Table of Contents

Schneider / MiCOM P821 T/J31 10E setting parameters & highlights (SC5012)

Table of Contents

Overview

MiCOM P821 is an advanced Breaker Failure relay with backup protection functions. It offers a range of protection functions, combined with extensive monitoring capacities to give you optimized efficiency and maximum control for your electric schemes. It is suitable for all voltage levels.

For more detailed information on “MiCOM P821” relays, refer to Schneider protection relays manuals.

To see other supported devices, click here.


Setting Parameters


Breaker Failure Protection Settings for Group1

Address Group Description Settings range Step Unit Format Default settings
0200 Setting group n°1 Breaker Failure 0-1 1 F24 0
0201   Threshold I< 5 to 400 1 In/100 F1 10
0202   TBF1 delay 0 to 4000 5 1/1000 s F1 10
0203   TBF2 delay 0 to 4000 5 1/10 F1 40
0204   1st stage Reset 0 – 1 1   F27 0
0205   End fault 0 – 1 1   F42 0
0206   I_DZ> threshold 5 – 400 1 In/100 F1 100
0207   DZ delay 0 to 40000 5 1/1000 s F1 10
0208   Pole Discrepancy 0 – 1 1   F43 0
0209   I_PD> Threshold 8 – 400 1 In/100 F1 80
020A   I_PD< Threshold 5 – 100 1 In/100 F1 40
020B   PD Delay 0 to 40000 5 1/1000 s F1 10
020C   Phase Breaker failure 0-1 1   F56 0
020D   Earth Breaker failure 0-1 1   F57 0
020E   I0< Threshold N: 5 to 400
S: 1 to 400
VS: 2 to 800
1 In/100
In/100
In/1000
F1 N: 10
S: 5
VS: 25
020F   Phase Delay stage 1 0 to 40000 5 1/1000 s F1  
0210   Phase Delay stage 2 0 to 40000 5 1/1000 s F1  
0211   CB Fail Neg. Seq. 0 to 1 1   F24  
0212   I2< BF 5 to 200 1 1/100 F1  
0213   Neg. Delay stage 1 0 to 40000 5 1/1000 s F1  
0214   Neg. Delay stage 2 0 to 40000 5 1/1000 s F1  
0215   CB unhealthy 0 to 1 1   F24  
0216   CB unh. stage 1 0 to 40000 5 1/1000 s F1  
0217   CB unh. stage 2 0 to 40000 5 1/1000 s F1  
0218   Ie DZ>threshold N: 5 to 400
S: 1 to 400
VS: 2 to 800
1 In/100
In/100
In/1000
F1  
0219   External Non I Reset by 0 to 2 1   F62  

