Siemens / Power swing blocking function _ Setting & highlights _ SI5017

Table of Contents

Overview

The “Power swing blocking” detects power swings, evaluates the impedances per phase accordingly, checks the impedance trajectory on a continual basis, reports the power-swing detection per phase, blocks the selected zones of the distance protection in case of power swings, detects 1-phase, 2-phase, and 3-phase short circuits during a power swing and then cancels the blocking for the specific phase, works during a 1-pole dead time, activates only when the distance-protection function is active , does not generate tripping of the out-of-step condition; a separate out-of-step protection function is available for this purpose.

For more detailed information on “Power swing blocking”, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Power Swing Blocking Together with the Distance Protection Function

Power swing Blocking Together with the Distance Protection Function

Setting Parameters


Setting parameters for Power swing blocking

Addr. Parameter C Setting Options Default Setting
Power-Swing Blocking
_:1 68 P.swing blk:Mode   off
on
test
off
_:103 68 P.swing blk:Max. blocking time   0.00 s to 60.00 s; ∞ -1 s
_:102 68 P.swing blk:Zones to be blocked   Setting options depend on configuration  

Logic Diagrams & highlights


Power Swings

Power Swings

Impedance Vectors During a Power Swing and During a Short Circuit

Impedance Vectors During a Power Swing and During a Short Circuit

Operating Range for the Power-Swing Detection for Polygonal and MHO Characteristic

Operating Range for the Power-Swing Detection for Polygonal and MHO Characteristic

Power-Swing Blocking Logic

Power-Swing Blocking Logic