GE / Phase overvoltage (ANSI 59P, IEC PTOV) _ Element settings & highlights _ GU8070

Table of Contents

Overview

A “Phase overvoltage” element is used as an instantaneous element with no intentional time delay or as a definite time element. The input voltage is the phase-to-phase voltage, either measured directly from delta-connected VTs or as calculated from phase-to-ground (wye) connected VTs.

For more detailed information on “Phase overvoltage” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
B30, C60, C70, C95, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60, T60 478B Phase Overvoltage 1 Function 0 to 1 1 F102 0 (Disabled)
" 478C Phase Overvoltage 1 Source 0 to 5 1 F167 0 (SRC 1)
" 478D Phase Overvoltage 1 Pickup 0.004 to 3 pu 0.001 F001 1000
" 478E Phase Overvoltage 1 Delay 0 to 600 s 0.01 F001 100
" 478F Phase Overvoltage 1 Reset Delay 0 to 600 s 0.01 F001 100
" 4790 Phase Overvoltage 1 Block 0 to 4294967295 1 F300 0
" 4792 Phase Overvoltage 1 Target 0 to 2 1 F109 0 (Self-reset)
" 4793 Phase Overvoltage 1 Events 0 to 1 1 F102 0 (Disabled)
" 4794 …Repeated for Phase Overvoltage 2          
" 479D …Repeated for Phase Overvoltage 3          
B30 47A6 …Repeated for Phase Overvoltage 4          
" 47AF …Repeated for Phase Overvoltage 5          
" 47B8 …Repeated for Phase Overvoltage 6          
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F167 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6

Logics & highlights


Phase overvoltage logic

Phase overvoltage logic