GE / Overfrequency (ANSI 81O) _ Element settings & highlights _ GU8224

Table of Contents

Overview

The steady-state frequency of a power system is an indicator of the existing balance between the generated power and the load. Whenever this balance is disrupted through the disconnection of significant load or the isolation of a part of the system that has a surplus of generation, the effect is an increase in frequency. For more detailed information on “Overfrequency” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
C60, C95, D60, F60, G30, G60, L90, M60, N60, T60 4034 Overfrequency 1 Function 0 to 1 1 F102 0 (Disabled)
" 4035 Overfrequency 1 Block 0 to 4294967295 1 F300 0
" 4037 Overfrequency 1 Source 0 to 5 1 F167 0 (SRC 1)
" 4038 Overfrequency 1 Pickup 20 to 65 Hz 0.01 F001 6050
" 4039 Overfrequency 1 Pickup Delay 0 to 65.535 s 0.001 F001 500
" 403A Overfrequency 1 Reset Delay 0 to 65.535 s 0.001 F001 500
" 403B Overfrequency 1 Target 0 to 2 1 F109 0 (Self-reset)
" 403C Overfrequency 1 Events 0 to 1 1 F102 0 (Disabled)
" 403D Reserved (4 items) 0 to 1 1 F001 0
" 4041 …Repeated for Overfrequency 2          
" 404E …Repeated for Overfrequency 3          
" 405B …Repeated for Overfrequency 4          
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F167 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6

Logics & highlights


Overfrequency logic

Overfrequency logic