Siemens / Motor differential protection (ANSI 87M) _ Setting & highlights _ SI5076

Table of Contents

Overview

The “Motor differential protection” function detects ground faults and multiphase short circuits in motors, and also ground faults during the operation of motors using mains with a grounded neutral point.

For more detailed information on “Motor differential protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Function

Setting Parameters


Setting parameters for Motor differential protection

Addr. Parameter C Setting Options Default Setting
General
_:2311:186 General:Protection Mode   Transformer
Current node
Transformer
_:2311:100 General:Meas. gnd. current side 1   no
yes
no
_:2311:101 General:Meas. gnd. current side 2   no
yes
no
_:2311:102 General:Meas. gnd. current side 3   no
yes
no
_:2311:181 General:Meas. gnd. curr. autosides   no
with CT 1ph
with CT 3ph
no
_:2311:182 General:Meas. gnd. curr. comp.side   no
yes
no
_:2311:191 General:Reference side is   not assigned
Side 1
Side 2
Side 3
not assigned
_:2311:151 General:MU-ID Side 1
Mp3ph 1
  0 to 100 0
_:2311:152 General:MU-ID Side 1
Mp3ph 2
  0 to 100 0
_:2311:153 General:MU-ID Side 1
Mp3ph 3
  0 to 100 0
_:2311:154 General:MU-ID Side 1
Mp3ph 4
  0 to 100 0
_:2311:155 General:MU-ID Side 1 Mp1ph   0 to 100 0
_:2311:156 General:MU-ID Side 2
Mp3ph 1
  0 to 100 0
_:2311:157 General:MU-ID Side 2
Mp3ph 2
  0 to 100 0
_:2311:158 General:MU-ID Side 2
Mp3ph 3
  0 to 100 0
_:2311:159 General:MU-ID Side 2
Mp3ph 4
  0 to 100 0
_:2311:160 General:MU-ID Side 2 Mp1ph   0 to 100 0
_:2311:161 General:MU-ID Side 3
Mp3ph 1
  0 to 100 0
_:2311:162 General:MU-ID Side 3
Mp3ph 2
  0 to 100 0
_:2311:163 General:MU-ID Side 3
Mp3ph 3
  0 to 100 0
_:2311:164 General:MU-ID Side 3
Mp3ph 4
  0 to 100 0
_:2311:165 General:MU-ID Side 3 Mp1ph   0 to 100 0
_:2311:185 General:MU-ID Mp1ph   0 to 100 0
General
_:11041:1 I-DIFF:Mode   off
on
test
off
_:11041:2 I-DIFF:Operate & flt.rec. blocked   no
yes
no
_:11041:6 I-DIFF:Operate delay   0.00 s to 60.00 s 0.00 s
Operate curve
_:11041:3 I-DIFF:Threshold   0.05 I/IrObj to 2.00 I/IrObj 0.20 I/IrObj
_:11041:100 I-DIFF:Slope 1   0.00 to 0.80 0.30
_:11041:101 I-DIFF:Intersection 1 Irest   0.00 I/IrObj to 5.00 I/IrObj 0.67 I/IrObj
_:11041:102 I-DIFF:Slope 2   0.25 to 0.95 0.70
_:11041:103 I-DIFF:Intersection 2 Irest   1.00 I/IrObj to 20.00 I/IrObj 2.50 I/IrObj
Starting detection
_:11041:106 I-DIFF:Starting detection   no
yes
yes
_:11041:107 I-DIFF:Thresh. startup detection   0.1 I/IrObj to 2.0 I/IrObj 0.1 I/IrObj
_:11041:108 I-DIFF:Factor increasing char.   1.0 to 5.0 1.0
_:11041:109 I-DIFF:Max. perm. Start. time   0.1 s to 180.0 s 5.0 s
DC offset detection
_:11041:110 I-DIFF:Factor increasing char. DC   1.0 to 5.0 2.3
Ext. fault detection
_:11041:128 I-DIFF:Threshold add-on stabiliz.   1.00 I/IrObj to 20.00 I/IrObj 2.00 I/IrObj
_:11041:129 I-DIFF:Time of add-on stabiliz.   0.00 s to 5.00 s;∞ 0.30 s
_:11041:130 I-DIFF:Crossblk. time add- on st.   0.00 s to 2.00 s;∞ 0.30 s
I-DIFF fast
_:11071:1 I-DIFF fast:Mode   off
on
test
off
_:11071:3 I-DIFF fast:Threshold   0.5 I/IrObj to 35.0 I/IrObj 7.5 I/IrObj
_:11071:6 I-DIFF fast:Operate delay   0.00 s to 60.00 s 0.00 s
_:11071:100 I-DIFF fast:Operate & flt.rec. blocked   no
yes
no
I-DIFF unrestr
_:18002:1 I-DIFF unrestr:Mode   off
on
test
off
_:18002:3 I-DIFF unrestr:Threshold   0.5 I/IrObj to 35.0 I/IrObj 10.0 I/IrObj
_:18002:6 I-DIFF unrestr:Operate delay   0.00 s to 60.00 s 0.00 s
_:18002:100 I-DIFF unrestr:Operate & flt.rec. blocked   no
yes
no

Logic Diagrams & highlights


Basic Principle of Differential Protection Using the Example of 2 Sides

Basic Principle of Differential Protection Using the Example of 2 Sides

Current Stabilization

Current Stabilization

Principle Current Course in External Short Circuit and Temporary Current-Transformer Saturation on One Side

Principle Current Course in External Short Circuit and Temporary Current-Transformer Saturation on One Side

Logic Diagram of the Differential Protection Function

Logic Diagram of the Differential Protection Function

Operate Curve of the Differential Protection Function

Operate Curve of the Differential Protection Function

Amount Correction

Amount Correction

Calculation of differential protection currents

Calculation of differential protection currents

Pickup Characteristic of the Differential Protection

Pickup Characteristic of the Differential Protection

Increasing the Characteristic Curve after DC Detection

Increasing the Characteristic Curve after DC Detection

Logic DC Detection

Logic DC Detection

Logic Startup Detection

Logic Startup Detection

Characteristic-Curve Increase at Startup

Characteristic-Curve Increase at Startup

Trip Logic of I-DIFF

Trip Logic of I-DIFF

Instantaneous-Value Method calculations

Instantaneous-Value Method

I-DIFF Fast Characteristic Curve

I-DIFF Fast Characteristic Curve

Curve Plot for Internal Fault with Transformer Saturation (k= 0.65)

Curve Plot for Internal Fault with Transformer Saturation (k= 0.65)

Curve Plot for External Fault with Transformer Saturation (k= 0.65)

Curve Plot for External Fault with Transformer Saturation (k= 0.65)

Logic of the I-DIFF Fast Differential Protection Function

Logic of the I-DIFF Fast Differential Protection Function

Operate current calculation

Logic of the I-DIFF Fast Differential Protection Function

I-DIFF Unrestrained Characteristic Curve

I-DIFF Unrestrained Characteristic Curve

Logic of the I-DIFF Unrestrained Differential Protection Function

Logic of the I-DIFF Unrestrained Differential Protection Function

Overall Trip Logic

Overall Trip Logic

Connection Example

Connection Example