Siemens / Line differential protection function (ANSI 87L) _ Setting & highlights _ SI5011

Table of Contents

Overview

The “Line differential protection” function is a selective short-circuit protection for overhead lines, cables, and busbars with single-side and multiside infeed in radial, looped, or meshed systems. It allows instantaneous tripping on 2 to 6 line ends if short circuits occur, works strictly phase-selectively, allows protection of a transformer in the protection range of the line, and becomes more sensitive when using charging-current compensation (Ic compensat.).

For more detailed information on “Line differential protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Line differential protection Function

Setting Parameters


General setting parameters

Addr. Parameter C Setting Options Default Setting
General
_:2311:1 General:Mode   off
on
test
off
_:2311:102 General:Min. current for release 1 A @ 100 Irated 0.000 A to 35.000 A 0.000 A
5 A @ 100 Irated 0.00 A to 175.00 A 0.00 A
1 A @ 50 Irated 0.000 A to 35.000 A 0.000 A
5 A @ 50 Irated 0.00 A to 175.00 A 0.00 A
1 A @ 1.6 Irated 0.000 A to 1.600 A 0.000 A
5 A @ 1.6 Irated 0.000 A to 8.000 A 0.000 A
_:2311:104 General:Supervision Idiff   no
yes: reporting only
yes: block diff. prot.
block diff.

Setting parameters for Stage I-DIFF

Addr. Parameter C Setting Options Default Setting
I-DIFF
_:3451:1 I-DIFF:Mode   off
on
on
_:3451:2 I-DIFF:Operate & flt.rec. blocked   no
yes
no
_:3451:27 I-DIFF:Blk. w. inrush curr. detect.   no
yes
no
_:3451:3 I-DIFF:Threshold 1 A @ 100 Irated 0.100 A to 20.000 A 0.300 A
5 A @ 100 Irated 0.50 A to 100.00 A 1.50 A
1 A @ 50 Irated 0.100 A to 20.000 A 0.300 A
5 A @ 50 Irated 0.50 A to 100.00 A 1.50 A
_:3451:101 I-DIFF:Thresh. switch onto fault 1 A @ 100 Irated 0.100 A to 20.000 A 0.300 A
5 A @ 100 Irated 0.50 A to 100.00 A 1.50 A
1 A @ 50 Irated 0.100 A to 20.000 A 0.300 A
5 A @ 50 Irated 0.50 A to 100.00 A 1.50 A
_:3451:102 I-DIFF:Delay 1-phase pickup   0.00 s to 0.50 s 0.04 s
_:3451:6 I-DIFF:Operate delay   0.00 s to 60.00 s 0.00 s

Setting parameters for Stage I-DIFF Fast 2

Addr. Parameter C Setting Options Default Setting
I-DIFF fast 2
_:18211:1 I-DIFF fast 2:Mode   off
on
on
_:18211:2 I-DIFF fast 2:Operate & flt.rec. blocked   no
yes
no
_:18211:3 I-DIFF fast 2:Threshold 1 A @ 100 Irated 0.500 A to 100.000 A 1.000 A
5 A @ 100 Irated 2.50 A to 500.00 A 5.00 A
1 A @ 50 Irated 0.500 A to 100.000 A 1.000 A
5 A @ 50 Irated 2.50 A to 500.00 A 5.00 A
_:18211:101 I-DIFF fast 2:Thresh. switch onto fault 1 A @ 100 Irated 0.500 A to 100.000 A 1.000 A
5 A @ 100 Irated 2.50 A to 500.00 A 5.00 A
1 A @ 50 Irated 0.500 A to 100.000 A 1.000 A
5 A @ 50 Irated 2.50 A to 500.00 A 5.00 A
_:18211:106 I-DIFF fast 2:Delay 1- phase pickup   0.00 s to 0.50 s 0.04 s