Other Setting Parameters

Address Group Description Settings range Step Unit Format Default settings
0100 Remote settings Address 1 to 255 1 F1 1
0101   Language 0 to 7 F1
0102   Password characters 1 and 2 32 -127 1 F10 AA
0103   Password characters 3 and 4 32 -127 1 F10 AA
0104   Frequency 50-60 10 Hz F1 50
0105   Phase A Labelling L1 – A – R VTA   F25 A
0106   Phase B Labelling L2 – B – S VTA   F25 B
0107   Phase C Labelling L3 – C – T VTA   F25 C
0108   Earth Labelling N – E – o VTA   F25 N
0109   Default display 1-3 1 F26 1
010A   User reference (characters 1 and 2) 32-127 1   F10 AL
010B   User reference (characters 3 and 4) 32-127 1   F10 ST
010C   Fault number to be displayed 1-5 1   F49 5
010D   Configuration of the logic inputs validation edge   0   F11 0
010E   Reserved          
010F   Type of the logic inputs input voltage 0-1 1   F50 0
0110 CB supervision CB operation number   1   F1  
0111   CB operating time   1 1/10 sec F1  
0112 to 0113   San IA     An F18  
0113 to 0114   San IB     An F18  
0114 to 0115   San IC     An F18  
0118   Wiring security 0 – 1 1   F52  
0119   Relay to test 1 1 – 8 1   F53  
011A   Relay to test 1 1 – 8 1   F53  
011B to 011E   Reserved          
011F   Latched relays       F14  
120 Ratios Phase CT: primary value 1 to 50000 1   F14 1000
0121   Phase CT: secondary value 1 to 5 4   F1 1
0122 Trip relay allocation Trip relay functionality (word 1) 0 to 65535 1   F6  
0123 Latching Trip relay latching function (word 1) 0 to 255 1 10 V F8  
0124 Ratio Earth CT: primary value 1 to 50000 1   F1 1000
0125   Earth CT: secondary value 1 to 5 4   F1 1
0126   Trip relay functionality (word 2) 0 to 65535 1   F6’  
0127 Latching Trip relay latching function (word 2) 0 to 65535 1   F8’  
0128 to 012F   Reserved          
0130 Communication Baud rate 0 to 7 1 F4 6 = 19200 bauds
0131   Parity 0 to 2 1 F5 0 = without
0132   Data bits 0 to 1 1   F28 1 = 8 bits
0133   Number of stop bits 0 to 1 1 F29 0 = 1 stop bit
0134   Comm. Available 0 to 1 1 F30 1 = COM available
0135   Date Format 0 to 1 0   F48 0 = Private
0136   Reserved          
0137   AddressRear Port          
0138 to 013F   Reserved          
0140 Setting group Active setting group 1 to 2 1 F1 1
0141   Validation of instantaneous self resetting 0 to 1 1   F1 0
0142   Configuration of the change of the setting group 0 to 1 1   F47 1
0143   Configuration of Battery and RAM error alarms 0 to 1 1   F1 0
0144   conf. TS AC/DC visible          
0145 to 014F   Reserved          
0150 LEDs
configuration
LED 5 (Word 1)   1 F19 0
0151   LED 6 (Word 1)   1 F19  
0152   LED 7 (Word 1)   1 F19  
0153   LED 8 (Word 1)   1   F19  
0154   LED 5 (Word 2)   1   F19’  
0155   LED 6 (Word 2)   1   F19’  
0156   LED 7 (Word 2)   1   F19’  
0157   LED 8 (Word 2)   1   F19’ 0
0158   LED 5 (Word 3)       F19’’  
