Overview

The “Low active power and power factor protection” function measures power flow. It can be used for protection and monitoring of phase wise low active power, phase wise low power factor and phase wise reactive power and apparent power as service values.

For more detailed information on “Low active power and power factor protection” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Low active power and power factor protection LAPPGAPC 37_55

Signals & Setting Parameters


LAPPGAPC function block

LAPPGAPC function block

LAPPGAPC Input signals

LAPPGAPC Input signals
Name Type Default Description
I3P GROUP SIGNAL Three phase group signal for current
U3P GROUP SIGNAL Three phase group signal for voltage
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block all trip signals of the funtction

LAPPGAPC Output signals

LAPPGAPC Output signals
Name Type Description
TRLAP BOOLEAN Trip low active power
TRLPF BOOLEAN Trip low power factor
TRLPFL1 BOOLEAN Trip low power factor phase 1
TRLPFL2 BOOLEAN Trip low power factor phase 2
TRLPFL3 BOOLEAN Trip low power factor phase 3
STLAP BOOLEAN Start low active power
STLPF BOOLEAN Start low power factor
STLAPL1 BOOLEAN Start low active power phase 1
STLAPL2 BOOLEAN Start low active power phase 2
STLAPL3 BOOLEAN Start low active power phase 3
STLPFL1 BOOLEAN Start low power factor phase 1
STLPFL2 BOOLEAN Start low power factor phase 2
STLPFL3 BOOLEAN Start low power factor phase 3

LAPPGAPC Group settings (basic)

LAPPGAPC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off/On
OperationLAP Off
On
Off Operation low active power Off/On
OpMode 2 out of 3
1 out of 3
2 out of 3 Trip mode low active power 2out of 3 or 1 out of 3
LAP< 2.0 – 100.0 %SB 0.1 5.0 3 Phase start value for low active power in % of SBase
tOpLAP 0.000 – 60.000 s 0.001 0.010 Time delay to operate for low active power
OperationLPF Off
On
Off Operation low power factor Off/On
LPF< 0.00 – 1.00 0.01 0.40 Start value for low power factor
tOpLPF 0.000 – 60.000 s 0.001 0.010 Time delay to operate for low power factor

LAPPGAPC Group settings (advanced)

LAPPGAPC Group settings (advanced)
Name Values (Range) Unit Step Default Description
UGenZeroDb 0.0 – 100.0 %UB 0.1 30.0 Zero point Clamping in % of UBase
IGenZeroDb 0.0 – 100.0 %IB 0.1 3.0 Zero point clamping in % of IBase

LAPPGAPC Non group settings (basic)

LAPPGAPC Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

LAPPGAPC Monitored data

LAPPGAPC Monitored data
Name Type Values (Range) Unit Description
SL1 REAL MVA Apparent power for phase 1
SL2 REAL MVA Apparent power for phase 2
SL3 REAL MVA Apparent power for phase 3
PL1 REAL MW Active power for phase 1
PL2 REAL MW Active power for phase 2
PL3 REAL MW Active power for phase 3
QL1 REAL MVAr Reactive power for phase 1
QL2 REAL MVAr Reactive power for phase 2
QL3 REAL MVAr Reactive power for phase 3
PFL1 REAL Power factor phase 1
PFL2 REAL Power factor phase 2
PFL3 REAL Power factor phase 3

Logics & highlights


Active power calculation

Active power calculation

Power factor calculation

Power factor calculation

Logic diagram of Low active power and low power factor protection (LAPPGAPC)

Logic diagram of Low active power and low power factor protection (LAPPGAPC)

LAPPGAPC technical data

LAPPGAPC technical data