Overview

The “Permissive underreaching transfer trip” scheme (PUTT) uses an under-reaching zone 1 distance element to key a transfer trip signal(s) to the remote terminal(s) where it is supervised by an over-reaching zone 2 distance element. For proper operation, the zone 1 and 2 phase and ground distance elements must be enabled, configured, and set per rules of distance relaying.

For more detailed information on “Permissive underreaching transfer trip” scheme (PUTT), refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
D60, L90 4275 PUTT 1P Scheme Function 0 to 1 1 F102 0 (Disabled)
" 4276 PUTT 1P Rx Pickup Delay 0 to 65.535 s 0.001 F001 0
" 4277 PUTT 1P Seal In Delay 0 to 65.535 s 0.001 F001 0
" 4278 PUTT 1P Number of Communication Bits 0 to 2 1 F198 0 (1)
" 4279 PUTT 1P Rx1 0 to 4294967295 1 F300 0
" 427B PUTT 1P Rx2 0 to 4294967295 1 F300 0
" 427D PUTT 1P Rx3 0 to 4294967295 1 F300 0
" 427F PUTT 1P Rx4 0 to 4294967295 1 F300 0
" 4281 PUTT 1P Target 0 to 2 1 F109 0 (Self-reset)
" 4282 PUTT 1P Event 0 to 1 1 F102 0 (Disabled)
" 4283 PUTT 1P Scheme Block 0 to 4294967295 1 F300 0
" 4285 Reserved (5 items) 0 to 1 1 F001 0
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F198 0 = 1, 1 = 2, 2 = 4

Logics & highlights


PUTT scheme logic

PUTT scheme logic