0159   LED 6 (Word 3)       F19’’  
015A   LED 7 (Word 3)       F19’’  
015B   LED 8 (Word 3)       F19’’  
015C to 015F   Reserved          
0160 Logic inputs configuration Logic input 1 (Word 1) VTA 1 F15 0
0161   Logic input 2 (Word 1) VTA 1 F15 0
0162   Logic input 3 (Word 1) VTA 1 F15 0
0163   Logic input 4 (Word 1) VTA 1 F15 0
0164   Logic input 5 (Word 1) VTA 1 F15 0
019A   Logic input 1 (Word 2) VTA 1 F15’ 0
019B   Logic input 2 (Word 2) VTA 1 F15’ 0
019C   Logic input 3 (Word 2) VTA 1 F15’ 0
019D   Logic input 4 (Word 2) VTA 1 F15’ 0
019E   Logic input 5 (Word 2) VTA 1 F15’ 0
0165   Aux. Timer 1 0 to 20000 1 1/100 s F1 0
0166   Aux. Timer 2 0 to 20000 1 1/100 s F1 0
0167 Allocation of information to auxiliary output contact (RL2 to RL8) Phase A Retrip (DTA’) 0 to 7F 1 F14 0
0168   Phase B Retrip (DTA’) 0 to 7F 1 F14 0
0169   Phase C Retrip (DTA’) 0 to 7F 1 F14 0
016A   Retrip 1st stage (DTA’ | DTB’ | DTC’) 0 to 7F 1 F14 0
016B   General retrip (DTG) 0 to 7F 1 F14 0
016C   End fault protection (T_DZ) 0 to 7F 1 F14 0
016D   3 poles discrepancy 0 to 7F 1 F14 0
016E   Taux 1 0 to 7F 1 F14 0
016F   Taux 2 0 to 7F 1 F14 0
0170 Allocation of information to auxiliary output contact (RL2 to RL8) Trip 0 – 7 or
0 – 127
1 F14 0
0170 Disturbance records Pre-time 1 to 30 1 1/10 sec F1 1
0171   Post-time (phase 1 only) 1 to 30 1 1/10 sec F1 1
0172   Disturbance record (Trigger Configuration) 0 to 1 1 F22 0
0173 CB supervision Operating time 0-1 1 F44 0
0174   Operating time threshold 10 to 500 1 1/100 sec F1 1
0175   Number of operations 0-1 1 F44 0
0176   Max number of the CB operation 0 to 50000 1 F1 0
0177   SAn summation 0 – 1 1 F44 0
0178   SAn summation threshold 0 to 4000 1E+7 10e6 An    
0179   n 1 to 2 1   F1 1
017A   Tripping pulse 10 to 500 10 1/100 sec F1 10
017B Relay allocation 1st stage Earth Retrip (DTE’) 0 – 7F 1 F14 0
017C   Opening time on external order 0 – 7F 1   F14 0
017D   Number of tripping operation threshold 0 – 7F 1   F14 0
017E   SAn threshold 0 – 7F 1   F14 0
017F   Stage 1 opening time threshold 0 – 7F 1   F14 0
0180 to
0187
  Reserved          
0188   Phase Non I stage1 0 – 7F 1   F14  
0189   Earth Non I stage1 0 – 7F 1   F14  
018A   Negative Non I stage1 0 – 7F 1   F14  
018B   t Equ. A 0 – FFFF     F14  
018C   t Equ. B 0 – FFFF     F14  
018D   t Equ. C 0 – FFFF     F14  
018E   t Equ. D 0 – FFFF     F14  
018F   t Equ. E 0 – FFFF     F14  
0190   t Equ. F 0 – FFFF     F14  
0191   t Equ. G 0 – FFFF     F14  
0192   t Equ. H 0 – FFFF     F14  
0193   Non I stage1 0 – 7F 1   F14  
0194   Non I stage2 0 – 7F 1   F14  
0195   Negative stage1 0 – 7F 1   F14  
0196   CB Unhealthy stage1 0 – 7F 1   F14  
0197   CB Unhealthy stage2 0 – 7F 1   F14  
0198   Blokc Logic 1 0 – FFFF     F66  
0199   Blokc Logic 2 0 – FFFF     F66  
019F to 01F3   Reserved          

