Siemens / Overvoltage protection with positive sequence voltage and compounding (ANSI 59) _ Setting & highlights _ SI5042

Table of Contents

Overview

The “Overvoltage protection with positive sequence voltage and compounding” function detects stationary overvoltages at the opposite line end.
On long, unloaded or weakly loaded transmission lines stationary overvoltages are caused by the capacitance per unit length (Ferranti effect). The overvoltage is present at the opposite line end in this case, but it can only be eliminated by switching off the local line end.

For more detailed information on “Overvoltage protection with positive sequence voltage and compounding” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Overvoltage protection with positive sequence voltage and compounding Function

Setting Parameters


Setting parameters of the function

Addr. Parameter C Setting Options Default Setting
Stage 1
_:241:1 Stage 1:Mode   off
on
test
off
_:241:2 Stage 1:Operate & flt.rec. blocked   no
yes
no
_:241:3 Stage 1:Threshold   0.300 V to 200.000 V 65.000 V
_:241:4 Stage 1:Dropout ratio   0.90 to 0.99 0.95
_:241:6 Stage 1:Operate delay   0.00 s to 60.00 s 3.00 s
Stage 2
_:242:1 Stage 2:Mode   off
on
test
off
_:242:2 Stage 2:Operate & flt.rec. blocked   no
yes
no
_:242:3 Stage 2:Threshold   0.300 V to 200.000 V 75.000 V
_:242:4 Stage 2:Dropout ratio   0.90 to 0.99 0.95
_:242:6 Stage 2:Operate delay   0.00 s to 60.00 s 0.50 s

Logic Diagrams & highlights


Logic Diagram of an “Overvoltage Protection with Positive-Sequence Voltage and Compounding” stage

Logic Diagram of an "Overvoltage Protection with Positive-Sequence Voltage and Compounding" stage

Equivalent Circuit Diagram of the Line