Overview
The “Overvoltage protection with any voltage” function detects any 1-phase overvoltages and is intended for special applications.
For more detailed information on “Overvoltage protection with any voltage” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported functions, click here.
Structure/Embedding of the Function
Setting Parameters
Setting parameters of the function
Addr. | Parameter | C | Setting Options | Default Setting |
Stage 1 | ||||
_:391:1 | Stage 1:Mode | off on test |
off | |
_:391:2 | Stage 1:Operate & flt.rec. blocked | no yes |
no | |
_:391:9 | Stage 1:Measured value | VA measured VB measured VC measured VAB calculated VBC calculated VCA calculated V0 calculated |
VA measured | |
_:391:8 | Stage 1:Method of measure- ment | fundamental comp. RMS value |
fundamental comp. | |
_:391:3 | Stage 1:Threshold | 0.300 V to 340.000 V | 110.000 V | |
_:391:4 | Stage 1:Dropout ratio | 0.90 to 0.99 | 0.95 | |
_:391:6 | Stage 1:Operate delay | 0.00 s to 60.00 s | 3.00 s | |
Stage 2 | ||||
_:392:1 | Stage 2:Mode | off on test |
off | |
_:392:2 | Stage 2:Operate & flt.rec. blocked | no yes |
no | |
_:392:9 | Stage 2:Measured value | VA measured VB measured VC measured VAB measured VBC measured VCA measured VAB calculated VBC calculated VCA calculated V0 calculated |
VA measured | |
_:392:8 | Stage 2:Method of measure- ment | fundamental comp. RMS value |
fundamental comp. | |
_:392:3 | Stage 2:Threshold | 0.300 V to 340.000 V | 130.000 V | |
_:392:4 | Stage 2:Dropout ratio | 0.90 to 0.99 | 0.95 | |
_:392:6 | Stage 2:Operate delay | 0.00 s to 60.00 s | 0.50 s | |