GE / Phase undervoltage (ANSI 27P, IEC PTUV) _ Element settings & highlights _ GU8069

Table of Contents

Overview

The “Phase undervoltage” element is used to give a time-delay operating characteristic versus the applied fundamental voltage (phase-toground or phase-to-phase for wye VT connection, or phase-to-phase for delta VT connection) or as a definite time element. The element resets instantaneously if the applied voltage exceeds the dropout voltage.

For more detailed information on “Phase undervoltage” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
All except B90, C30, T35 4725 Phase Undervoltage 1 Function 0 to 1 1 F102 0 (Disabled)
" 4726 Phase Undervoltage 1 Signal Source 0 to 5 1 F167 0 (SRC 1)
" 4727 Phase Undervoltage 1 Pickup 0.004 to 3 pu 0.001 F001 1000
" 4728 Phase Undervoltage 1 Curve 0 to 1 1 F111 0 (Definite Time)
" 4729 Phase Undervoltage 1 Delay 0 to 600 s 0.01 F001 100
" 472A Phase Undervoltage 1 Minimum Voltage 0 to 3 pu 0.001 F001 100
" 472B Phase Undervoltage 1 Block 0 to 4294967295 1 F300 0
" 472D Phase Undervoltage 1 Target 0 to 2 1 F109 0 (Self-reset)
" 472E Phase Undervoltage 1 Events 0 to 1 1 F102 0 (Disabled)
" 472F Phase Undervoltage 1 Measurement Mode 0 to 1 1 F186 0 (Phase to Ground)
" 4730 Reserved (6 items) 0 to 1 1 F001 0
" 4736 …Repeated for Phase Undervoltage 2          
" 4747 …Repeated for Phase Undervoltage 3          
B30 4758 …Repeated for Phase Undervoltage 4          
" 4769 …Repeated for Phase Undervoltage 5          
" 477A …Repeated for Phase Undervoltage 6          
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F111 0 = Definite Time, 1 = Inverse Time
F167 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6
F168 0 = Disabled, 1 = Adapt. 2nd, 2 = Trad. 2nd