Overview

The “Negative sequence protection” function detects 1-phase or 2-phase short circuits in the electrical power system with clearly increased sensitivity compared to the classical overcurrent protection, protects electric machines during excessive unbalanced load, reports unbalanced load conditions in the electricity supply system, detects phase interruptions in the primary system, and locates short circuits or inversions in the connections to the current transformers.

For more detailed information on “Negative sequence protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Negative sequence protection Function

Setting Parameters


Setting parameters for Stage with Definite-Time Characteristic Curve

Addr. Parameter C Setting Options Default Setting
General
_:2311:106 General:Reference value   pos. seq. current
rated current
rated current
_:2311:107 General:Current limita- tion Imax   no
yes
no
_:2311:101 General:Maximum phase current 1 A @ 100 Irated 0.030 A to 35.000 A 10.000 A
5 A @ 100 Irated 0.15 A to 175.00 A 50.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 10.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 50.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 10.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 50.000 A
_:2311:104 General:Release current 1 A @ 100 Irated 0.030 A to 10.000 A 0.050 A
5 A @ 100 Irated 0.15 A to 50.00 A 0.25 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.050 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.25 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.050 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.250 A
Definite-T 1
_:1981:1 Definite-T 1:Mode   off
on
test
off
_:1981:2 Definite-T 1:Operate & flt.rec. blocked   no
yes
no
_:1981:3 Definite-T 1:Threshold   5.0 % to 999.9 % 10.0 %
_:1981:4 Definite-T 1:Dropout ratio   0.40 to 0.99 0.95
_:1981:104 Definite-T 1:Blk. w. inrush curr. detect.   no
yes
no
_:1981:101 Definite-T 1:Dropout delay   0.00 s to 60.00 s 0.00 s
_:1981:6 Definite-T 1:Operate delay   0.00 s to 60.00 s 1.50 s
Definite-T 2
_:1982:1 Definite-T 2:Mode   off
on
test
off
_:1982:2 Definite-T 2:Operate & flt.rec. blocked   no
yes
no
_:1982:3 Definite-T 2:Threshold   5.0 % to 999.9 % 65.0 %
_:1982:4 Definite-T 2:Dropout ratio   0.40 to 0.99 0.95
_:1982:104 Definite-T 2:Blk. w. inrush curr. detect.   no
yes
no
_:1982:101 Definite-T 2:Dropout delay   0.00 s to 60.00 s 0.00 s
_:1982:6 Definite-T 2:Operate delay   0.00 s to 60.00 s 0.50 s

Setting parameters for Stage with Inverse-Time Characteristic Curve

Addr. Parameter C Setting Options Default Setting
Inverse-T #
_:1 Inverse-T #:Mode   off
on
test
off
_:2 Inverse-T #:Operate & flt.rec. blocked   no
yes
no
_:3 Inverse-T #:Threshold   5.0 % to 999.9 % 10.0 %
_:104 Inverse-T #:Blk. w. inrush curr. detect.   no
yes
no
_:105 Inverse-T #:Type of character. curve      
_:106 Inverse-T #:Reset   instantaneous
disk emulation
disk emulation
_:107 Inverse-T #:Time dial   0.05 to 15.00 1.00

Logic Diagrams & highlights


Logic Diagram of the General Functionality

Logic Diagram of the General Functionality

Logic Diagram of the Stage Negative-Sequence Protection with Definite-Time Characteristic Curve

Logic Diagram of the Stage Negative-Sequence Protection with Definite-Time Characteristic Curve

Logic Diagram of the Negative-Sequence Protection with Inverse-Time Characteristic Curve

Logic Diagram of the Negative-Sequence Protection with Inverse-Time Characteristic Curve