Siemens / Overfrequency protection (ANSI 81O) _ Setting & highlights _ SI5053

Table of Contents

Overview

The “Overfrequency protection” function detects overfrequencies in electrical power systems or machines, monitors the frequency band and output failure indications, disconnects generating units when the power frequency is critical, and provides additional turbine protection if the speed limiter fails.

For more detailed information on “Overfrequency protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Overfrequency protection Function

Setting Parameters


Setting parameters for Overfrequency protection Function

Addr. Parameter C Setting Options Default Setting
General
_:2311:101 General:Minimum voltage   3.000 V to 175.000 V 37.500 V
_:2311:109 General:Dropout differ- ential   20 mHz to 2000 mHz 20 mHz
Stage 1
_:31:1 Stage 1:Mode   off
on
test
off
_:31:2 Stage 1:Operate & flt.rec. blocked   no
yes
no
_:31:3 Stage 1:Threshold Overfrequency A 40.00 Hz to 90.00 Hz 51.50 Hz
Overfrequency B 40.00 Hz to 70.00 Hz
_:31:6 Stage 1:Operate delay   0.00 s to 600.00 s 10.00 s
Stage 2
_:32:1 Stage 2:Mode   off
on
test
off
_:32:2 Stage 2:Operate & flt.rec. blocked   no
yes
no
_:32:3 Stage 2:Threshold Overfrequency A 40.00 Hz to 90.00 Hz 54.00 Hz
Overfrequency B 40.00 Hz to 70.00 Hz
_:32:6 Stage 2:Operate delay   0.00 s to 600.00 s 5.00 s

Logic Diagrams & highlights


Logic Diagram of the Overfrequency Protection Stage

Logic Diagram of the Overfrequency Protection Stage