Siemens / Overvoltage protection with any voltage (ANSI 59) _ Setting & highlights _ SI5044

Table of Contents

Overview

The “Overvoltage protection with any voltage” function detects any 1-phase overvoltages and is intended for special applications.

For more detailed information on “Overvoltage protection with any voltage” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Overvoltage protection with any voltage Function

Setting Parameters


Setting parameters of the function

Addr. Parameter C Setting Options Default Setting
Stage 1
_:391:1 Stage 1:Mode   off
on
test
off
_:391:2 Stage 1:Operate & flt.rec. blocked   no
yes
no
_:391:9 Stage 1:Measured value   VA measured
VB measured
VC measured
VAB calculated
VBC calculated
VCA calculated
V0 calculated
VA measured
_:391:8 Stage 1:Method of measure- ment   fundamental comp.
RMS value
fundamental comp.
_:391:3 Stage 1:Threshold   0.300 V to 340.000 V 110.000 V
_:391:4 Stage 1:Dropout ratio   0.90 to 0.99 0.95
_:391:6 Stage 1:Operate delay   0.00 s to 60.00 s 3.00 s
Stage 2
_:392:1 Stage 2:Mode   off
on
test
off
_:392:2 Stage 2:Operate & flt.rec. blocked   no
yes
no
_:392:9 Stage 2:Measured value   VA measured
VB measured
VC measured
VAB measured
VBC measured
VCA measured
VAB calculated
VBC calculated
VCA calculated
V0 calculated
VA measured
_:392:8 Stage 2:Method of measure- ment   fundamental comp.
RMS value
fundamental comp.
_:392:3 Stage 2:Threshold   0.300 V to 340.000 V 130.000 V
_:392:4 Stage 2:Dropout ratio   0.90 to 0.99 0.95
_:392:6 Stage 2:Operate delay   0.00 s to 60.00 s 0.50 s

Logic Diagrams & highlights


Logic Diagram of an Overvoltage Protection with Any Voltage Stage

Logic Diagram of an Overvoltage Protection with Any Voltage Stage