GE / Loss of excitation (ANSI 40) _ Element settings & highlights _ GU8033

Table of Contents

Overview

The operating characteristic of the “Loss of excitation” element is shaped out of two offset mho circles shifted down along the imaginary axis. The stage 1 characteristic is typically set to detect a loss of excitation for load conditions of 30% of the nominal or higher. The stage 2 characteristic is typically set to detect a loss of excitation for all load conditions.

For more detailed information on “Loss of excitation” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To view other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
G30, G60 4123 Loss Of Excitation Function 0 to 1 1 F102 0 (Disabled)
" 4124 Loss Of Excitation Signal Source 0 to 5 1 F167 0 (SRC 1)
" 4125 Loss Of Excitation Center 1 0.1 to 300 ohm 0.01 F001 1000
" 4126 Loss Of Excitation Radius 1 0.1 to 300 ohm 0.01 F001 800
" 4127 Loss Of Excitation UV Supervision Enable 1 0 to 1 1 F102 1 (Enabled)
" 4128 Loss Of Excitation Pickup Delay 1 0 to 65.535 s 0.001 F001 50
" 4129 Loss Of Excitation Center 2 0.1 to 300 ohm 0.01 F001 1200
" 412A Loss Of Excitation Radius 2 0.1 to 300 ohm 0.01 F001 1000
" 412B Loss Of Excitation UV Supervision Enable 2 0 to 1 1 F102 1 (Enabled)
" 412C Loss Of Excitation Pickup Delay 2 0 to 65.535 s 0.001 F001 500
" 412D Loss Of Excitation UV Supervision 0 to 1.25 pu 0.001 F001 700
" 412E Loss Of Excitation Block 0 to 4294967295 1 F300 0
" 4130 Loss Of Excitation Target 0 to 2 1 F109 0 (Self-reset)
" 4131 Loss Of Excitation Events 0 to 1 1 F102 0 (Disabled)
" 4132 Reserved (5 items) 0 to 65535 1 F001 0
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F167 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6
F300 0 : Off (This is boolean FALSE value), 1 : On (This is boolean TRUE value)

Logics & highlights


Loss of excitation operating characteristics

Loss of excitation operating characteristics

Loss of excitation logic

Loss of excitation logic