Siemens / “Motor diff” function group _ Setting & highlights _ SI5213

Table of Contents

Overview

The individual function-group types are stored in the “Motor diff” function group folder. The “Motor differential” function group contains the differential protection function and protection-function-relevant measured values. In the “Motor side” function group, all of the functions that are necessary for protecting and supervising a motor side can be used.

For more detailed information on “Motor diff” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported function groups, click here.


Function-Group Types Motor differential

Function-Group Types Motor differential

Function-Group Type Motor Differential


Structure of the Motor Differential Protection Function Group

Structure of the Motor Differential Protection Function Group

Generation of Pickup Indication of the Motor Differential Protection Function Group

Generation of Pickup Indication of the Motor Differential Protection Function Group

Generation of Operate Indication of the Motor Differential Protection Function Group

Generation of Operate Indication of the Motor Differential Protection Function Group

Function-Group Type Motor Side


Structure of the Motor Side Function Group

Structure of the Motor Side Function Group

Write-Protected Settings

Addr. Parameter C Range of Values Default Setting
Rated values
_:1781:14671:101 Motor rated current   1 A to 100 000 A 1000 A
Side data
_:1781:14611:130 Side number   not assigned
Side 1
Side 2
Side 3
not assigned
_:1781:14611:210 MI3ph1 usesMeasP with ID   0 to 100 0
_:1781:14611:211 MI3ph2 usesMeasP with ID   0 to 100 0
_:1781:14611:212 MI3ph3 usesMeasP with ID   0 to 100 0
_:1781:14611:213 MI3ph4 usesMeasP with ID   0 to 100 0
_:1781:14611:215 CT mismatch M I-3ph 1   0.010 to 100.000 0.000
_:1781:14611:216 CT mismatch M I-3ph 1 IN   0.010 to 100.000 0.000
_:1781:14611:217 CT mismatch M I-3ph 2   0.010 to 100.000 0.000
_:1781:14611:218 CT mismatch M I-3ph 2 IN   0.010 to 100.000 0.000
_:1781:14611:219 CT mismatch M I-3ph 3   0.010 to 100.000 0.000
_:1781:14611:220 CT mismatch M I-3ph 3 IN   0.010 to 100.000 0.000
_:1781:14611:221 CT mismatch M I-3ph 4   0.010 to 100.000 0.000
_:1781:14611:222 CT mismatch M I-3ph 4 IN   0.010 to 100.000 0.000

Settings

Addr. Parameter C Setting Options Default Setting
Rated values
_:1781:14671:103 General:Rated apparent power   0.20 MVA to 5000.00 MVA 692.82 MVA
_:1781:14671:102 General:Motor rated voltage   0.40 kVto 800.00 kV 400.00 kV
Measurements
_:1781:14611:158 Further settings:P, Q sign   not reversed
reversed
not reversed

Possible Operational Measured Values of the Motor Side Function Group

Possible Operational Measured Values of the Motor Side Function Group

Generation of Pickup Indication of the Motor Side Function Group

Generation of Pickup Indication of the Motor Side Function Group

Generation of Operate Indication of the Motor Side Function Group

Generation of Operate Indication of the Motor Side Function Group