GE / Negative sequence overvoltage (ANSI 59Q, IEC PTOV) _ Element settings & highlights _ GU8072

Table of Contents

Overview

Use the “Negative sequence overvoltage” element to detect loss of one or two phases of the source, a reversed phase sequence of voltage, or a non-symmetrical system voltage condition.

For more detailed information on “Negative sequence overvoltage” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
C70, D30, D60, F60, G30, G60, L30, L60, M60, T60 3FDC Negative Sequence Overvoltage 1 Function 0 to 1 1 F102 0 (Disabled)
" 3FDD Negative Sequence Overvoltage 1 Source 0 to 5 1 F167 0 (SRC 1)
" 3FDE Negative Sequence Overvoltage 1 Pickup 0.004 to 1.25 pu 0.001 F001 300
" 3FDF Negative Sequence Overvoltage 1 Pickup Delay 0 to 600 s 0.01 F001 50
" 3FE0 Negative Sequence Overvoltage 1 Reset Delay 0 to 600 s 0.01 F001 50
" 3FE1 Negative Sequence Overvoltage 1 Block 0 to 4294967295 1 F300 0
" 3FE3 Negative Sequence Overvoltage 1 Target 0 to 2 1 F109 0 (Self-reset)
" 3FE4 Negative Sequence Overvoltage 1 Events 0 to 1 1 F102 0 (Disabled)
" 3FE5 …Repeated for Negative Sequence Overvoltage 2          
" 3FEE …Repeated for Negative Sequence Overvoltage 3          
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F167 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6

Logics & highlights


Negative-sequence overvoltage logic