Setting parameters for Stage I-DIFF Fast

Addr. Parameter C Setting Options Default Setting
I-DIFF fast
_:3481:1 I-DIFF fast:Mode   off
on
on
_:3481:2 I-DIFF fast:Operate & flt.rec. blocked   no
yes
no
_:3481:3 I-DIFF fast:Threshold 1 A @ 100 Irated 0.800 A to 100.000 A 1.000 A
5 A @ 100 Irated 4.000 A to 500.000 A 5.000 A
1 A @ 50 Irated 0.800 A to 100.000 A 1.000 A
5 A @ 50 Irated 4.000 A to 500.000 A 5.000 A
_:3481:101 I-DIFF fast:Thresh. switch onto fault 1 A @ 100 Irated 0.800 A to 100.000 A 1.000 A
5 A @ 100 Irated 4.000 A to 500.000 A 5.000 A
1 A @ 50 Irated 0.800 A to 100.000 A 1.000 A
5 A @ 50 Irated 4.000 A to 500.000 A 5.000 A
_:3481:106 I-DIFF fast:Delay 1-phase pickup   0.00 s to 0.50 s 0.04 s

Setting parameters for Remote Tripping

Addr. Parameter C Setting Options Default Setting
General
_:5551:1 Remote trip.:Mode   off
on
on
_:5551:100 Remote trip.:Transmit- ting   no
yes
yes
_:5551:101 Remote trip.:Receiving   yes
report only
yes
Intertrip
_:5551:103 Remote trip.:Send delay   0.00 s to 30.00 s 0.02 s
_:5551:104 Remote trip.:Send prolongation   0.00 s to 30.00 s 0.00 s

Setting parameters in case of Transformer in Protection Range

Addr. Parameter C Setting Options Default Setting
Transformer
_:103 Transformer:Voltage vector group nb.   0 to 11 0
_:104 Transformer:Current vector group nb.   0 to 11 0
_:105 Transformer:Residual curr. elimination   no
yes
 

Setting parameters for Charging-Current Compensation Ic-Compensation

Addr. Parameter C Setting Options Default Setting
Ic-compensat.
_:1 Ic-compensat.:Mode   off
on
on
_:101 Ic-compensat.:Ic-stabiliza- tion/Ic-rated   1.0 to 4.0 1.5
_:102 Ic-compensat.:Total line length   0.1 km to 1000.0 km 100.0 km

Logic Diagrams & highlights


Differential Protection for a Line with 2 Ends

Differential Protection for a Line with 2 Ends

Differential Protection for a Line with 3 Ends

Differential Protection for a Line with 3 Ends

Differential Protection for a Line with 3 Ends with 2 Devices

Differential Protection for a Line with 3 Ends with 2 Devices

Operate Curve of the Differential Protection

Operate Curve of the Differential Protection

Approximation of the Current-Transformer Errors

Approximation of the Current-Transformer Errors

Pickup Characteristic of the I-DIFF Stage

Pickup Characteristic of the I-DIFF Stage

Pickup Characteristic of the I-DIFF fast 2 Stage

Pickup Characteristic of the I-DIFF fast 2 Stage

Logic of the Transmit Direction

Logic of the Transmit Direction

Logic of the Receive Direction

Logic of the Receive Direction

Pickup Logic

Pickup Logic

Trip Logic

Trip Logic

Differential Protection with 3 Devices for a Line with a Feeder

Differential Protection with 3 Devices for a Line with a Feeder

Logic for Logging off the Function

Logic for Logging off the Function

External Push-Button Wiring for Logging off the Local Line Differential Protection

External Push-Button Wiring for Logging off the Local Line Differential Protection

External Switch Wiring for Logging off the Local Line Differential Protection

External Switch Wiring for Logging off the Local Line Differential Protection

Ground Fault Outside of the Transforme

Ground Fault Outside of the Transformer

Charging-Current Compensation for a Line with 2 Ends (1-Phase System)

Charging-Current Compensation for a Line with 2 Ends (1-Phase System)