Overview
The “Phase directional overcurrent” elements (one for each of phases A, B, and C) determine the phase current flow direction for steady state and fault conditions and can be used to control the operation of the phase overcurrent elements via the BLOCK inputs of these elements.
For more detailed information on “Phase directional overcurrent” elements, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.
To see other supported elements, click here.
Setting Parameters
Modbus memory map for Setting parametes
Products | Hex address | Register name | Range | Units | Step | Format | Default |
B30, C70, D30, D60, F60, G30, G60, L30, L60, L90, M60, N60, T60 | 4966 | Phase DIR 1 Function | 0 to 1 | — | 1 | F102 | 0 (Disabled) |
" | 4967 | Phase DIR 1 Source | 0 to 5 | — | 1 | F167 | 0 (SRC 1) |
" | 4968 | Phase DIR 1 Block | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 496A | Phase DIR 1 ECA | 0 to 359 | — | 1 | F001 | 30 |
" | 496B | Phase DIR 1 Pol V Threshold | 0.004 to 3 | pu | 0.001 | F001 | 700 |
" | 496C | Phase DIR 1 Block Overcurrent | 0 to 1 | — | 1 | F126 | 0 (No) |
" | 496D | Phase DIR 1 Target | 0 to 2 | — | 1 | F109 | 0 (Self-reset) |
" | 496E | Phase DIR 1 Events | 0 to 1 | — | 1 | F102 | 0 (Disabled) |
" | 496F | Phase DIR 1 CT Source | 0 to 5 | — | 1 | F677 | 0 (None) |
" | 4970 | Phase DIR 1 VT Source | 0 to 1 | — | 1 | F167 | 0 (SRC 1) |
" | 4971 | Reserved (6 items) | 0 to 1 | — | 1 | F001 | 0 |
B30, C70, D30, D60, F60, L30, L60, L90, M60, N60, T60 | 4977 | …Repeated for Phase DIR 2 | |||||
N60, T60 | 4988 | …Repeated for Phase DIR 3 | |||||
B30 | 4999 | …Repeated for Phase DIR 4 | |||||
" | 49AA | …Repeated for Phase DIR 5 | |||||
" | 49BB | …Repeated for Phase DIR 6 | |||||
F102 | 0 = Disabled, 1 = Enabled | ||||||
F109 | 0 = Self-reset, 1 = Latched, 2 = Disabled | ||||||
F167 | 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6 | ||||||
F677 | 0 = None, 1 = SRC 1, 2 = SRC 2, 3 = SRC 3, 4 = SRC 4, 5 = SRC 5, 6 = SRC 6, 7 = SRC 7 | ||||||