GE / Neutral overvoltage (ANSI 59N, IEC PTOV) _ Element settings & highlights _ GU8071

Table of Contents

Overview

The “Neutral overvoltage” element is used to detect asymmetrical system voltage condition due to a ground fault or to the loss of one or two phases of the source. The element responds to the system neutral voltage (3V_0), calculated from the phase voltages.

For more detailed information on “Neutral overvoltage” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
All except B90, C30, N60, T35 5043 Neutral Overvoltage 1 Function 0 to 1 1 F102 0 (Disabled)
" 5044 Neutral Overvoltage 1 Signal Source 0 to 5 1 F167 0 (SRC 1)
" 5045 Neutral Overvoltage 1 Pickup 0.004 to 3 pu 0.001 F001 300
" 5046 Neutral Overvoltage 1 Pickup Delay 0 to 600 s 0.01 F001 100
" 5047 Neutral Overvoltage 1 Reset Delay 0 to 600 s 0.01 F001 100
" 5048 Neutral Overvoltage 1 Block 0 to 4294967295 1 F300 0
" 504A Neutral Overvoltage 1 Target 0 to 2 1 F109 0 (Self-reset)
" 504B Neutral Overvoltage 1 Events 0 to 1 1 F102 0 (Disabled)
" 504C Neutral Overvoltage 1 Curves 0 to 3 1 F116 0 (Definite Time)
" 504D Reserved (7 items) 0 to 65535 1 F001 0
" 5054 …Repeated for Neutral Overvoltage 2          
" 5065 …Repeated for Neutral Overvoltage 3          
B30 5076 …Repeated for Neutral Overvoltage 4          
" 5087 …Repeated for Neutral Overvoltage 5          
" 5098 …Repeated for Neutral Overvoltage 6          
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F116 0 = Definite Time, 1 = FlexCurve A, 2 = FlexCurve B, 3 = FlexCurve C
F167 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6