Overview
The “Overvoltage protection with 3 phase voltage” function is used to monitor the permissible voltage range, protect equipment (for example, plant components, machines, etc.) against damages caused by overvoltage and decouple systems (for example, wind power supply).
For more detailed information on “Overvoltage protection with 3 phase voltage”, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported functions, click here.
Structure/Embedding of the Function
Setting Parameters
Setting parameters for Stage with Definite-Time Characteristic Curve
Addr. | Parameter | C | Setting Options | Default Setting |
General | ||||
_:2311:101 | General:Stabilization counter | 0 to 10 | 0 | |
Definite-T 1 | ||||
_:181:1 | Definite-T 1:Mode | off on test |
off | |
_:181:2 | Definite-T 1:Operate & flt.rec. blocked | no yes |
no | |
_:181:9 | Definite-T 1:Measured value | phase-to-ground phase-to-phase |
phase-to-phase | |
_:181:8 | Definite-T 1:Method of measurement | fundamental comp. RMS value |
fundamental comp. | |
_:181:101 | Definite-T 1:Pickup mode | 1 out of 3 3 out of 3 |
1 out of 3 | |
_:181:3 | Definite-T 1:Threshold | 0.300 V to 340.000 V | 110.000 V | |
_:181:4 | Definite-T 1:Dropout ratio | 0.90 to 0.99 | 0.95 | |
_:181:6 | Definite-T 1:Operate delay | 0.00 s to 300.00 s | 3.00 s | |
Definite-T 2 | ||||
_:182:1 | Definite-T 2:Mode | off on test |
off | |
_:182:2 | Definite-T 2:Operate & flt.rec. blocked | no yes |
no | |
_:182:9 | Definite-T 2:Measured value | phase-to-ground phase-to-phase |
phase-to-phase | |
_:182:8 | Definite-T 2:Method of measurement | fundamental comp. RMS value |
fundamental comp. | |
_:182:101 | Definite-T 2:Pickup mode | 1 out of 3 3 out of 3 |
1 out of 3 | |
_:182:3 | Definite-T 2:Threshold | 0.300 V to 340.000 V | 130.000 V | |
_:182:4 | Definite-T 2:Dropout ratio | 0.90 to 0.99 | 0.95 | |
_:182:6 | Definite-T 2:Operate delay | 0.00 s to 300.00 s | 0.50 s | |
Setting parameters for Stage with Inverse-Time Characteristic Curve
Addr. | Parameter | C | Setting Options | Default Setting |
Inverse-T # | ||||
_:1 | Inverse-T #:Mode | off on test |
off | |
_:2 | Inverse-T #:Operate & flt.rec. blocked | no yes |
no | |
_:9 | Inverse-T #:Measured value | phase-to-ground phase-to-phase |
phase-to-phase | |
_:8 | Inverse-T #:Method of measurement | fundamental comp. RMS value |
fundamental comp. | |
_:108 | Inverse-T #:Pickup mode | 1 out of 3 3 out of 3 |
1 out of 3 | |
_:3 | Inverse-T #:Threshold | 0.300 V to 340.000 V | 110.000 V | |
_:101 | Inverse-T #:Pickup factor | 1.00 to 1.20 | 1.10 | |
_:102 | Inverse-T #:Charact. constant k | 0.00 to 300.00 | 1.00 | |
_:103 | Inverse-T #:Charact. constant α | 0.010 to 5.000 | 1.000 | |
_:104 | Inverse-T #:Charact. constant c | 0.000 to 5.000 | 0.000 | |
_:105 | Inverse-T #:Time dial | 0.05 to 15.00 | 1.00 | |
_:106 | Inverse-T #:Additional time delay | 0.00 s to 60.00 s | 0.00 s | |
_:107 | Inverse-T #:Reset time | 0.00 s to 60.00 s | 0.00 s | |