Overview
The “Phase time overcurrent” element can provide a specified time-delay operating characteristic versus the applied current or be used as a simple definite time element. The phase current input quantities can be programmed as fundamental phasor magnitude or total waveform RMS magnitude as required by the application.
For more detailed information on “Phase time overcurrent” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.
To see other supported elements, click here.
Setting Parameters
Modbus memory map for Setting parameters
Products | Hex address | Register name | Range | Units | Step | Format | Default |
B30, C60, C70, C95, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60, T35, T60 | 334B | Phase TOC 1 Function | 0 to 1 | — | 1 | F102 | 0 (Disabled) |
" | 334C | Phase TOC 1 Signal Source | 0 to 5 | — | 1 | F167 | 0 (SRC 1) |
" | 334D | Phase TOC 1 Input | 0 to 1 | — | 1 | F122 | 0 (Phasor) |
" | 334E | Phase TOC 1 Pickup | 0.02 to 30 | pu | 0.001 | F001 | 1000 |
" | 334F | Phase TOC 1 Curve | 0 to 16 | — | 1 | F103 | 0 (IEEE Mod Inv) |
" | 3350 | Phase TOC 1 Multiplier | 0 to 600 | — | 0.01 | F001 | 100 |
" | 3351 | Phase TOC 1 Reset | 0 to 1 | — | 1 | F104 | 0 (Instantaneo us) |
" | 3352 | Phase TOC 1 Voltage Restraint | 0 to 1 | — | 1 | F102 | 0 (Disabled) |
" | 3353 | Phase TOC 1 Block For Each Phase (3 items) | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 3359 | Phase TOC 1 Target | 0 to 2 | — | 1 | F109 | 0 (Self-reset) |
" | 335A | Phase TOC 1 Events | 0 to 1 | — | 1 | F102 | 0 (Disabled) |
" | 335B | Reserved (3 items) | 0 to 1 | — | 1 | F001 | 0 |
" | 335E | …Repeated for Phase TOC 2 | |||||
" | 3371 | …Repeated for Phase TOC 3 | |||||
B30, C60, C70, C95, D60, F35, F60, L30, L60, L90, M60, N60, T35, T60 | 3384 | …Repeated for Phase TOC 4 | |||||
B30, C60, C70, C95, F35, F60, L90, M60, N60, T35, T60 | 3397 | …Repeated for Phase TOC 5 | |||||
" | 33AA | …Repeated for Phase TOC 6 | |||||
B30 | 33BD | …Repeated for Phase TOC 7 | |||||
" | 33D0 | …Repeated for Phase TOC 8 | |||||
" | 33000 | …Repeated for Phase TOC 9 | |||||
" | 33F6 | …Repeated for Phase TOC 10 | |||||
" | 3409 | …Repeated for Phase TOC 11 | |||||
" | 341C | …Repeated for Phase TOC 12 | |||||
" | 342F | …Repeated for Phase TOC 13 | |||||
" | 3442 | …Repeated for Phase TOC 14 | |||||
" | 3455 | …Repeated for Phase TOC 15 | |||||
" | 3468 | …Repeated for Phase TOC 16 | |||||
" | 347B | …Repeated for Phase TOC 17 | |||||
" | 348E | …Repeated for Phase TOC 18 | |||||
" | 34A1 | …Repeated for Phase TOC 19 | |||||
" | 34B4 | …Repeated for Phase TOC 20 | |||||
F102 | 0 = Disabled, 1 = Enabled | ||||||
F103 | 0 = IEEE Mod Inv, 1 = IEEE Very Inv, 2 = IEEE Ext Inv, 3 = IEC Curve A, 4 = IEC Curve B, 5 = IEC Curve C, 6 = IEC Short Inv, 7 = IAC Ext Inv, 9 = IAC Inverse, 10 = IAC Short Inv, 11 = I2t, 12 = Definite Time, 13 = FlexCurve A, 14 = FlexCurve B, 15 = FlexCurve C, 16 = FlexCurve D | ||||||
F104 | 0 = Instantaneous, 1 = Timed | ||||||
F109 | 0 = Self-reset, 1 = Latched, 2 = Disabled | ||||||
F122 | 0 = Phasor, 1 = RMS | ||||||
F167 | 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6 | ||||||