Overview
MiCOM P821 is an advanced Breaker Failure relay with backup protection functions. It offers a range of protection functions, combined with extensive monitoring capacities to give you optimized efficiency and maximum control for your electric schemes. It is suitable for all voltage levels.
For more detailed information on “MiCOM P821” relays, refer to Schneider protection relays manuals.
To see other supported devices, click here.
Setting Parameters
Breaker Failure Protection Settings for Group1
Address | Group | Description | Settings range | Step | Unit | Format | Default settings |
0200 | Setting group n°1 | Breaker Failure | 0-1 | 1 | – | F24 | 0 |
0201 | Threshold I< | 5 to 400 | 1 | In/100 | F1 | 10 | |
0202 | TBF1 delay | 0 to 4000 | 5 | 1/1000 s | F1 | 10 | |
0203 | TBF2 delay | 0 to 4000 | 5 | 1/10 | F1 | 40 | |
0204 | 1st stage Reset | 0 – 1 | 1 | F27 | 0 | ||
0205 | End fault | 0 – 1 | 1 | F42 | 0 | ||
0206 | I_DZ> threshold | 5 – 400 | 1 | In/100 | F1 | 100 | |
0207 | DZ delay | 0 to 40000 | 5 | 1/1000 s | F1 | 10 | |
0208 | Pole Discrepancy | 0 – 1 | 1 | F43 | 0 | ||
0209 | I_PD> Threshold | 8 – 400 | 1 | In/100 | F1 | 80 | |
020A | I_PD< Threshold | 5 – 100 | 1 | In/100 | F1 | 40 | |
020B | PD Delay | 0 to 40000 | 5 | 1/1000 s | F1 | 10 | |
020C | Phase Breaker failure | 0-1 | 1 | F56 | 0 | ||
020D | Earth Breaker failure | 0-1 | 1 | F57 | 0 | ||
020E | I0< Threshold | N: 5 to 400 S: 1 to 400 VS: 2 to 800 |
1 | In/100 In/100 In/1000 |
F1 | N: 10 S: 5 VS: 25 |
|
020F | Phase Delay stage 1 | 0 to 40000 | 5 | 1/1000 s | F1 | ||
0210 | Phase Delay stage 2 | 0 to 40000 | 5 | 1/1000 s | F1 | ||
0211 | CB Fail Neg. Seq. | 0 to 1 | 1 | F24 | |||
0212 | I2< BF | 5 to 200 | 1 | 1/100 | F1 | ||
0213 | Neg. Delay stage 1 | 0 to 40000 | 5 | 1/1000 s | F1 | ||
0214 | Neg. Delay stage 2 | 0 to 40000 | 5 | 1/1000 s | F1 | ||
0215 | CB unhealthy | 0 to 1 | 1 | F24 | |||
0216 | CB unh. stage 1 | 0 to 40000 | 5 | 1/1000 s | F1 | ||
0217 | CB unh. stage 2 | 0 to 40000 | 5 | 1/1000 s | F1 | ||
0218 | Ie DZ>threshold | N: 5 to 400 S: 1 to 400 VS: 2 to 800 |
1 | In/100 In/100 In/1000 |
F1 | ||
0219 | External Non I Reset by | 0 to 2 | 1 | F62 | |||
Other Setting Parameters
Address | Group | Description | Settings range | Step | Unit | Format | Default settings |
0100 | Remote settings | Address | 1 to 255 | 1 | – | F1 | 1 |
0101 | Language | 0 to 7 | – | – | F1 | – | |
0102 | Password characters 1 and 2 | 32 -127 | 1 | – | F10 | AA | |
0103 | Password characters 3 and 4 | 32 -127 | 1 | – | F10 | AA | |
0104 | Frequency | 50-60 | 10 | Hz | F1 | 50 | |
0105 | Phase A Labelling | L1 – A – R | VTA | F25 | A | ||
0106 | Phase B Labelling | L2 – B – S | VTA | F25 | B | ||
0107 | Phase C Labelling | L3 – C – T | VTA | F25 | C | ||
0108 | Earth Labelling | N – E – o | VTA | F25 | N | ||
0109 | Default display | 1-3 | 1 | – | F26 | 1 | |
010A | User reference (characters 1 and 2) | 32-127 | 1 | F10 | AL | ||
010B | User reference (characters 3 and 4) | 32-127 | 1 | F10 | ST | ||
010C | Fault number to be displayed | 1-5 | 1 | F49 | 5 | ||
010D | Configuration of the logic inputs validation edge | 0 | F11 | 0 | |||
