Table of Contents

GE / Phase time overcurrent (ANSI 51P, IEC PTOC) _ Element settings & highlights _ GU8044

Table of Contents

Overview

The “Phase time overcurrent” element can provide a specified time-delay operating characteristic versus the applied current or be used as a simple definite time element. The phase current input quantities can be programmed as fundamental phasor magnitude or total waveform RMS magnitude as required by the application.

For more detailed information on “Phase time overcurrent” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
B30, C60, C70, C95, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60, T35, T60 334B Phase TOC 1 Function 0 to 1 1 F102 0 (Disabled)
" 334C Phase TOC 1 Signal Source 0 to 5 1 F167 0 (SRC 1)
" 334D Phase TOC 1 Input 0 to 1 1 F122 0 (Phasor)
" 334E Phase TOC 1 Pickup 0.02 to 30 pu 0.001 F001 1000
" 334F Phase TOC 1 Curve 0 to 16 1 F103 0 (IEEE Mod
Inv)
" 3350 Phase TOC 1 Multiplier 0 to 600 0.01 F001 100
" 3351 Phase TOC 1 Reset 0 to 1 1 F104 0
(Instantaneo us)
" 3352 Phase TOC 1 Voltage Restraint 0 to 1 1 F102 0 (Disabled)
" 3353 Phase TOC 1 Block For Each Phase (3 items) 0 to 4294967295 1 F300 0
" 3359 Phase TOC 1 Target 0 to 2 1 F109 0 (Self-reset)
" 335A Phase TOC 1 Events 0 to 1 1 F102 0 (Disabled)
" 335B Reserved (3 items) 0 to 1 1 F001 0
" 335E …Repeated for Phase TOC 2          
" 3371 …Repeated for Phase TOC 3          
B30, C60, C70, C95, D60, F35, F60, L30, L60, L90, M60, N60, T35, T60 3384 …Repeated for Phase TOC 4          
B30, C60, C70, C95, F35, F60, L90, M60, N60, T35, T60 3397 …Repeated for Phase TOC 5          
" 33AA …Repeated for Phase TOC 6          
B30 33BD …Repeated for Phase TOC 7          
" 33D0 …Repeated for Phase TOC 8          
" 33000 …Repeated for Phase TOC 9          
" 33F6 …Repeated for Phase TOC 10          
" 3409 …Repeated for Phase TOC 11          
" 341C …Repeated for Phase TOC 12          
" 342F …Repeated for Phase TOC 13          
" 3442 …Repeated for Phase TOC 14          
" 3455 …Repeated for Phase TOC 15          
" 3468 …Repeated for Phase TOC 16          
" 347B …Repeated for Phase TOC 17          
" 348E …Repeated for Phase TOC 18          
" 34A1 …Repeated for Phase TOC 19          
" 34B4 …Repeated for Phase TOC 20          
F102 0 = Disabled, 1 = Enabled
F103 0 = IEEE Mod Inv, 1 = IEEE Very Inv, 2 = IEEE Ext Inv, 3 = IEC Curve A, 4 = IEC Curve B, 5 = IEC Curve C, 6 = IEC Short Inv, 7 = IAC Ext Inv, 9 = IAC Inverse, 10 = IAC Short Inv, 11 = I2t, 12 = Definite Time, 13 = FlexCurve A, 14 = FlexCurve B, 15 = FlexCurve C, 16 = FlexCurve D
F104 0 = Instantaneous, 1 = Timed
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F122 0 = Phasor, 1 = RMS
F167 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6

Logics & highlights


Overcurrent curve types

Overcurrent curve types

IEEE curves

IEEE curves
IEEE curve trip times (in seconds)
IEEE curve trip times (in seconds)

IEC curves

IEC curve trip times (in seconds)
IEC curve trip times (in seconds)

IAC curves

GE type IAC curve trip times
GE type IAC curve trip times

I2t curves


FlexCurves


Definite time curve


Phase time overcurrent voltage restraint characteristic

Phase time overcurrent voltage restraint characteristic

Phase time overcurrent 1 logic


error: Content is protected !!