Siemens / Positive sequence overcurrent protection (ANSI 50/51) _ Setting & highlights _ SI5028

Table of Contents

Overview

The “Positive sequence overcurrent protection” function detects short circuits in electric equipment. It can be applied when the zero-sequence current or negative-sequence current should not influence the tripping, for example, on the tertiary delta winding of an auto transformer.

For more detailed information on “Positive sequence overcurrent protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Positive sequence overcurrent protection Function

Setting Parameters


Setting parameters for Stage with Definite-Time Characteristic Curve

Addr. Parameter C Setting Options Default Setting
Definite-T 1
_:20581:1 Definite-T 1:Mode   off
on
test
off
_:20581:2 Definite-T 1:Operate & flt.rec. blocked   no
yes
no
_:20581:3 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:20581:104 Definite-T 1:Blk. w. inrush curr. detect.   no
yes
no
_:20581:6 Definite-T 1:Operate delay   0.00 s to 60.00 s 0.50 s
Definite-T 2
_:20582:1 Definite-T 2:Mode   off
on
test
off
_:20582:2 Definite-T 2:Operate & flt.rec. blocked   no
yes
no
_:20582:3 Definite-T 2:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:20582:104 Definite-T 2:Blk. w. inrush curr. detect.   no
yes
no
_:20582:6 Definite-T 2:Operate delay   0.00 s to 60.00 s 0.50 s

Setting parameters for Stage with Inverse-Time Characteristic Curve

Addr. Parameter C Setting Options Default Setting
Inverse-T #
_:1 Inverse-T #:Mode   off
on
test
off
_:2 Inverse-T #:Operate & flt.rec. blocked   no
yes
no
_:3 Inverse-T #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:104 Inverse-T #:Blk. w. inrush curr. detect.   no
yes
no
_:105 Inverse-T #:Type of character. curve   ANSI long-time inv.
ANSI short-time inv.
ANSI extremely inv.
ANSI very inverse
ANSI normal inverse
ANSI moderately inv.
ANSI definite inverse
IEC normal inverse
IEC very inverse
IEC extremely inv.
IEC long-time inverse
IEC normal inverse
_:106 Inverse-T #:Reset   instantaneous
disk emulation
disk emulation
_:107 Inverse-T #:Time dial   0.05 to 15.00 1.00

Logic Diagrams & highlights


Logic Diagram of the Stage Definite-Time Positive-Sequence Overcurrent Protection

Logic Diagram of the Stage Definite-Time Positive-Sequence Overcurrent Protection

Application Example: Auto Transformer with Tertiary Delta Winding

Application Example: Auto Transformer with Tertiary Delta Winding

Logic Diagram of the Inverse-Time Positive-Sequence Overcurrent Protection

Logic Diagram of the Inverse-Time Positive-Sequence Overcurrent Protection