Siemens / Power plant disconnection protection (ANSI 37 (-dP)) _ Setting & highlights _ SI5084

Table of Contents

Overview

The “Power plant disconnection protection” function detects external short circuits in the vicinity of the power plant (line, busbar) and opens the high-voltage circuit breaker if the fault duration is long. It also protects the stator winding from excessively long short-circuit current stress.

For more detailed information on “Power plant disconnection protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Function

Setting Parameters


Setting parameters for Power plant disconnection protection

Addr. Parameter C Setting Options Default Setting
General
_:18451:1 Stage 1:Mode   off
on
test
off
_:18451:2 Stage 1:Operate & flt.rec. blocked   no
yes
no
_:18451:101 Stage 1:Threshold dP1<   -100.00 % to -30.00 % -70.00 %
_:18451:102 Stage 1:Threshold P1>   50.00 % to 100.00 % 60.00 %
_:18451:7 Stage 1:Dropout delay   0.00 s to 60.00 s 0.50 s
_:18451:103 Stage 1:Threshold P1<   0.00 % to 60.00 % 30.00 %
_:18451:3 Stage 1:Threshold I> 1 A @ 100 Irated 0.030 A to 35.000 A 1.300 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.300 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.300 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.500 A
_:18451:104 Stage 1:Threshold Vph- ph<   0.300 V to 175.000 V 70.000 V
_:18451:106 Stage 1:Characteristic curve   no
yes
yes
_:18451:6 Stage 1:Operate delay   0.00 s to 60.00 s 0.15 s

Logic Diagrams & highlights


History of the Rotor Angle for Short Circuit near the Power Plant

History of the Rotor Angle for Short Circuit near the Power Plant

Basic Structure of Power-Plant Disconnection

Basic Structure of Power-Plant Disconnection

Logic Diagram for Release of dP Measurement

Logic Diagram for Release of dP Measurement

Logic Diagram of the Function

Logic Diagram of the Function

Connection Example for the Generator-Stator Function Group

Connection Example for the Generator-Stator Function Group

Connection Example for the Voltage-Current 3-Phase Function Group

Connection Example for the Voltage-Current 3-Phase Function Group