010E | Reserved | ||||||
010F | Type of the logic inputs input voltage | 0-1 | 1 | F50 | 0 | ||
0110 | CB supervision | CB operation number | 1 | F1 | |||
0111 | CB operating time | 1 | 1/10 sec | F1 | |||
0112 to 0113 | San IA | An | F18 | ||||
0113 to 0114 | San IB | An | F18 | ||||
0114 to 0115 | San IC | An | F18 | ||||
0118 | Wiring security | 0 – 1 | 1 | F52 | |||
0119 | Relay to test 1 | 1 – 8 | 1 | F53 | |||
011A | Relay to test 1 | 1 – 8 | 1 | F53 | |||
011B to 011E | Reserved | ||||||
011F | Latched relays | F14 | |||||
120 | Ratios | Phase CT: primary value | 1 to 50000 | 1 | F14 | 1000 | |
0121 | Phase CT: secondary value | 1 to 5 | 4 | F1 | 1 | ||
0122 | Trip relay allocation | Trip relay functionality (word 1) | 0 to 65535 | 1 | F6 | ||
0123 | Latching | Trip relay latching function (word 1) | 0 to 255 | 1 | 10 V | F8 | |
0124 | Ratio | Earth CT: primary value | 1 to 50000 | 1 | F1 | 1000 | |
0125 | Earth CT: secondary value | 1 to 5 | 4 | F1 | 1 | ||
0126 | Trip relay functionality (word 2) | 0 to 65535 | 1 | F6’ | |||
0127 | Latching | Trip relay latching function (word 2) | 0 to 65535 | 1 | F8’ | ||
0128 to 012F | Reserved | ||||||
0130 | Communication | Baud rate | 0 to 7 | 1 | – | F4 | 6 = 19200 bauds |
0131 | Parity | 0 to 2 | 1 | – | F5 | 0 = without | |
0132 | Data bits | 0 to 1 | 1 | F28 | 1 = 8 bits | ||
0133 | Number of stop bits | 0 to 1 | 1 | – | F29 | 0 = 1 stop bit | |
0134 | Comm. Available | 0 to 1 | 1 | – | F30 | 1 = COM available | |
0135 | Date Format | 0 to 1 | 0 | F48 | 0 = Private | ||
0136 | Reserved | ||||||
0137 | AddressRear Port | ||||||
0138 to 013F | Reserved | ||||||
0140 | Setting group | Active setting group | 1 to 2 | 1 | – | F1 | 1 |
0141 | Validation of instantaneous self resetting | 0 to 1 | 1 | F1 | 0 | ||
0142 | Configuration of the change of the setting group | 0 to 1 | 1 | F47 | 1 | ||
0143 | Configuration of Battery and RAM error alarms | 0 to 1 | 1 | F1 | 0 | ||
0144 | conf. TS AC/DC visible | ||||||
0145 to 014F | Reserved | ||||||
0150 | LEDs configuration |
LED 5 (Word 1) | 1 | – | F19 | 0 | |
0151 | LED 6 (Word 1) | 1 | – | F19 | |||
0152 | LED 7 (Word 1) | 1 | – | F19 | |||
0153 | LED 8 (Word 1) | 1 | F19 | ||||
0154 | LED 5 (Word 2) | 1 | F19’ | ||||
0155 | LED 6 (Word 2) | 1 | F19’ | ||||
0156 | LED 7 (Word 2) | 1 | F19’ | ||||
0157 | LED 8 (Word 2) | 1 | F19’ | 0 | |||
0158 | LED 5 (Word 3) | F19’’ | |||||
0159 | LED 6 (Word 3) | F19’’ | |||||
015A | LED 7 (Word 3) | F19’’ | |||||
015B | LED 8 (Word 3) | F19’’ | |||||
015C to 015F | Reserved | ||||||
0160 | Logic inputs configuration | Logic input 1 (Word 1) | VTA | 1 | – | F15 | 0 |
0161 | Logic input 2 (Word 1) | VTA | 1 | – | F15 | 0 | |
0162 | Logic input 3 (Word 1) | VTA | 1 | – | F15 | 0 | |
0163 | Logic input 4 (Word 1) | VTA | 1 | – | F15 | 0 | |
0164 | Logic input 5 (Word 1) | VTA | 1 | – | F15 | 0 | |
019A | Logic input 1 (Word 2) | VTA | 1 | – | F15’ | 0 | |
019B | Logic input 2 (Word 2) | VTA | 1 | – | F15’ | 0 | |
019C | Logic input 3 (Word 2) | VTA | 1 | – | F15’ | 0 | |
019D | Logic input 4 (Word 2) | VTA | 1 | – | F15’ | 0 | |
