GE / Load encroachment _ Element settings & highlights _ GU8032

Table of Contents

Overview

The “Load encroachment” element responds to the positive-sequence voltage and current. It operates if the positive-sequence voltage is above a settable level and asserts its output signal that can be used to block selected protection elements, such as distance or phase overcurrent.

For more detailed information on “Load encroachment” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To view other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
D30, D60, F60, L60, L90, T60 416F Load Encroachment Function 0 to 1 1 F102 0 (Disabled)
" 4170 Load Encroachment Source 0 to 5 1 F167 0 (SRC 1)
" 4171 Load Encroachment Minimum Voltage 0.004 to 3 pu 0.001 F001 250
" 4172 Load Encroachment Reach 0.02 to 250 ohms 0.01 F001 100
" 4173 Load Encroachment Angle 5 to 50 degrees 1 F001 30
" 4174 Load Encroachment Pickup Delay 0 to 65.535 s 0.001 F001 0
" 4175 Load Encroachment Reset Delay 0 to 65.535 s 0.001 F001 0
" 4176 Load Encroachment Block 0 to 4294967295 1 F300 0
" 4178 Load Encroachment Target 0 to 2 1 F109 0 (Self-reset)
" 4179 Load Encroachment Events 0 to 1 1 F102 0 (Disabled)
" 417A Reserved (6 items) 0 to 65535 1 F001 0
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F167 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6
F300 0 : Off (This is boolean FALSE value), 1 : On (This is boolean TRUE value)

Logics & highlights


Load encroachment characteristic

Load encroachment characteristic

Load encroachment applied to distance element

Load encroachment applied to distance element

Load encroachment logic

Load encroachment logic

Definition of Setting Parameters


LOAD ENCROACHMENT MIN VOLT — This setting specifies the minimum positive-sequence voltage required for operation of the element. When the voltage is below this threshold, a blocking signal is not asserted by the element. When selecting this setting, remember that the D60 measures the phase-to-ground sequence voltages regardless of the VT connection.

LOAD ENCROACHMENT REACH — This setting specifies the resistive reach of the element as shown in the Load Encroachment Characteristic diagram. Enter this setting in secondary ohms and calculate it as the positive-sequence resistance seen by the relay under maximum load conditions and unity power factor.

LOAD ENCROACHMENT ANGLE — This setting specifies the size of the blocking region as shown on the Load Encroachment Characteristic diagram and applies to the positive-sequence impedance.