Overview

The “Phase sequence switchover” function enables correct execution of the protection of the device and supervision functions, independently of the phase sequence of the phases in a system or system section.

For more detailed information on “Phase sequence switchover” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Phase sequence switchover Function

Setting Parameters


Setting parameters of the function

Addr. Parameter C Setting Options Default Setting
General
_:101 General:Phase sequence   ABC
ACB
ABC
General
_:101 VT 3-phase:Rated primary voltage   0.20 kV to 1200.00 kV 400.00 kV
_:102 VT 3-phase:Rated secondary voltage   80 V to 230 V 100 V
_:103 VT 3-phase:Matching ratio Vph / VN   0.10 to 9.99 1.73
_:104 VT 3-phase:VT connection   3 ph-to-gnd volt. + VN
3 ph-to-gnd voltages
3 ph-to-ph volt. + VN
3 ph-to-ph voltages
3 ph-to-gnd volt. + VN
_:106 VT 3-phase:Inverted phases   none
AC
BC
AB
none
_:111 VT 3-phase:Tracking   inactive
active
active
_:107 VT 3-phase:Measuring- point ID   0 to 100 0

Logic Diagrams & highlights


Vector with Different Phase Sequences

Vector with Different Phase Sequences

Phase Sequence Switchover

Phase Sequence Switchover

Application Example for Phase-Rotation Reversal in a Pump Station

Application Example for Phase-Rotation Reversal in a Pump Station

Measured Values for Changed-Over Phases

Measured Values for Changed-Over Phases