019E | Logic input 5 (Word 2) | VTA | 1 | – | F15’ | 0 | |
0165 | Aux. Timer 1 | 0 to 20000 | 1 | 1/100 s | F1 | 0 | |
0166 | Aux. Timer 2 | 0 to 20000 | 1 | 1/100 s | F1 | 0 | |
0167 | Allocation of information to auxiliary output contact (RL2 to RL8) | Phase A Retrip (DTA’) | 0 to 7F | 1 | – | F14 | 0 |
0168 | Phase B Retrip (DTA’) | 0 to 7F | 1 | – | F14 | 0 | |
0169 | Phase C Retrip (DTA’) | 0 to 7F | 1 | – | F14 | 0 | |
016A | Retrip 1st stage (DTA’ | DTB’ | DTC’) | 0 to 7F | 1 | – | F14 | 0 | |
016B | General retrip (DTG) | 0 to 7F | 1 | – | F14 | 0 | |
016C | End fault protection (T_DZ) | 0 to 7F | 1 | – | F14 | 0 | |
016D | 3 poles discrepancy | 0 to 7F | 1 | – | F14 | 0 | |
016E | Taux 1 | 0 to 7F | 1 | – | F14 | 0 | |
016F | Taux 2 | 0 to 7F | 1 | – | F14 | 0 | |
0170 | Allocation of information to auxiliary output contact (RL2 to RL8) | Trip | 0 – 7 or 0 – 127 |
1 | – | F14 | 0 |
0170 | Disturbance records | Pre-time | 1 to 30 | 1 | 1/10 sec | F1 | 1 |
0171 | Post-time (phase 1 only) | 1 to 30 | 1 | 1/10 sec | F1 | 1 | |
0172 | Disturbance record (Trigger Configuration) | 0 to 1 | 1 | – | F22 | 0 | |
0173 | CB supervision | Operating time | 0-1 | 1 | – | F44 | 0 |
0174 | Operating time threshold | 10 to 500 | 1 | 1/100 sec | F1 | 1 | |
0175 | Number of operations | 0-1 | 1 | – | F44 | 0 | |
0176 | Max number of the CB operation | 0 to 50000 | 1 | – | F1 | 0 | |
0177 | SAn summation | 0 – 1 | 1 | – | F44 | 0 | |
0178 | SAn summation threshold | 0 to 4000 | 1E+7 | 10e6 An | |||
0179 | n | 1 to 2 | 1 | F1 | 1 | ||
017A | Tripping pulse | 10 to 500 | 10 | 1/100 sec | F1 | 10 | |
017B | Relay allocation | 1st stage Earth Retrip (DTE’) | 0 – 7F | 1 | – | F14 | 0 |
017C | Opening time on external order | 0 – 7F | 1 | F14 | 0 | ||
017D | Number of tripping operation threshold | 0 – 7F | 1 | F14 | 0 | ||
017E | SAn threshold | 0 – 7F | 1 | F14 | 0 | ||
017F | Stage 1 opening time threshold | 0 – 7F | 1 | F14 | 0 | ||
0180 to 0187 |
Reserved | ||||||
0188 | Phase Non I stage1 | 0 – 7F | 1 | F14 | |||
0189 | Earth Non I stage1 | 0 – 7F | 1 | F14 | |||
018A | Negative Non I stage1 | 0 – 7F | 1 | F14 | |||
018B | t Equ. A | 0 – FFFF | F14 | ||||
018C | t Equ. B | 0 – FFFF | F14 | ||||
018D | t Equ. C | 0 – FFFF | F14 | ||||
018E | t Equ. D | 0 – FFFF | F14 | ||||
018F | t Equ. E | 0 – FFFF | F14 | ||||
0190 | t Equ. F | 0 – FFFF | F14 | ||||
0191 | t Equ. G | 0 – FFFF | F14 | ||||
0192 | t Equ. H | 0 – FFFF | F14 | ||||
0193 | Non I stage1 | 0 – 7F | 1 | F14 | |||
0194 | Non I stage2 | 0 – 7F | 1 | F14 | |||
0195 | Negative stage1 | 0 – 7F | 1 | F14 | |||
0196 | CB Unhealthy stage1 | 0 – 7F | 1 | F14 | |||
0197 | CB Unhealthy stage2 | 0 – 7F | 1 | F14 | |||
0198 | Blokc Logic 1 | 0 – FFFF | F66 | ||||
0199 | Blokc Logic 2 | 0 – FFFF | F66 | ||||
019F to 01F3 | Reserved | ||||||
Description of Mapping Format
Code | Format Description | Format Data | |||
Type | Description | Bit | Value | Data | |
F1 | Unsigned Integer | Numerical Data: 0 – 65535 | – | – | – |
F2 | Signed Integer | Numerical Data: -32768 – 32767 | – | – | – |
F3 | Reserved | ||||
F4 | Unsigned Integer | Communications Speed | – | 0 | 300 |
– | 1 | 600 | |||