Description of Mapping Format


Code Format Description   Format Data  
  Type Description Bit Value Data
F1 Unsigned Integer Numerical Data: 0 – 65535
F2 Signed Integer Numerical Data: -32768 – 32767
F3   Reserved      
F4 Unsigned Integer Communications Speed 0 300
      1 600
      2 1200
      3 2400
      4 4800
      5 9600
      6 19200
      7 38400
F5 Unsigned Integer Communications Parity 0 None
      1 Even
      2 Odd
F6 Unsigned Integer Trip Relay Mapping (Part 1) 0 1 DTA’
      1 2 DTB’
      2 4 DTC’
      3 8 Stage 1
      4 16 Stage 2
      5 32 Dead zone
      6 64 Pole Discrepancy
      7 128 Aux. 1
      8 256 Aux. 2
      9 512 DTE’
      10 1024 Trip Phase Non I stage1
      11 2048 Trip Neg.  Non I stage1
      12 4096 Trip Neg.  stage1
      13 8192 Trip Non I stage1
      14 16384 Trip Unhealthy stage1
      15 32768 Trip Unhealthy stage2
F6′ Unsigned Integer Trip Relay Mapping (Part 2) 0 1 Trip Equation A
      1 2 Trip Equation B
      2 4 Trip Equation C
      3 8 Trip Equation D
      4 16 Trip Equation E
      5 32 Trip Equation F
      6 64 Trip Equation G
      7 128 Trip Equation H
      8 256 Trip Earth Non I stage1
      9 512 Trip Non I stage2
F7   Reserved
F8 Unsigned Integer Trip Relay Latching Mapping (Part 1) 0 1 DTA’
      1 2 DTB’
      2 4 DTC’
      3 8 Stage 1
      4 16 Stage 2
      5 32 Dead zone
      6 64 Pole Discrepancy
      7 128 Aux. 1
      8 256 Aux. 2
      9 512 DTE’
      10 1024 Phase Non I stage1
      11 2048 Negative Non I stage1
      12 4096 Negative stage1
      13 8192 Non I stage1
      14 16384 Unhealthy stage1
      15 32768 Unhealthy stage2
F8′ Unsigned Integer Trip Relay Latching Mapping (Part 2) 0 1 Earth Non I stage1
      1 2 Non I stage2
F9 Unsigned Integer Remote Control Word 1 0 1 Unlatch Trip Contact
      1 2 Acknowledge 1st Alarm
      2 4 Acknowledge All Alarms
      3 8 Reserved
      4 16 Reserved
      5 32 Change Setting Group
      6 64 Reserved
      7 128 Reserved
      8 256 Disturbance Record Remote Start
      9 512 Reserved
      10 1024 Reserved
      11 2048 Reserved
      12 4096 Manual event/fault/distur acknowledgement mode
      13 8192 Acknowledge Oldest Event Record
      14 16384 Acknowledge Oldest Fault Record
      15 32768 Acknowledge Hardware SRAM Alarm
F10   ASCII Characters 32 – 127 ASCII Character 1
      32 – 127 ASCII Character 2
F10′   ASCII Characters 32 – 127 ASCII Character 1
        32 – 127 ASCII Character 2
        32 – 127 ASCII Character 3
        32 – 127 ASCII Character 4
        32 – 127 ASCII Character 5
        32 – 127 ASCII Character 6
        32 – 127 ASCII Character 7
        32 – 127 ASCII Character 8
F11   Reserved
F12 Unsigned Integer Logic Inputs 0 1 Logic Input Number 1
      1 2 Logic Input Number 2
      2 4 Logic Input Number 3
      3 8 Logic Input Number 4
      4 16 Logic Input Number 5
F13 Unsigned Integer Output Contacts status 0 1 Output Contact RL1 (Trip)
      1 2 Output Contact RL2
      2 4 Output Contact RL3
      3 8 Ouptut Contact RL4
      4 16 Ouput Contact RL0 (Watchdog)
      5 32 Ouput Contact RL5
      6 64 Ouput Contact RL6
      7 128 Output Contact RL7
      8 256 Output Contact RL8
F14 Unsigned Integer Output Contact Mapping 0 1 Ouput Contact RL2
      1 2 Ouput Contact RL3
      2 4 Ouput Contact RL4
      3 8 Ouput Contact RL5
      4 16 Ouput Contact RL6
      5 32 Ouput Contact RL7
      6 64 Ouput Contact RL8
F15 Unsigned Integer Logic Input Mapping(word 1) 0 1 Trip phase A
      1 2 Trip phase B
      2 4 Trip phase C
      3 8 Trip 3 phase
      4 16 Relay unlatch
      5 32 52a
      6 64 52b
      7 128 tAux1
      8 256 tAux2
      9 512 Change Setting group
      10 1024 Disturbance recorder external start
      11 2048 Secu. 1
