Overview

In order to adjust its functions to the application, the Siprotec devices requires some data about the power system. The necessary settings can be found in the “Power system data” under General as well as in the Measuring points.

For more detailed information on “Power-System Data”, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure of the Power-System Data

Structure of the Power System Data

Setting Parameters


Setting parameters for MP disconnection

Addr. Parameter C Setting Options Default Setting
MP disconnection
_:8881:173 CT 3-phase:Current check   inactive
active
active
_:8881:112 CT 3-phase:I< threshold 1 A @ 100 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 100 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A

General setting parameters

Addr. Parameter C Setting Options Default Setting
General
_:2311:101 General:Phase sequence   ABC
ACB
ABC

Setting parameters for Measuring Point I-3ph

Addr. Parameter C Setting Options Default Setting
General
_:8881:115 CT 3-phase:CT connec- tion   not assigned
3-phase + IN
3-phase
3-phase + IN-separate
3-phase, 2 primary CT
3ph,2prim.CT + IN-sep
2ph, 2p. CT + IN-sep
3-phase + IN
_:8881:127 CT 3-phase:Tracking   inactive
active
active
_:8881:130 CT 3-phase:Measuring- point ID   0 to 100 0
CT phases
_:8881:101 CT 3-phase:Rated primary current   1.0 A to 100000.0 A 1000.0 A
_:8881:102 CT 3-phase:Rated secon- dary current   1 A
5 A
1 A
_:8881:117 CT 3-phase:Current range   1.6 x IR
100 x IR
50 x IR
100 x IR
_:8881:118 CT 3-phase:Internal CT type   CT protection
CT measurement
CT protection
CT measurement
CT Process bus
CT protection
_:8881:116 CT 3-phase:Neutr.point in dir.of ref.obj   no
yes
yes
_:8881:114 CT 3-phase:Inverted phases   none
AC
BC
AB
none
_:8881:107 CT 3-phase:CT error changeover   1.00 to 10.00 1.00
_:8881:108 CT 3-phase:CT error A   0.5 % to 50.0 % 5.0 %
_:8881:109 CT 3-phase:CT error B   0.5 % to 50.0 % 15.0 %
CT IN
_:8881:104 CT 3-phase:Rated primary current   1.0 A to 100000.0 A 1000.0 A
_:8881:105 CT 3-phase:Rated secon- dary current   1 A
5 A
1 A
_:8881:119 CT 3-phase:Current range   1.6 x IR
100 x IR
50 x IR
100 x IR
_:8881:120 CT 3-phase:Internal CT type   CT protection
CT measurement
CT protection
CT measurement
CT Process bus
CT protection
CT 1
_:3841:103 CT 1:Magnitude correc- tion   0.010 to 10.000 1.000
_:3841:117 CT 1:Phase   I A
I B
I C
IN
INsens
Ix
 
CT 2
_:3842:103 CT 2:Magnitude correc- tion   0.010 to 10.000 1.000
_:3842:117 CT 2:Phase   I A
I B
I C
IN
INsens
Ix
 
CT 3
_:3843:103 CT 3:Magnitude correc- tion   0.010 to 10.000 1.000
_:3843:117 CT 3:Phase   I A
I B
I C
IN
INsens
Ix
 
CT 4
_:3844:103 CT 4:Magnitude correc- tion   0.010 to 10.000 1.000
_:3844:117 CT 4:Phase   I A
I B
I C
IN
INsens
Ix
 
