Overview

The “Overvoltage protection with 3 phase voltage” function is used to monitor the permissible voltage range, protect equipment (for example, plant components, machines, etc.) against damages caused by overvoltage and decouple systems (for example, wind power supply).

For more detailed information on “Overvoltage protection with 3 phase voltage”, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Overvoltage protection with 3 phase voltage Function

Setting Parameters


Setting parameters for Stage with Definite-Time Characteristic Curve

Addr. Parameter C Setting Options Default Setting
General
_:2311:101 General:Stabilization counter   0 to 10 0
Definite-T 1
_:181:1 Definite-T 1:Mode   off
on
test
off
_:181:2 Definite-T 1:Operate & flt.rec. blocked   no
yes
no
_:181:9 Definite-T 1:Measured value   phase-to-ground
phase-to-phase
phase-to-phase
_:181:8 Definite-T 1:Method of measurement   fundamental comp.
RMS value
fundamental comp.
_:181:101 Definite-T 1:Pickup mode   1 out of 3
3 out of 3
1 out of 3
_:181:3 Definite-T 1:Threshold   0.300 V to 340.000 V 110.000 V
_:181:4 Definite-T 1:Dropout ratio   0.90 to 0.99 0.95
_:181:6 Definite-T 1:Operate delay   0.00 s to 300.00 s 3.00 s
Definite-T 2
_:182:1 Definite-T 2:Mode   off
on
test
off
_:182:2 Definite-T 2:Operate & flt.rec. blocked   no
yes
no
_:182:9 Definite-T 2:Measured value   phase-to-ground
phase-to-phase
phase-to-phase
_:182:8 Definite-T 2:Method of measurement   fundamental comp.
RMS value
fundamental comp.
_:182:101 Definite-T 2:Pickup mode   1 out of 3
3 out of 3
1 out of 3
_:182:3 Definite-T 2:Threshold   0.300 V to 340.000 V 130.000 V
_:182:4 Definite-T 2:Dropout ratio   0.90 to 0.99 0.95
_:182:6 Definite-T 2:Operate delay   0.00 s to 300.00 s 0.50 s

Setting parameters for Stage with Inverse-Time Characteristic Curve

Addr. Parameter C Setting Options Default Setting
Inverse-T #
_:1 Inverse-T #:Mode   off
on
test
off
_:2 Inverse-T #:Operate & flt.rec. blocked   no
yes
no
_:9 Inverse-T #:Measured value   phase-to-ground
phase-to-phase
phase-to-phase
_:8 Inverse-T #:Method of measurement   fundamental comp.
RMS value
fundamental comp.
_:108 Inverse-T #:Pickup mode   1 out of 3
3 out of 3
1 out of 3
_:3 Inverse-T #:Threshold   0.300 V to 340.000 V 110.000 V
_:101 Inverse-T #:Pickup factor   1.00 to 1.20 1.10
_:102 Inverse-T #:Charact. constant k   0.00 to 300.00 1.00
_:103 Inverse-T #:Charact. constant α   0.010 to 5.000 1.000
_:104 Inverse-T #:Charact. constant c   0.000 to 5.000 0.000
_:105 Inverse-T #:Time dial   0.05 to 15.00 1.00
_:106 Inverse-T #:Additional time delay   0.00 s to 60.00 s 0.00 s
_:107 Inverse-T #:Reset time   0.00 s to 60.00 s 0.00 s

Logic Diagrams & highlights


Logic Diagram of the Definite-Time Overvoltage Protection with 3-Phase Voltage

Logic Diagram of the Definite-Time Overvoltage Protection with 3-Phase Voltage

Logic Diagram of the Inverse-Time Overvoltage Protection with 3-Phase Voltage

Logic Diagram of the Inverse-Time Overvoltage Protection with 3-Phase Voltage

Operate Curve of Inverse-Time Characteristic

Operate Curve of Inverse-Time Characteristic