Siemens / “Line” function group _ Setting & highlights _ SI5200

Table of Contents

Overview

In the “Line” function group, all of the functions that are necessary for protecting and monitoring a line can be used. The Line function group also contains the measuring functions.

For more detailed information on “Line” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported function groups, click here.


Structure of the Line Function Group

Structure of the Line Function Group

Structure/Embedding of the Process Monitor (FG Line)

Structure/Embedding of the Process Monitor (FG Line)

Setting Parameters


Setting parameters for Line Function Group

Addr. Parameter C Setting Options Default Setting
Rated values
_:9001:101 General:Rated current   1 A to 100000 A 1000 A
_:9001:102 General:Rated voltage   0.20 kV to 1200.00 kV 400.00 kV
Line data
_:9001:149 General:Neutral point   grounded
suppress. coil grounded
isolated
grounded
_:9001:112 General:C1 per length unit 1 A 0.000 °F/km to 100000.000
°F/km
0.010 °F/km
5 A 0.000 °F/km to 500000.000
°F/km
0.050 °F/km
_:9001:148 General:C0 per length unit 1 A 0.000 °F/km to 100000.000
°F/km
0.010 °F/km
5 A 0.000 °F/km to 500000.000
°F/km
0.050 °F/km
_:9001:113 General:X per length unit 1 A 0.0010 Ω/km to 9.5000 Ω/km 0.0525 Ω/km
5 A 0.0002 Ω/km to 1.9000 Ω/km 0.0105 Ω/km
_:9001:114 General:Line length   0.10 km to 1000.00 km 60.00 km
_:9001:108 General:Line angle   10.00 ° to 89.00 ° 85.00 °
_:9001:104 General:Kr   -0.33 to 11.00 1.00
_:9001:105 General:Kx   -0.33 to 11.00 1.00
_:9001:118 General:K0   0.000 to 11.000 1.000
_:9001:150 General:Angle (K0)   -180.00 ° to 180.00 ° 0.00 °
_:9001:106 General:KmR   0.00 to 8.00 1.00
_:9001:107 General:KmX   0.00 to 8.00 1.00
_:9001:124 General:Km0   0.000 to 8.000 1.000
_:9001:125 General:Angle (Km0)   -180.00 ° to 180.00 ° 0.00 °
_:9001:109 General:Gnd.curr.ratio(Mut Comp)   50 % to 95 % 85 %
_:9001:119 General:CT saturation detection   no
yes
no
_:9001:120 General:CT saturation threshold 1 A 0.030 A to 125.000 A 10.000 A
5 A 0.150 A to 625.000 A 50.000 A
_:9001:111 General:Series compensa- tion   no
yes
no
_:9001:110 General:Series capacit. reactance 1 A 0.000 Ω to 600.000 Ω 0.000 Ω
5 A 0.000 Ω to 120.000 Ω 0.000 Ω
Closure detec.
_:1131:4681:10 1 Closure detec.:Operating mode   Manual close only
I open and V open
CB and I open
I open
Manual close only
_:1131:4681:10 2 Closure detec.:Action time after closure   0.01 s to 60.00 s 0.05 s
_:1131:4681:10 3 Closure detec.:Min. time feeder open   0.05 s to 60.00 s 0.25 s
1pol.open det.
_:1131:4711:10 1 1pol.open det.:Operating mode   off
with measurement
CB and I open
with measurement

Setting parameters for Process Monitor: Current-Flow Criterion

Addr. Parameter C Setting Options Default Setting
Breaker settings
_:2311:112 General:Current thresh. CB open 1 A @ 100 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 100 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A
_:2311:136 General:Op. mode BFP   unbalancing
I> query
unbalancing

Setting parameters for Process Monitor: Closure Detection

Addr. Parameter C Setting Options Default Setting
Closure detec.
_:4681:101 Closure detec.:Operating mode   Manual close only
Iopen,Vopen,ManCl
CB, Iopen, ManCl
Iopen, ManCl
Manual close only
_:4681:102 Closure detec.:Action time after closure   0.01 s to 60.00 s 0.05 s
_:4681:103 Closure detec.:Min. time feeder open   0.05 s to 60.00 s 0.25 s

Setting parameters for Process Monitor: Voltage Criterion (Optional)

Addr. Parameter C Setting Options Default Setting
Volt.criterion
_:101 Volt.criterion:Threshold U open   0.300 V to 170.000 V 51.960 V

Setting parameters for Process Monitor: Cold-Load Pickup Detection (Optional)

Addr. Parameter C Setting Options Default Setting
Cold-load PU
_:1 Cold-load PU:Mode   off
on
test
off
_:101 Cold-load PU:Operating mode   I open
CB and I open
I open
_:102 Cold-load PU:Dropout threshold current 1 A @ 100 Irated 0.030 A to 10.000 A 1.000 A
5 A @ 100 Irated 0.15 A to 50.00 A 5.00 A
1 A @ 50 Irated 0.030 A to 10.000 A 1.000 A
5 A @ 50 Irated 0.15 A to 50.00 A 5.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 5.000 A
_:103 Cold-load PU:Dropout delay curr.crit.   1sto600 s 600s
_:104 Cold-load PU:Dropout delay CB closed   1 s to 21600 s 3600 s
_:105 Cold-load PU:Min. CB- open time   0 s to 21600 s 3600 s

Setting parameters for Process Monitor:Closure detec.

Addr. Parameter C Setting Options Default Setting
Closure detec.
_:4681:101 Closure detec.:Operating mode   Manual close only
CB and I open
I open and V open
I open
Manual close only
_:4681:102 Closure detec.:Action time after closure   0.01 s to 60.00 s 0.05 s
_:4681:103 Closure detec.:Min. time feeder open   0.05 s to 60.00 s 0.25 s

Logic Diagrams & highlights


Operational Measured Values of the Function Group Line

Operational Measured Values of the Function Group Line

Generation of a Pickup Indication of the Line Function Group

Generation of a Pickup Indication of the Line Function Group

Generation of an Operate Indication of the Line Function Group

Generation of an Operate Indication of the Line Function Group

Logic Diagram of the Overall Function Process Monitor

Logic Diagram of the Overall Function Process Monitor

Logic Diagram of the Current-Flow Criterion Function Block

Logic Diagram of the Current-Flow Criterion Function Block

Logic Diagram of the Circuit-Breaker Condition for the Protected-Object Function Block

Logic Diagram of the Circuit-Breaker Condition for the Protected-Object Function Block

Logic Diagram of the Closure-Detection Function Block

Logic Diagram of the Closure-Detection Function Bloc

Logic Diagram of the 1-Pole Open Detector Function Block

Logic Diagram of the 1-Pole Open Detector Function Block

Logic Diagram of the Voltage-Criterion Function Block

Logic Diagram of the Voltage-Criterion Function Block

Logic Diagram of the Cold-Load Pickup Detection Function Block

Logic Diagram of the Cold-Load Pickup Detection Function Block