Brk.wire det.
_:5581:1 Brk.wire det.:Mode   off
on
test
off
Supv. balan. I
_:2491:1 Supv. balan. I:Mode   off
on
test
off
_:2491:101 Supv. balan. I:Release threshold 1 A @ 100 Irated 0.030 A to 35.000 A 0.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 2.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 2.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 2.500 A
_:2491:102 Supv. balan. I:Threshold min/max   0.10 to 0.95 0.50
_:2491:6 Supv. balan. I:Delay failure indication   0.00 s to 100.00 s 5.00 s
Supv. ph.seq.I
_:2551:1 Supv. ph.seq.I:Mode   off
on
test
off
_:2551:6 Supv. ph.seq.I:Delay failure indication   0.00 s to 100.00 s 5.00 s
Supv. sum I
_:2431:1 Supv. sum I:Mode   off
on
test
off
_:2431:102 Supv. sum I:Threshold 1 A @ 100 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 100 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A
_:2431:101 Supv. sum I:Slope factor   0.00 to 0.95 0.10
_:2431:6 Supv. sum I:Delay failure indication   0.00 s to 100.00 s 5.00 s
Supv.ADC sum I
_:2401:1 Supv.ADC sum I:Mode   off
on
test
off
Saturat. det.
_:17731:1 Saturat. det.:Mode   off
on
on
_:17731:101 Saturat. det.:CT satura- tion threshold 1 A @ 100 Irated 1.200 A to 100.000 A 8.000 A
5 A @ 100 Irated 6.00 A to 500.00 A 40.00 A
1 A @ 50 Irated 1.200 A to 50.000 A 8.000 A
5 A @ 50 Irated 6.00 A to 250.00 A 40.00 A
1 A @ 1.6 Irated 0.040 A to 1.600 A 8.000 A
5 A @ 1.6 Irated 0.200 A to 8.000 A 40.000 A

Setting parameters for Measuring Point I-1ph

Addr. Parameter C Setting Options Default Setting
General
_:2311:101 General:Rated primary current   1.0 A to 100000.0 A 1000.0 A
_:2311:102 General:Rated secondary current   1 A
5 A
1 A
_:2311:103 General:Current range   1.6 x IR
100 x IR
50 x IR
100 x IR
_:2311:104 General:Internal CT type   CT protection
CT measurement
CT Process bus
CT protection
_:2311:116 General:Term. 1,3,5,7 in dir. of obj.   no
yes
yes
_:2311:105 General:Tracking   inactive
active
inactive
_:2311:130 General:Measuring-point ID   0 to 100 0
CT 1
_:3841:103 CT 1:Magnitude correc- tion   0.010 to 10.000 1.000
_:3841:117 CT 1:Phase   I A
I B
I C
IN
INsens
Ix
 

Setting parameters for Measuring Point V-3ph

Addr. Parameter C Setting Options Default Setting
General
_:8911:101 VT 3-phase:Rated primary voltage   0.200 kV to 1200.000 kV 400.000 kV
_:8911:102 VT 3-phase:Rated secon- dary voltage   80 V to 230 V 100 V
_:8911:103 VT 3-phase:Matching ratio Vph / VN   0.10 to 9.99 1.73
_:8911:104 VT 3-phase:VT connec- tion   not assigned
3 ph-to-gnd volt. + VN
3 ph-to-gnd voltages
3 ph-to-ph volt. + VN
3 ph-to-ph voltages
3 ph-to-gnd volt. + VN
_:8911:106 VT 3-phase:Inverted phases   none
AC
BC
AB
none
_:8911:111 VT 3-phase:Tracking   inactive
active
active
_:8911:130 VT 3-phase:Measuring- point ID   0 to 100 0
VT 1
_:3811:103 VT 1:Magnitude correc- tion   0.010 to 10.000 1.000
_:3811:108 VT 1:Phase   V A
V B
V C
V AB
V BC
V CA
VN
Vx
VCB
 
VT 2
_:3812:103 VT 2:Magnitude correc- tion   0.010 to 10.000 1.000
_:3812:108 VT 2:Phase   V A
V B
V C
V AB
V BC
V CA
VN
Vx
VCB
 
VT 3
_:3813:103 VT 3:Magnitude correc- tion   0.010 to 10.000 1.000
_:3813:108 VT 3:Phase   V A
V B
V C
V AB
V BC
V CA
VN
Vx
VCB
 
VT 4
_:3814:103 VT 4:Magnitude correc- tion   0.010 to 10.000 1.000
_:3814:108 VT 4:Phase   V A
V B
V C
V AB
V BC
V CA
VN
Vx
VCB
 
