Overview
The “Overvoltage protection with negative sequence voltage” function is used to monitor the power system and electric machines for voltage unbalances and establish a release criterion of overcurrent protection for unbalanced faults.
For more detailed information on “Overvoltage protection with negative sequence voltage” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported functions, click here.
Structure/Embedding of the Function
Setting Parameters
General Setting parameters
Addr. | Parameter | C | Setting Options | Default Setting |
General | ||||
_:2311:10 | General:Blk. by meas.- volt. failure | no yes |
yes | |
_:2311:101 | General:Measuring window | 1 cycles to 10 cycles | 1 cycles | |
Setting parameters for Stage with Negative-Sequence Voltage
Addr. | Parameter | C | Setting Options | Default Setting |
Stage 1 | ||||
_:271:1 | Stage 1:Mode | off on test |
off | |
_:271:2 | Stage 1:Operate & flt.rec. blocked | no yes |
no | |
_:271:3 | Stage 1:Threshold | 0.300 V to 200.000 V | 5.800 V | |
_:271:4 | Stage 1:Dropout ratio | 0.90 to 0.99 | 0.95 | |
_:271:6 | Stage 1:Operate delay | 0.00 s to 60.00 s | 3.00 s | |
Stage 2 | ||||
_:272:1 | Stage 2:Mode | off on test |
off | |
_:272:2 | Stage 2:Operate & flt.rec. blocked | no yes |
no | |
_:272:3 | Stage 2:Threshold | 0.300 V to 200.000 V | 9.000 V | |
_:272:4 | Stage 2:Dropout ratio | 0.90 to 0.99 | 0.95 | |
_:272:6 | Stage 2:Operate delay | 0.00 s to 60.00 s | 0.50 s | |