated and consumed active power. It is also used for network decoupling and load shedding.

For more detailed information on “Rate of frequency change protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Rate of frequency change protection Function

Setting Parameters


Setting parameters for Rate of frequency change protection function

Addr. Parameter C Setting Options Default Setting
General
_:13171:101 General:Minimum voltage   3.000 V to 175.000 V 37.500 V
_:13171:137 General:Measuring window   2 periods to 5 periods 5 periods
df/dt falling1
_:13231:1 df/dt falling1:Mode   off
on
test
off
_:13231:2 df/dt falling1:Operate & flt.rec. blocked   no
yes
no
_:13231:3 df/dt falling1:Threshold   0.100 Hz/s to 20.000 Hz/s 3.000 Hz/s
_:13231:4 df/dt falling1:Dropout differential   0.02 Hz/s to 0.99 Hz/s 0.10 Hz/s
_:13231:6 df/dt falling1:Operate delay   0.00 s to 60.00 s 1.00 s
df/dt rising1
_:13201:1 df/dt rising1:Mode   off
on
test
off
_:13201:2 df/dt rising1:Operate & flt.rec. blocked   no
yes
no
_:13201:3 df/dt rising1:Threshold   0.100 Hz/s to 20.000 Hz/s 3.000 Hz/s
_:13201:4 df/dt rising1:Dropout differential   0.02 Hz/s to 0.99 Hz/s 0.10 Hz/s
_:13201:6 df/dt rising1:Operate delay   0.00 s to 60.00 s 1.00 s

Logic Diagrams & highlights


Logic Diagram of General Functionality

Logic Diagram of General Functionality

Logic Diagram of Rate of Frequency Change Protection

Logic Diagram of Rate of Frequency Change Protection