Supv. balan. V
_:2521:1 Supv. balan. V:Mode   off
on
test
off
_:2521:101 Supv. balan. V:Release threshold   0.300 V to 170.000 V 50.000 V
_:2521:102 Supv. balan. V:Threshold min/max   0.58 to 0.95 0.75
_:2521:6 Supv. balan. V:Delay failure indication   0.00 s to 100.00 s 5.00 s
Supv. ph.seq.V
_:2581:1 Supv. ph.seq.V:Mode   off
on
test
off
_:2581:6 Supv. ph.seq.V:Delay failure indication   0.00 s to 100.00 s 5.00 s
Supv. sum V
_:2461:1 Supv. sum V:Mode   off
on
test
off
_:2461:3 Supv. sum V:Threshold   0.300 V to 170.000 V 25.000 V
_:2461:6 Supv. sum V:Delay failure indication   0.00 s to 100.00 s 5.00 s
VT miniatureCB
_:2641:101 VT minia- tureCB:Response time   0.00 s to 0.03 s 0.00 s

Setting parameters for Measuring Point V-1ph

Addr. Parameter C Setting Options Default Setting
General
_:2311:101 General:Rated primary voltage   0.200 kV to 1200.000 kV 400.000 kV
_:2311:102 General:Rated secondary voltage   80 V to 340 V 100 V
_:2311:108 General:Matching ratio Vph / VN   0.10 to 9.99 1.73
_:2311:103 General:Tracking   inactive
active
inactive
_:2311:130 General:Measuring-point ID   0 to 100 0
VT 1
_:3811:103 VT 1:Magnitude correc- tion   0.010 to 10.000 1.000
_:3811:108 VT 1:Phase   V A
V B
V C
V AB
V BC
V CA
VN
Vx
VCB
VN broken-delta
 
_:3811:107 VT 1:Sequence number device   1 to 2147483647 2147483647
VT miniatureCB
_:2641:101 VT minia- tureCB:Response time   0.00 s to 0.03 s 0.00 s

Logic Diagrams & highlights


Polarity of Current Transformers

Polarity of Current Transformers

Transmission Behavior of the Current Transformer

Transmission Behavior of the Current Transformer

Setting Recommendations for Current Transformer Data

Setting Recommendations for Current Transformer Data

Possible Disconnection of Measuring Point for the Line Differential Protection

Possible Disconnection of Measuring Point for the Line Differential Protection

Possible Disconnection of Measuring Point for the Feeder Protection

Possible Disconnection of Measuring Point for the Feeder Protection

Connection to 3 Phase Current Transformers (Zero-Sequence Current to be Calculated)

Connection to 3 Phase Current Transformers (Zero-Sequence Current to be Calculated)

Connection to 3 Phase Current Transformers and a Measured Zero-Sequence Current (Current in Common Return Conductor)

Connection to 3 Phase Current Transformers and a Measured Zero-Sequence Current (Current in Common Return Conductor)

Connection to 3 Phase Current Transformers and a Cable Type Current Transformer for Sensitive Ground-Fault Detection

Connection to 3 Phase Current Transformers and a Cable Type Current Transformer for Sensitive Ground-Fault Detection

Connection to 3 Phase Current Transformers and a Measured Ground Current from a Complete Holmgreen Connection

Connection to 3 Phase Current Transformers and a Measured Ground Current from a Complete Holmgreen Connection

Connection to 3 Phase Current Transformers and a Measured Residual Current from the Current-Transformer Neutral Point of the Respective Parallel Line (for Parallel-Line Compensation)

Connection to 3 Phase Current Transformers and a Measured Residual Current from the Current-Transformer Neutral Point of the Respective Parallel Line (for Parallel-Line Compensation)

Connection to 3 Phase Current Transformers and a Measured Ground Current via the Neutral-Point Current Transformer of a Grounded Power Transformer

Connection to 3 Phase Current Transformers and a Measured Ground Current via the Neutral-Point Current Transformer of a Grounded Power Transformer

Connection to a 2 Phase Current Transformers – for Isolated or Resonant-Grounded Systems Only

Connection to a 2 Phase Current Transformers – for Isolated or Resonant-Grounded Systems Only