– | 2 | 1200 | |||
– | 3 | 2400 | |||
– | 4 | 4800 | |||
– | 5 | 9600 | |||
– | 6 | 19200 | |||
– | 7 | 38400 | |||
F5 | Unsigned Integer | Communications Parity | – | 0 | None |
– | 1 | Even | |||
– | 2 | Odd | |||
F6 | Unsigned Integer | Trip Relay Mapping (Part 1) | 0 | 1 | DTA’ |
1 | 2 | DTB’ | |||
2 | 4 | DTC’ | |||
3 | 8 | Stage 1 | |||
4 | 16 | Stage 2 | |||
5 | 32 | Dead zone | |||
6 | 64 | Pole Discrepancy | |||
7 | 128 | Aux. 1 | |||
8 | 256 | Aux. 2 | |||
9 | 512 | DTE’ | |||
10 | 1024 | Trip Phase Non I stage1 | |||
11 | 2048 | Trip Neg. Non I stage1 | |||
12 | 4096 | Trip Neg. stage1 | |||
13 | 8192 | Trip Non I stage1 | |||
14 | 16384 | Trip Unhealthy stage1 | |||
15 | 32768 | Trip Unhealthy stage2 | |||
F6′ | Unsigned Integer | Trip Relay Mapping (Part 2) | 0 | 1 | Trip Equation A |
1 | 2 | Trip Equation B | |||
2 | 4 | Trip Equation C | |||
3 | 8 | Trip Equation D | |||
4 | 16 | Trip Equation E | |||
5 | 32 | Trip Equation F | |||
6 | 64 | Trip Equation G | |||
7 | 128 | Trip Equation H | |||
8 | 256 | Trip Earth Non I stage1 | |||
9 | 512 | Trip Non I stage2 | |||
F7 | Reserved | – | – | – | |
F8 | Unsigned Integer | Trip Relay Latching Mapping (Part 1) | 0 | 1 | DTA’ |
1 | 2 | DTB’ | |||
2 | 4 | DTC’ | |||
3 | 8 | Stage 1 | |||
4 | 16 | Stage 2 | |||
5 | 32 | Dead zone | |||
6 | 64 | Pole Discrepancy | |||
7 | 128 | Aux. 1 | |||
8 | 256 | Aux. 2 | |||
9 | 512 | DTE’ | |||
10 | 1024 | Phase Non I stage1 | |||
11 | 2048 | Negative Non I stage1 | |||
12 | 4096 | Negative stage1 | |||
13 | 8192 | Non I stage1 | |||
14 | 16384 | Unhealthy stage1 | |||
15 | 32768 | Unhealthy stage2 | |||
F8′ | Unsigned Integer | Trip Relay Latching Mapping (Part 2) | 0 | 1 | Earth Non I stage1 |
1 | 2 | Non I stage2 | |||
F9 | Unsigned Integer | Remote Control Word 1 | 0 | 1 | Unlatch Trip Contact |
1 | 2 | Acknowledge 1st Alarm | |||
2 | 4 | Acknowledge All Alarms | |||
3 | 8 | Reserved | |||
4 | 16 | Reserved | |||
5 | 32 | Change Setting Group | |||
6 | 64 | Reserved | |||
7 | 128 | Reserved | |||
8 | 256 | Disturbance Record Remote Start | |||
9 | 512 | Reserved | |||
10 | 1024 | Reserved | |||
11 | 2048 | Reserved | |||
12 | 4096 | Manual event/fault/distur acknowledgement mode | |||
13 | 8192 | Acknowledge Oldest Event Record | |||
14 | 16384 | Acknowledge Oldest Fault Record | |||
15 | 32768 | Acknowledge Hardware SRAM Alarm | |||
F10 | ASCII Characters | – | 32 – 127 | ASCII Character 1 | |
– | 32 – 127 | ASCII Character 2 | |||
F10′ | ASCII Characters | – | 32 – 127 | ASCII Character 1 | |
32 – 127 | ASCII Character 2 | ||||
32 – 127 | ASCII Character 3 | ||||
32 – 127 | ASCII Character 4 | ||||
32 – 127 | ASCII Character 5 | ||||
32 – 127 | ASCII Character 6 | ||||
32 – 127 | ASCII Character 7 | ||||
32 – 127 | ASCII Character 8 | ||||
F11 | Reserved | – | – | – | |
F12 | Unsigned Integer | Logic Inputs | 0 | 1 | Logic Input Number 1 |
1 | 2 | Logic Input Number 2 | |||
2 | 4 | Logic Input Number 3 | |||
3 | 8 | Logic Input Number 4 | |||
4 | 16 | Logic Input Number 5 | |||
F13 | Unsigned Integer | Output Contacts status | 0 | 1 | Output Contact RL1 (Trip) |
1 | 2 | Output Contact RL2 | |||
