Siemens / Overvoltage protection with zero sequence voltage/residual voltage (ANSI 59N) _ Setting & highlights _ SI5043

Table of Contents

Overview

The “Overvoltage protection with zero sequence voltage/residual voltage” function detects ground faults in isolated or arc-suppression-coil-grounded systems, determines the phase affected by the ground fault and works with electrical machines to detect ground faults in the stator winding.

For more detailed information on “Overvoltage protection with zero sequence voltage/residual voltage” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Overvoltage protection with zero sequence voltage/residual voltage Function

Setting Parameters


Setting parameters of the function

Addr. Parameter C Setting Options Default Setting
Stage 1
_:331:1 Stage 1:Mode   off
on
test
off
_:331:2 Stage 1:Operate & flt.rec. blocked   no
yes
no
_:331:10 Stage 1:Blk. by meas.- volt. failure   no
yes
yes
_:331:109 Stage 1:Detection of faulty phase   no
yes
no
_:331:8 Stage 1:Method of measurement   fundamental comp.
fund. comp. long filter
RMS value
fundamental comp.
_:331:3 Stage 1:Threshold   0.300 V to 340.000 V 30.000 V
_:331:4 Stage 1:Dropout ratio   0.90 to 0.99 0.95
_:331:107 Stage 1:Pickup delay   0.00 s to 320.00 s 0.00 s
_:331:6 Stage 1:Operate delay   0.00 s to 60.00 s 3.00 s
_:331:101 Stage 1:V> healthy ph- to-gnd volt.   0.300 V to 200.000 V 75.000 V
_:331:104 Stage 1:V< faulty ph-to- gnd volt.   0.300 V to 200.000 V 40.000 V

Logic Diagrams & highlights


Logic Diagram of an Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage Stage

Logic Diagram of an Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage Stage