      12 4096 Secu. 2
      13 8192 LEDs reset
      14 16384 CB unhealthy
      15 32768 Block Logic 1
F15′ Unsigned Integer Logic Input Mapping(word 2) 0 1 Block Logic 2
      1 2 SYNCHRO
      2 4 External Non I Trip order
F16   Reserved      
F17 Unsigned Integer Internal logic data 0 1 Latching
      1 2 Trip
F18 Signed Long Integer Numerical Data : -2147483648 to 2147483647
F19 Unsigned Integer User Configurable LED Mapping (Part 1) 0 1 External DTA
      1 2 External DTB
      2 4 External DTC
      3 8 External DTRI
      4 16 Backup DTA’
      5 32 Backup DTB’
      6 64 Backup DTC’
      7 128 t Stage 1
      8 256 t Stage 2
      9 512 Problem secu 1
      10 1024 Problem secu 2
      11 2048 t_DZ
      12 4096 tPD
      13 8192 tAux1
      14 16384 tAux2
      15 32768 Backup DTE’
F19′ Unsigned Integer User Configurable LED Mapping (Part 2) 0 1 CB Open time  ext.
      1 2 CB operation Nb
      2 4 Sum A n
      3 8 CB Open time st.1
      4 16 Earth Non I stage1
      5 32 Negative Non I  stage1
      6 64 Retrip order negative
      7 128 Non I general retrip
      8 256 CB Unhealthy stage1
      9 512 CB Unhealthy stage2
      10 1024 Logic Equation A
      11 2048 Logic Equation B
      12 4096 Logic Equation C
      13 8192 Logic Equation D
      14 16384 Logic Equation E
      15 32768 Logic Equation F
F19” Unsigned Integer User Configurable LED Mapping (Part 3) 0 1 Logic Equation G
      1 2 Logic Equation H
      2 4 Phase.Non I   Stage1
      3 8 Non I  general back-up
F20 Unsigned Integer Logic Input Data Status 0 1 External trip order phase A
      1 2 External trip order phase B
      2 4 External trip order phase C
      3 8 External trip order 3 phase
      4 16 Relay Unlatch
      5 32 52a
      6 64 52b
      7 128 tAux1
      8 256 tAux2
      9 512 Change Setting group
      10 1024 Disturbance record Start
      11 2048 Secu. 1
      12 4096 Secu. 2
      13 8192 LEDs reset
      14 16384 CB Unhealthy
      15 32768 Block Logic 1
F20′ Unsigned Integer Logic Input Data Status 0 1 Block Logic 2
      1 2 GPS time synchro
      2 4 External non I input
      3 8 Reserved
F21 Unsigned Integer Software Version 10 Version 1.A
      11 Version 1.B
      20 Version2.A etc…
F22 Unsigned Integer Disturbance record start kinds 0 1 Disturbance record starts on Ins.
      1 2 Disturbance record starts onTrip
F23 Unsigned Integer Quick Read Status Byte Format 0 1 Major Hardware Alarm Present
      1 2 Minor Hardware Alarm Present
      2 4 Non-Acknowledged Event Available
      3 8 Time Synchronisation State
      4 16 Non-Acknowledged Disturbance Record Available
      5 32 Non-Acknowledged Fault Record Available
F24 Unsigned Integer Breaker failure functionality 0 Disabled/No
      1 Enabled/Yes
F25 Characters ASCII        
F26 Unsigned Integer Default Display Selection 1 IA RMS Measurement
      2 IB RMS Measurement
      3 IC RMS Measurement
      4 IN RMS Measurement
      5 IA, IB, IC, IN RMS Measurements
F27 Unsigned Integer 1st stage reset configuration 0 Disabled/No
        1 Enabled/Yes
F28 Unsigned Integer Communications data Bits 0 1 7 bit data
      1 2 8 bit datas
F29 Unsigned Integer Communications Stop Bits 0 1 Stop Bit
      1 2 Stop Bits
F30 Unsigned Integer Rear communication Availability 0 1 Communications Disabled
      1 2 Communications Enabled
F31 Unsigned Integer 50 BF flag 0 1 1st stage delayed Breaker failure data
      1 2 2nd stage delayed Breaker failure data
      2 4 Configuration problem
      3 8 Non I stage 1
      4 16 Non I stage 2
      5 32 CB Unhealthy stage1
      6 64 CB Unhealthy stage2
      7 128 Phase configuration problem
      8 256 Earth configuration problem
      9 512 Negative configuration problem
           