2 | 4 | Output Contact RL3 | |||
3 | 8 | Ouptut Contact RL4 | |||
4 | 16 | Ouput Contact RL0 (Watchdog) | |||
5 | 32 | Ouput Contact RL5 | |||
6 | 64 | Ouput Contact RL6 | |||
7 | 128 | Output Contact RL7 | |||
8 | 256 | Output Contact RL8 | |||
F14 | Unsigned Integer | Output Contact Mapping | 0 | 1 | Ouput Contact RL2 |
1 | 2 | Ouput Contact RL3 | |||
2 | 4 | Ouput Contact RL4 | |||
3 | 8 | Ouput Contact RL5 | |||
4 | 16 | Ouput Contact RL6 | |||
5 | 32 | Ouput Contact RL7 | |||
6 | 64 | Ouput Contact RL8 | |||
F15 | Unsigned Integer | Logic Input Mapping(word 1) | 0 | 1 | Trip phase A |
1 | 2 | Trip phase B | |||
2 | 4 | Trip phase C | |||
3 | 8 | Trip 3 phase | |||
4 | 16 | Relay unlatch | |||
5 | 32 | 52a | |||
6 | 64 | 52b | |||
7 | 128 | tAux1 | |||
8 | 256 | tAux2 | |||
9 | 512 | Change Setting group | |||
10 | 1024 | Disturbance recorder external start | |||
11 | 2048 | Secu. 1 | |||
12 | 4096 | Secu. 2 | |||
13 | 8192 | LEDs reset | |||
14 | 16384 | CB unhealthy | |||
15 | 32768 | Block Logic 1 | |||
F15′ | Unsigned Integer | Logic Input Mapping(word 2) | 0 | 1 | Block Logic 2 |
1 | 2 | SYNCHRO | |||
2 | 4 | External Non I Trip order | |||
F16 | Reserved | ||||
F17 | Unsigned Integer | Internal logic data | 0 | 1 | Latching |
1 | 2 | Trip | |||
F18 | Signed Long Integer | Numerical Data : -2147483648 to 2147483647 | – | – | – |
F19 | Unsigned Integer | User Configurable LED Mapping (Part 1) | 0 | 1 | External DTA |
1 | 2 | External DTB | |||
2 | 4 | External DTC | |||
3 | 8 | External DTRI | |||
4 | 16 | Backup DTA’ | |||
5 | 32 | Backup DTB’ | |||
6 | 64 | Backup DTC’ | |||
7 | 128 | t Stage 1 | |||
8 | 256 | t Stage 2 | |||
9 | 512 | Problem secu 1 | |||
10 | 1024 | Problem secu 2 | |||
11 | 2048 | t_DZ | |||
12 | 4096 | tPD | |||
13 | 8192 | tAux1 | |||
14 | 16384 | tAux2 | |||
15 | 32768 | Backup DTE’ | |||
F19′ | Unsigned Integer | User Configurable LED Mapping (Part 2) | 0 | 1 | CB Open time ext. |
1 | 2 | CB operation Nb | |||
2 | 4 | Sum A n | |||
3 | 8 | CB Open time st.1 | |||
4 | 16 | Earth Non I stage1 | |||
5 | 32 | Negative Non I stage1 | |||
6 | 64 | Retrip order negative | |||
7 | 128 | Non I general retrip | |||
8 | 256 | CB Unhealthy stage1 | |||
9 | 512 | CB Unhealthy stage2 | |||
10 | 1024 | Logic Equation A | |||
11 | 2048 | Logic Equation B | |||
12 | 4096 | Logic Equation C | |||
13 | 8192 | Logic Equation D | |||
14 | 16384 | Logic Equation E | |||
15 | 32768 | Logic Equation F | |||
F19” | Unsigned Integer | User Configurable LED Mapping (Part 3) | 0 | 1 | Logic Equation G |
1 | 2 | Logic Equation H | |||
2 | 4 | Phase.Non I Stage1 | |||
3 | 8 | Non I general back-up | |||
F20 | Unsigned Integer | Logic Input Data Status | 0 | 1 | External trip order phase A |
1 | 2 | External trip order phase B | |||
2 | 4 | External trip order phase C | |||
3 | 8 | External trip order 3 phase | |||
4 | 16 | Relay Unlatch | |||
5 | 32 | 52a | |||
6 | 64 | 52b | |||
7 | 128 | tAux1 | |||
8 | 256 | tAux2 | |||
9 | 512 | Change Setting group | |||
10 | 1024 | Disturbance record Start | |||
11 | 2048 | Secu. 1 | |||
12 | 4096 | Secu. 2 | |||
13 | 8192 | LEDs reset | |||