Connection to 2 Phase Current Transformers and a Cable Type Current Transformer for Sensitive Ground-Fault Detection – for Isolated or Resonant-Grounded Systems Only

Connection to 2 Phase Current Transformers and a Cable Type Current Transformer for Sensitive Ground-Fault Detection – for Isolated or Resonant-Grounded Systems Only

Connection to 3 Phase Current Transformers and an Additional Current Transformer in the Neutral Point of a Grounded Power Transformer

Connection to 3 Phase Current Transformers and an Additional Current Transformer in the Neutral Point of a Grounded Power Transformer

Current Transformer Connection for High-Impedance Differential Protection (for Example, a Power Transformer, in Preparation)

Current Transformer Connection for High-Impedance Differential Protection (for Example, a Power Transformer, in Preparation)

Connection to 3 Phase Current Transformers in the Neutral Point of a Generator and a Cable Type Current Transformer for Sensitive Ground-Fault Detection of the Line

Connection to 3 Phase Current Transformers in the Neutral Point of a Generator and a Cable Type Current Transformer for Sensitive Ground-Fault Detection of the Line

Current-Transformer Connection for High-Impedance Differential Protection (Example: Power Transformer)

Current-Transformer Connection for High-Impedance Differential Protection (Example: Power Transformer)

Connection to 3 Star-Connected Voltage Transformers

Connection to 3 Star-Connected Voltage Transformers

Connection to 3 Star-Connected Voltage Transformers and to the Broken-Delta Winding

Connection to 3 Star-Connected Voltage Transformers and to the Broken-Delta Winding

Connection to 3 Star-Connected Voltage Transformers and to the Broken-Delta Winding of a Separate Voltage Transformer (for Example Busbar)

Connection to 3 Star-Connected Voltage Transformers and to the Broken-Delta Winding of a Separate Voltage Transformer (for Example Busbar)

Connection to 3 Star-Connected Voltage Transformers and to the Phase-to-Phase Voltage of a Busbar Voltage Transformer (for Example for Synchrocheck Applications)

Connection to 3 Star-Connected Voltage Transformers and to the Phase-to-Phase Voltage of a Busbar Voltage Transformer (for Example for Synchrocheck Applications)

Connection to V-Connected Voltage Transformer (Delta-Connected Device Input Transformer) and Connection to the Phase-to-Phase Voltage of a Busbar Voltage Transformer

Connection to V-Connected Voltage Transformer (Delta-Connected Device Input Transformer) and Connection to the Phase-to-Phase Voltage of a Busbar Voltage Transformer

Connection to V-Connected Voltage Transformer (Delta-Connected Device Input Transformer) and Connection to the Broken-Delta Winding of a Busbar Voltage Transformer

Connection to V-Connected Voltage Transformer (Delta-Connected Device Input Transformer) and Connection to the Broken-Delta Winding of a Busbar Voltage Transformer

Connection to a 1-Pole Insulated Voltage Transformer (Phase-to-Ground Voltage)

Connection to a 1-Pole Insulated Voltage Transformer (Phase-to-Ground Voltage)

Connection to 3 Star-Connected Voltage Transformers

Connection to 3 Star-Connected Voltage Transformers

Connection to 3 Star-Connected Voltage Transformers and to the Broken-Delta Winding of a Separate Voltage Transformer (for Example Busbar)

Connection to 3 Star-Connected Voltage Transformers and to the Broken-Delta Winding of a Separate Voltage Transformer (for Example Busbar)

Connection to 3 Star-Connected Voltage Transformers and to the Phase-to-Phase Voltage of a Busbar Voltage Transformer (for Example for Synchrocheck Applications)

Connection to 3 Star-Connected Voltage Transformers and to the Phase-to-Phase Voltage of a Busbar Voltage Transformer (for Example for Synchrocheck Applications)

Connection to a 1-Pole Insulated Voltage Transformer (Phase-to-Ground Voltage)

Connection to a 1-Pole Insulated Voltage Transformer (Phase-to-Ground Voltage)

Connection Example for a 1 1/2 Circuit-Breaker Layout

Connection Example for a 1 1/2 Circuit-Breaker Layout