Overview

The “Non-directional intermittent ground fault protection” function is used to protect against intermittent ground faults which occur, for example, in cables due to poor insulation or water ingress in cable joints.

For more detailed information on “Non-directional intermittent ground fault protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Non-directional intermittent ground fault protection Function

Setting Parameters


Setting parameters of the Function

Addr. Parameter C Setting Options Default Setting
Stage 1
_:11341:1 Stage 1:Mode   off
on
test
off
_:11341:2 Stage 1:Operate & flt.rec. blocked   no
yes
no
_:11341:3 Stage 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 100 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 5.000 A
_:11341:101 Stage 1:No. pickups till interm.GF   2 to 10 3
_:11341:102 Stage 1:Pickup extension time   0.00 s to 10.00 s 0.10 s
_:11341:103 Stage 1:Sum of extended PU times   0.00 s to 100.00 s 20.00 s
_:11341:104 Stage 1:Reset time   1.00 s to 600.00 s 300.00 s

Logic Diagrams & highlights


Logic of the Non-Directional Intermittent Ground-Fault Protection

Logic of the Non-Directional Intermittent Ground-Fault Protection

Fault Detection of the Intermittent Ground-Fault Protection

Fault Detection of the Intermittent Ground-Fault Protection

Example of Selectivity Criteria of the Intermittent Ground-Fault Protection

Example of Selectivity Criteria of the Intermittent Ground-Fault Protection