14 | 16384 | CB Unhealthy | |||
15 | 32768 | Block Logic 1 | |||
F20′ | Unsigned Integer | Logic Input Data Status | 0 | 1 | Block Logic 2 |
1 | 2 | GPS time synchro | |||
2 | 4 | External non I input | |||
3 | 8 | Reserved | |||
F21 | Unsigned Integer | Software Version | – | 10 | Version 1.A |
– | 11 | Version 1.B | |||
– | 20 | Version2.A etc… | |||
F22 | Unsigned Integer | Disturbance record start kinds | 0 | 1 | Disturbance record starts on Ins. |
1 | 2 | Disturbance record starts onTrip | |||
F23 | Unsigned Integer | Quick Read Status Byte Format | 0 | 1 | Major Hardware Alarm Present |
1 | 2 | Minor Hardware Alarm Present | |||
2 | 4 | Non-Acknowledged Event Available | |||
3 | 8 | Time Synchronisation State | |||
4 | 16 | Non-Acknowledged Disturbance Record Available | |||
5 | 32 | Non-Acknowledged Fault Record Available | |||
F24 | Unsigned Integer | Breaker failure functionality | – | 0 | Disabled/No |
– | 1 | Enabled/Yes | |||
F25 | Characters ASCII | ||||
F26 | Unsigned Integer | Default Display Selection | – | 1 | IA RMS Measurement |
– | 2 | IB RMS Measurement | |||
– | 3 | IC RMS Measurement | |||
– | 4 | IN RMS Measurement | |||
– | 5 | IA, IB, IC, IN RMS Measurements | |||
F27 | Unsigned Integer | 1st stage reset configuration | – | 0 | Disabled/No |
1 | Enabled/Yes | ||||
F28 | Unsigned Integer | Communications data Bits | 0 | 1 | 7 bit data |
1 | 2 | 8 bit datas | |||
F29 | Unsigned Integer | Communications Stop Bits | – | 0 | 1 Stop Bit |
– | 1 | 2 Stop Bits | |||
F30 | Unsigned Integer | Rear communication Availability | 0 | 1 | Communications Disabled |
1 | 2 | Communications Enabled | |||
F31 | Unsigned Integer | 50 BF flag | 0 | 1 | 1st stage delayed Breaker failure data |
1 | 2 | 2nd stage delayed Breaker failure data | |||
2 | 4 | Configuration problem | |||
3 | 8 | Non I stage 1 | |||
4 | 16 | Non I stage 2 | |||
5 | 32 | CB Unhealthy stage1 | |||
6 | 64 | CB Unhealthy stage2 | |||
7 | 128 | Phase configuration problem | |||
8 | 256 | Earth configuration problem | |||
9 | 512 | Negative configuration problem | |||
F32 | Unsigned Integer | Security flag | 0 | 1 | Security problem1 |
1 | 2 | Security problem2 | |||
2 | 4 | EL configured on Secu1 | |||
3 | 8 | EL configured on Secu2 | |||
4 | 16 | Security Configuration problem | |||
F33 | Unsigned Integer | Phase current & 50 BF flag | 0 | 1 | Indicates the current presence |
1 | 2 | Instant information for current presence | |||
2 | 4 | Stage 1 information for current presence | |||
3 | 8 | Indicates the first detection of current presence | |||
F34 | Unsigned Integer | CB position | 0 | 1 | Wrong configuration of Breaker position |
1 | 2 | Wrong Breaker position | |||
2 | 4 | CB on Open Position | |||
Reserved | |||||
F35 | Unsigned Integer | End fault function data status | 0 | 1 | Instantaneous data DZ |
1 | 2 | Delayed data T_DZ | |||
2 | 4 | DZ Configuration problem | |||
3 | 8 | Phase A threshold crossed | |||
4 | 16 | Phase B threshold crossed | |||
5 | 32 | Phase C threshold crossed | |||
F36 | Unsigned Integer | Pole discrepancy function data status | 0 | 1 | Instantaneous data PD |
1 | 2 | Delayed data T_PD | |||