F32 Unsigned Integer Security flag 0 1 Security problem1
      1 2 Security problem2
      2 4 EL configured on Secu1
      3 8 EL configured on Secu2
      4 16 Security Configuration problem
F33 Unsigned Integer Phase current & 50 BF flag 0 1 Indicates the current presence
      1 2 Instant information for current presence
      2 4 Stage 1 information for current presence
      3 8 Indicates the first detection of current presence
F34 Unsigned Integer CB position 0 1 Wrong configuration of Breaker position
      1 2 Wrong Breaker position
      2 4 CB on Open Position
          Reserved
F35 Unsigned Integer End fault function data status 0 1 Instantaneous data DZ
      1 2 Delayed data T_DZ
      2 4 DZ Configuration problem
      3 8 Phase A threshold crossed
      4 16 Phase B threshold crossed
      5 32 Phase C threshold crossed
F36 Unsigned Integer Pole discrepancy function data status 0 1 Instantaneous data PD
      1 2 Delayed data T_PD
      2 4 PD Configuration problem
      3 8 Phase A threshold crossed
      4 16 Phase B threshold crossed
      5 32 Phase C threshold crossed
F37 Unsigned Integer End fault protection memorisation 0 1 Instantaneous data DZ
      1 2 Delayed data T_DZ
F38 Unsigned Integer Pole discrepancy function memorisation 0 1 Instantaneous data PD
      1 2 Delayed data T_PD
F39   Reserved      
F40 Unsigned Integer Aux. data Memorisation 0 1 Aux1
      1 2 Aux2
F41   Communications Port Allocation 0 Front and Rear Port ModBus Communications
      1 Front Port ModBus and Rear Port Courier Communications
      2 Front Port ModBus and Rear Port VDEW Communications
F42 Unsigned Integer End Fault protection function 0 1 Disabled
      1 2 Enabled
F43 Unsigned Integer Pole discrepancy function 0 1 Disabled
      1 2 Enabled
F44 Unsigned Integer Breaker supervision function 0 1 Disabled
      1 2 Enabled
F45 Unsigned Integer Hardware Alarm Status 0 1 Watchdog
      1 2 User Communications Failure
      2 4 SETTING Failure
      3 8 ANA Failure
      4 16 Real Time Clock Failure
      5 32 EEPROM Failure
      6 64 SRAM Failure
      7 128 DEFAUT SETTING
      8 256 Main Power Supply
      9 512 Auxiliary Power Supplies
      10 1024 Transformers Offset Failure
F46 Unsigned Integer 50 BF supervision flag 0 1 Breaker longest operating time elapsed on external order
      1 2 Breaker longest operating time elapsed on 1st stage order
      2 4 Maximum number of breaker operation reached
      3 8 CB SA2N elapsed
F47 Unsigned Integer Configuration group change 0 change on Input edge or remote order or via front panel
      1 change on Input level change
F48 Unsigned integer Modbus Date Format Configuration   0 Private
        1 IEC
F49 Unsigned Integer Fault number to be displayed 0 None
      1~25 1~25
F50 Unsigned Integer Opto Power Supply Configuration 0 DC Supply
      1 AC Supply
F51 Unsigned Integer Remote Control Word 2 0 1 Unlatch trip relaly
      1 2 Unlatch output relay
      2 4 Reserved
      3 8 Reset SA2n
      4 16 Reset CB Open Number
      5 32 Reset event number
          Reserved
F52 Unsigned Integer Wiring check function 0 Disable
      1 Enable
F53 Unsigned Integer Relay to test 0 1 Relay 1 (Trip)
      1 2 Relay 2
