Overview

Negative sequence components are present in all types of fault condition. They can reach considerably high values during abnormal operation. The “Negative sequence overcurrent protection” is a definite time stage comparator function.

For more detailed information on “Negative sequence overcurrent protection” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Negative sequence overcurrent protection LCNSPTOC 46

Signals & Setting Parameters


LCNSPTOC Function block

LCNSPTOC Function block

LCNSPTOC Input signals

LCNSPTOC Input signals
Name Type Default Description
I3P GROUP SIGNAL Three phase group signal for current inputs
BLOCK BOOLEAN 0 Block overall function
BLKTR BOOLEAN 0 Block trip signal

LCNSPTOC Output signals

LCNSPTOC Output signals
Name Type Description
TRIP BOOLEAN Trip signal negative sequence over current protection
START BOOLEAN Start signal for negative sequence over current protection

LCNSPTOC Group settings (basic)

LCNSPTOC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off/On
I2> 3 – 2500 %IB 1 100 Negative sequence over current start value in % of IBase
tI2 0.000 – 60.000 s 0.001 0.000 Time delay to operate

LCNSPTOC Non group settings (basic)

LCNSPTOC Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

LCNSPTOC Monitored data

LCNSPTOC Monitored data
Name Type Values (Range) Unit Description
I2 Real A Neagative sequence current value

Technical Data


LCNSPTOC technical data

LCNSPTOC technical data