2 | 4 | PD Configuration problem | |||
3 | 8 | Phase A threshold crossed | |||
4 | 16 | Phase B threshold crossed | |||
5 | 32 | Phase C threshold crossed | |||
F37 | Unsigned Integer | End fault protection memorisation | 0 | 1 | Instantaneous data DZ |
1 | 2 | Delayed data T_DZ | |||
F38 | Unsigned Integer | Pole discrepancy function memorisation | 0 | 1 | Instantaneous data PD |
1 | 2 | Delayed data T_PD | |||
F39 | Reserved | ||||
F40 | Unsigned Integer | Aux. data Memorisation | 0 | 1 | Aux1 |
1 | 2 | Aux2 | |||
F41 | Communications Port Allocation | – | 0 | Front and Rear Port ModBus Communications | |
– | 1 | Front Port ModBus and Rear Port Courier Communications | |||
– | 2 | Front Port ModBus and Rear Port VDEW Communications | |||
F42 | Unsigned Integer | End Fault protection function | 0 | 1 | Disabled |
1 | 2 | Enabled | |||
F43 | Unsigned Integer | Pole discrepancy function | 0 | 1 | Disabled |
1 | 2 | Enabled | |||
F44 | Unsigned Integer | Breaker supervision function | 0 | 1 | Disabled |
1 | 2 | Enabled | |||
F45 | Unsigned Integer | Hardware Alarm Status | 0 | 1 | Watchdog |
1 | 2 | User Communications Failure | |||
2 | 4 | SETTING Failure | |||
3 | 8 | ANA Failure | |||
4 | 16 | Real Time Clock Failure | |||
5 | 32 | EEPROM Failure | |||
6 | 64 | SRAM Failure | |||
7 | 128 | DEFAUT SETTING | |||
8 | 256 | Main Power Supply | |||
9 | 512 | Auxiliary Power Supplies | |||
10 | 1024 | Transformers Offset Failure | |||
F46 | Unsigned Integer | 50 BF supervision flag | 0 | 1 | Breaker longest operating time elapsed on external order |
1 | 2 | Breaker longest operating time elapsed on 1st stage order | |||
2 | 4 | Maximum number of breaker operation reached | |||
3 | 8 | CB SA2N elapsed | |||
F47 | Unsigned Integer | Configuration group change | – | 0 | change on Input edge or remote order or via front panel |
– | 1 | change on Input level change | |||
F48 | Unsigned integer | Modbus Date Format Configuration | 0 | Private | |
1 | IEC | ||||
F49 | Unsigned Integer | Fault number to be displayed | – | 0 | None |
– | 1~25 | 1~25 | |||
F50 | Unsigned Integer | Opto Power Supply Configuration | – | 0 | DC Supply |
– | 1 | AC Supply | |||
F51 | Unsigned Integer | Remote Control Word 2 | 0 | 1 | Unlatch trip relaly |
1 | 2 | Unlatch output relay | |||
2 | 4 | Reserved | |||
3 | 8 | Reset SA2n | |||
4 | 16 | Reset CB Open Number | |||
5 | 32 | Reset event number | |||
Reserved | |||||
F52 | Unsigned Integer | Wiring check function | – | 0 | Disable |
– | 1 | Enable | |||
F53 | Unsigned Integer | Relay to test | 0 | 1 | Relay 1 (Trip) |
1 | 2 | Relay 2 | |||
2 | 4 | Relay 3 | |||
3 | 8 | Relay 4(watch dog) | |||
4 | 16 | Relay 5 | |||
5 | 32 | Relay 6 | |||
6 | 64 | Relay 7 | |||
7 | 128 | Relay 8 | |||
F54 | Unsigned Integer | Aux. Input Data | 0 | 1 | Disable |
1 | 2 | Enable | |||
F55 | Unsigned Integer | Number of disturbance records | – | 0 | None |
– | 1 | 1 | |||
– | 2 | 2 | |||
– | 3 | 3 | |||
– | 4 | 4 | |||
– | 5 | 5 | |||
F56 | Unsigned Integer | Breaker fail phase function | – | 0 | Disable |
– | 1 | Enable | |||
F57 | Unsigned Integer | Breaker fail earth function | – | 0 | Disable |