      2 4 Relay 3
      3 8 Relay 4(watch dog)
      4 16 Relay 5
      5 32 Relay 6
      6 64 Relay 7
      7 128 Relay 8
F54 Unsigned Integer Aux. Input Data 0 1 Disable
      1 2 Enable
F55 Unsigned Integer Number of disturbance records 0 None
      1 1
      2 2
      3 3
      4 4
      5 5
F56 Unsigned Integer Breaker fail phase function 0 Disable
      1 Enable
F57 Unsigned  Integer Breaker fail earth function 0 Disable
      1 Enable
F58 Unsigned Integer Boolean Equation Operand   0 None
        1 Ph. A Stage 1
        2 Ph. B Stage 1
        3 Ph. C Stage 1
        4 Earth Non I   stage1
        5 Earth Stage 1
        6 Neg. Non I    stage1
        7 Neg. Stage 1
        8 Phase.Non I   Stage1
        9 CB unhealthy stage 1
        10 CB unhealthy stage 2
        11 t Stage 1
        12 t Stage 2
        13 t dead Zone
        14 t Pole Discre.
        15 t Aux1
        16 t Aux2
        17 CB open ext.
        18 CB open st. 1
        19 CB NB. op.
        20 Sum A n
        21 Input 1
        22 Input 2
        23 Input 3
        24 Input 4
        25 Input 5
        26 Non I stage1
        27 Non I stage2
F59 Unsigned Integer Boolean Equation Operator   0 OR
        1 OR NOT
        2 AND
        3 AND NOT
F61 Unsigned Integer Logic Equation Flag 0 1 Equation A
      1 2 Equation B
      2 4 Equation C
      3 8 Equation D
      4 16 Equation E
      5 32 Equation F
      6 64 Equation G
      7 128 Equation H
F62 Unsigned Integer External Non I Reset by   0 Reset by current/Default
        1 Reset by CB open
        2 Reset by current & CB open
F63 Unsigned Integer Remote Control Word 3 0 1 Reserved
      1 2 Reserved
      2 4 Acknowledge Oldest Disturbance Record
      3 8 Reserved
      4 16 Reserved
      5 32 Reserved
      6 64 Reserved
      7 128 Reserved
      8 256 Reserved
      9 512 Reserved
      10 1024 Reserved
      11 2048 Reserved
      12 4096 Reserved
      13 8192 Reserved
      14 16384 Erase all records (events, faults, alarms, disturbances,etc)
      15 32768 Reserved
F65 Unsigned Integer Memo alarm flag 1 0 1 Phase Non I stage1
      1 2 Earth Non I stage1
      2 4 Negative Non I stage1
      3 8 Negative stage1
      4 16 Equation A
      5 32 Equation B
      6 64 Equation C
      7 128 Equation D
      8 256 Equation E
      9 512 Equation F
      10 1024 Equation G
      11 2048 Equation H
F66 Unsigned Integer Blocking Logic Mapping 0 1 CBF phase
      1 2 CBF earth
      2 4 CBF neg.
      3 8 Dead zone
      4 16 Pole discrepancy
      5 32 tAux1
      6 64 tAux2
F98 Unsigned Integer auxiliary power supply self test status 0 1 -3V3 out of range
      1 2 5V0 out of range
      2 4 3V3 out of range
      3 8 12V out of range
      4 16 1V3 out of range
      5 32 0V  out of range
F99 Unsigned Integer Transformer self test status 0 1 Abnormal offset with transformer 1
      1 2 Abnormal offset with transformer 2
      2 4 Abnormal offset with transformer 3
      3 8 Abnormal offset with transformer 4
      4 16 Abnormal offset with transformer 5
      5 32 Abnormal offset with transformer 6
      6 64 Abnormal offset with transformer 7
      7 128 Abnormal offset with transformer 8
      8 256 Abnormal offset with transformer 9