Overview

The “Power protection (P,Q) 3-Phase” function is used to detect whether the active or reactive power rises above or drops below a set threshold, monitor agreed power limits and output warning indications, detect both active and reactive power feedback in the power systems or on electric machines, detect machines (motors, generators) running without load and output an indication to shut them down, and be integrated into any automation solution, for example, to monitor very specific power limits (further logical processing in CFC).

For more detailed information on “Power protection (P,Q) 3-Phase” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of thePower protection (P,Q) 3-Phase Function

Logical Combination of Operate Indications in CFC

Logical Combination of Operate Indications in CFC

Setting Parameters


Setting parameters of the function

Addr. Parameter C Setting Options Default Setting
Power P> 1
_:6241:1 Power P> 1:Mode   off
on
test
off
_:6241:2 Power P> 1:Operate & flt.rec. blocked   no
yes
no
_:6241:104 Power P> 1:Measured value   power of phase A
power of phase B
power of phase C
positive seq. power
positive seq. power
_:6241:3 Power P> 1:Threshold   -200.0 % to 200.0 % 80.0 %
_:6241:101 Power P> 1:Dropout ratio   0.90 to 0.99 0.95
_:6241:103 Power P> 1:Tilt power characteristic   -89.0 ° to 89.0 ° 0.0 °
_:6241:7 Power P> 1:Dropout delay   0.00 s to 60.00 s 0.00 s
_:6241:6 Power P> 1:Operate delay   0.00 s to 60.00 s 1.00 s
Power P< 1
_:6271:1 Power P< 1:Mode   off
on
test
off
_:6271:2 Power P< 1:Operate & flt.rec. blocked   no
yes
no
_:6271:105 Power P< 1:Measured value   power of phase A
power of phase B
power of phase C
positive seq. power
positive seq. power
_:6271:3 Power P< 1:Threshold   -200.0 % to 200.0 % 5.0 %
_:6271:101 Power P< 1:Dropout ratio   1.01 to 1.10 1.05
_:6271:103 Power P< 1:Tilt power char- acteristic   -89.0 ° to 89.0 ° 0.0 °
_:6271:7 Power P< 1:Dropout delay   0.00 s to 60.00 s 0.00 s
_:6271:6 Power P< 1:Operate delay   0.00 s to 60.00 s 1.00 s
Power Q> 1
_:6301:1 Power Q> 1:Mode   off
on
test
off
_:6301:2 Power Q> 1:Operate & flt.rec. blocked   no
yes
no
_:6301:105 Power Q> 1:Measured value   power of phase A
power of phase B
power of phase C
positive seq. power
positive seq. power
_:6301:3 Power Q> 1:Threshold   -200.0 % to 200.0 % 70.0 %
_:6301:101 Power Q> 1:Dropout ratio   0.90 to 0.99 0.95
_:6301:103 Power Q> 1:Tilt power characteristic   -89.0 ° to 89.0 ° 0.0 °
_:6301:7 Power Q> 1:Dropout delay   0.00 s to 60.00 s 0.00 s
_:6301:6 Power Q> 1:Operate delay   0.00 s to 60.00 s 1.00 s
Power Q< 1
_:6331:1 Power Q< 1:Mode   off
on
test
off
_:6331:2 Power Q< 1:Operate & flt.rec. blocked   no
yes
no
_:6331:105 Power Q< 1:Measured value   power of phase A
power of phase B
power of phase C
positive seq. power
positive seq. power
_:6331:3 Power Q< 1:Threshold   -200.0 % to 200.0 % -30.0 %
_:6331:101 Power Q< 1:Dropout ratio   0.90 to 0.99 0.95
_:6331:103 Power Q< 1:Tilt power characteristic   -89.0 ° to 89.0 ° 0.0 °
_:6331:7 Power Q< 1:Dropout delay   0.00 s to 60.00 s 0.00 s
_:6331:6 Power Q< 1:Operate delay   0.00 s to 60.00 s 1.00 s

Logic Diagrams & highlights


Logic Diagram of the Active Power Stage (Stage Type: Power P<)

Logic Diagram of the Active Power Stage (Stage Type: Power P<)

Tilt-Power Characteristic

Tilt-Power Characteristic

Logic Diagram of the Reactive Power Stage (Stage Type: Power Q<)

Logic Diagram of the Reactive Power Stage (Stage Type: Power Q<)

Tilt-Power Characteristic

Tilt-Power Characteristic

Pickup Values and Characteristic Curves

Pickup Values and Characteristic Curves