– | 1 | Enable | |||
F58 | Unsigned Integer | Boolean Equation Operand | 0 | None | |
1 | Ph. A Stage 1 | ||||
2 | Ph. B Stage 1 | ||||
3 | Ph. C Stage 1 | ||||
4 | Earth Non I stage1 | ||||
5 | Earth Stage 1 | ||||
6 | Neg. Non I stage1 | ||||
7 | Neg. Stage 1 | ||||
8 | Phase.Non I Stage1 | ||||
9 | CB unhealthy stage 1 | ||||
10 | CB unhealthy stage 2 | ||||
11 | t Stage 1 | ||||
12 | t Stage 2 | ||||
13 | t dead Zone | ||||
14 | t Pole Discre. | ||||
15 | t Aux1 | ||||
16 | t Aux2 | ||||
17 | CB open ext. | ||||
18 | CB open st. 1 | ||||
19 | CB NB. op. | ||||
20 | Sum A n | ||||
21 | Input 1 | ||||
22 | Input 2 | ||||
23 | Input 3 | ||||
24 | Input 4 | ||||
25 | Input 5 | ||||
26 | Non I stage1 | ||||
27 | Non I stage2 | ||||
F59 | Unsigned Integer | Boolean Equation Operator | 0 | OR | |
1 | OR NOT | ||||
2 | AND | ||||
3 | AND NOT | ||||
F61 | Unsigned Integer | Logic Equation Flag | 0 | 1 | Equation A |
1 | 2 | Equation B | |||
2 | 4 | Equation C | |||
3 | 8 | Equation D | |||
4 | 16 | Equation E | |||
5 | 32 | Equation F | |||
6 | 64 | Equation G | |||
7 | 128 | Equation H | |||
F62 | Unsigned Integer | External Non I Reset by | 0 | Reset by current/Default | |
1 | Reset by CB open | ||||
2 | Reset by current & CB open | ||||
F63 | Unsigned Integer | Remote Control Word 3 | 0 | 1 | Reserved |
1 | 2 | Reserved | |||
2 | 4 | Acknowledge Oldest Disturbance Record | |||
3 | 8 | Reserved | |||
4 | 16 | Reserved | |||
5 | 32 | Reserved | |||
6 | 64 | Reserved | |||
7 | 128 | Reserved | |||
8 | 256 | Reserved | |||
9 | 512 | Reserved | |||
10 | 1024 | Reserved | |||
11 | 2048 | Reserved | |||
12 | 4096 | Reserved | |||
13 | 8192 | Reserved | |||
14 | 16384 | Erase all records (events, faults, alarms, disturbances,etc) | |||
15 | 32768 | Reserved | |||
F65 | Unsigned Integer | Memo alarm flag 1 | 0 | 1 | Phase Non I stage1 |
1 | 2 | Earth Non I stage1 | |||
2 | 4 | Negative Non I stage1 | |||
3 | 8 | Negative stage1 | |||
4 | 16 | Equation A | |||
5 | 32 | Equation B | |||
6 | 64 | Equation C | |||
7 | 128 | Equation D | |||
8 | 256 | Equation E | |||
9 | 512 | Equation F | |||
10 | 1024 | Equation G | |||
11 | 2048 | Equation H | |||
F66 | Unsigned Integer | Blocking Logic Mapping | 0 | 1 | CBF phase |
1 | 2 | CBF earth | |||
2 | 4 | CBF neg. | |||
3 | 8 | Dead zone | |||
4 | 16 | Pole discrepancy | |||
5 | 32 | tAux1 | |||
6 | 64 | tAux2 | |||
F98 | Unsigned Integer | auxiliary power supply self test status | 0 | 1 | -3V3 out of range |
1 | 2 | 5V0 out of range | |||
2 | 4 | 3V3 out of range | |||
3 | 8 | 12V out of range | |||
4 | 16 | 1V3 out of range | |||
5 | 32 | 0V out of range | |||
F99 | Unsigned Integer | Transformer self test status | 0 | 1 | Abnormal offset with transformer 1 |
1 | 2 | Abnormal offset with transformer 2 | |||
2 | 4 | Abnormal offset with transformer 3 | |||
3 | 8 | Abnormal offset with transformer 4 | |||
4 | 16 | Abnormal offset with transformer 5 | |||
5 | 32 | Abnormal offset with transformer 6 | |||
6 | 64 | Abnormal offset with transformer 7 | |||
7 | 128 | Abnormal offset with transformer 8 | |||
8 | 256 | Abnormal offset with transformer 9 | |||