Table of Contents

Siemens / Overcurrent protection, 1-phase (ANSI 50N/51N) _ Setting & highlights _ SI5031

Table of Contents

Overview

The “Overcurrent protection, 1-phase” function detects and monitors the current measured in a transformer neutral point grounding. It can operate as sensitive tank leakage protection, detects and monitors the circulating current between the neutral points of 2 capacitor banks, and switches off high-current faults instantaneously.

For more detailed information on “Overcurrent protection, 1-phase” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding the Function Overcurrent Protection, 1-Phase – Advanced

Structure/Embedding the Function Overcurrent protection, 1-Phase – Advanced

Structure/Embedding the Function Overcurrent Protection, 1-Phase – Basic

Structure/Embedding the Function Overcurrent protection, 1-Phase – Basic

Setting Parameters


Setting parameters for Stage with Definite-Time Characteristic Curve

Addr. Parameter C Setting Options Default Setting
Definite-T 1
_:12661:1 Definite-T 1:Mode   off
on
test
off
_:12661:2 Definite-T 1:Operate & flt.rec. blocked   no
yes
no
_:12661:27 Definite-T 1:Blk. w. inrush curr. detect.   no
yes
no
_:12661:102 Definite-T 1:Blk. w. 2nd harm. 1ph det.   no
yes
no
_:12661:8 Definite-T 1:Method of measurement   fundamental comp.
RMS value
fundamental comp.
_:12661:3 Definite-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:12661:6 Definite-T 1:Operate delay   0.00 s to 60.00 s 0.30 s

Setting parameters for Stage with Inverse-Time Characteristic Curve

Addr. Parameter C Setting Options Default Setting
Inverse-T 1
_:12691:1 Inverse-T 1:Mode   off
on
test
off
_:12691:2 Inverse-T 1:Operate & flt.rec. blocked   no
yes
no
_:12691:27 Inverse-T 1:Blk. w. inrush curr. detect.   no
yes
no
_:12691:102 Inverse-T 1:Blk. w. 2nd harm. 1ph det.   no
yes
no
_:12691:8 Inverse-T 1:Method of measurement   fundamental comp.
RMS value
fundamental comp.
_:12691:3 Inverse-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:12691:108 Inverse-T 1:Type of char- acter. curve   ANSI long-time inv.
ANSI short-time inv.
ANSI extremely inv.
ANSI very inverse
ANSI normal inverse
ANSI moderately inv.
ANSI definite inverse
IEC normal inverse
IEC very inverse
IEC extremely inv.
IEC long-time inverse
IEC normal inverse
_:12691:109 Inverse-T 1:Reset   instantaneous
disk emulation
disk emulation
_:12691:101 Inverse-T 1:Time dial   0.05 to 15.00 1.00

Setting parameters for Stage with Inverse-Time Overcurrent Protection with Logarithmic-Inverse Characteristic Curve

Addr. Parameter C Setting Options Default Setting
Log.-inv.-T #
_:1 Log.-inv.-T #:Mode   off
on
test
off
_:2 Log.-inv.-T #:Operate & flt.rec. blocked   no
yes
no
_:27 Log.-inv.-T #:Blk. w. inrush curr. detect.   no
yes
no
_:102 Log.-inv.-T #:Blk. w. 2nd harm. 1ph det.   no
yes
no
_:8 Log.-inv.-T #:Method of measurement   fundamental comp.
RMS value
fundamental comp.
_:3 Log.-inv.-T #:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:6 Log.-inv.-T #:Time dial   0.000 s to 60.000 s 1.250 s
_:113 Log.-inv.-T #:Min. time of the curve   0.000 s to 60.000 s 1.200 s
_:114 Log.-inv.-T #:Max. time of the curve   0.000 s to 60.000 s 5.800 s
_:116 Log.-inv.-T #:Threshold multiplier   1.00 to 4.00 1.10
_:115 Log.-inv.-T #:Additional time delay   0.000 s to 60.000 s 0.000 s

Setting parameters for Stage with User-Defined Characteristic Curve

Addr. Parameter C Setting Options Default Setting
General
_:1 User curve #:Mode   off
on
test
off
_:2 User curve #:Operate & flt.rec. blocked   no
yes
no
_:27 User curve #:Blk. w. inrush curr. detect.   no
yes
no
_:102 User curve #:Blk. w. 2nd harm. 1ph det.   no
yes
no
_:8 User curve #:Method of measurement   fundamental comp.
RMS value
fundamental comp.
_:3 User curve #:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:110 User curve #:Reset   instantaneous
disk emulation
disk emulation
_:101 User curve #:Time dial   0.05 to 15.00 1.00

Setting parameters for Fast Stage

Addr. Parameter C Setting Options Default Setting
Fast stage #
_:1 Fast stage #:Mode   off
on
test
off
_:2 Fast stage #:Operate & flt.rec. blocked   no
yes
no
_:3 Fast stage #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 10.000 A
5 A @ 100 Irated 0.15 A to 175.00 A 50.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 10.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 50.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 10.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 50.000 A
_:4 Fast stage #:Dropout ratio   0.90 to 0.99 0.90
_:6 Fast stage #:Operate delay   0.00 s to 60.00 s 0.00 s

Logic Diagrams & highlights


Logic Diagram of the Definite-Time Overcurrent Protection, 1-Phase

Logic Diagram of the Definite-Time Overcurrent Protection, 1-Phase

Logic Diagram of the Inverse-Time Overcurrent Protection (1-Phase)

Logic Diagram of the Inverse-Time Overcurrent Protection (1-Phase)

Logic Diagram of the Logarithmic Inverse-Time Overcurrent Protection (1-Phase)

Logic Diagram of the Logarithmic Inverse-Time Overcurrent Protection (1-Phase)

Operate Curve of Logarithmic Inverse-Time Characteristic

Operate Curve of Logarithmic Inverse-Time Characteristic

Pickup Behavior and Dropout Behavior when Using a User-Defined Characteristic Curve

Pickup Behavior and Dropout Behavior when Using a User-Defined Characteristic Curve

Logic Diagram of the Fast Stage, 1-Phase

Logic Diagram of the Fast Stage, 1-Phase

Part-Logic Diagram on the Influence of Inrush-Current Detection Exemplified by the 1st Definite-Time Overcurrent Protection Stage

Part-Logic Diagram on the Influence of Inrush-Current Detection Exemplified by the 1st Definite-Time Overcurrent Protection Stage

Restricted Ground-Fault Protection According to the High-Impedance Principle

Restricted Ground-Fault Protection According to the High-Impedance Principle

Principle of the Restricted Ground-Fault Protection According to the High-Impedance Principle

Principle of the Restricted Ground-Fault Protection According to the High-Impedance Principle

Connection Diagram of the Restricted Ground-Fault Protection According to the High- Impedance Principle

Connection Diagram of the Restricted Ground-Fault Protection According to the High- Impedance Principle

Simplified Connection Diagram of a Layout for High-Impedance Restricted Ground-Fault Protection

Simplified Connection Diagram of a Layout for High-Impedance Restricted Ground-Fault Protection

Connection Diagram of the Restricted Ground-Fault Protection According to the High- Impedance Principle

Connection Diagram of the Restricted Ground-Fault Protection According to the High- Impedance Principle

Tank-Control Principle – Application Example: Tank Leakage Protection

Tank-Control Principle