Overview

The “Interturn fault detection” element is a complement to the percent differential function. It detects interturn fault conditions using voltage compensated differential currents. The voltage-based compensation term cancels out steady state differential current of each phase. The resulting compensated differential current is sensitive enough to pick up turn-to-turn faults.

For more detailed information on “Interturn fault detection” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
T35, T60 D9A0 Interturn Fault Detect 1 Function 0 to 1 1 F102 0 (Disabled)
" D9A1 Interturn Fault Detect 1 Prot Transformer 0 to 1 1 F690 0 (XFMR 1)
" D9A2 Interturn Fault Detect 1 Supv Src 0 to 5 1 F167 0 (SRC 1)
" D9A3 Interturn Fault Detect 1 Autoset Mode 0 to 2 1 F691 1 (AUTO)
" D9A4 Interturn Fault Detect 1 K-Fact Updt 1 to 240 min 1 F001 30
" D9A5 Force Interturn 1 K UP 0 to 4294967295 1 F300 0
" D9A7 Interturn Fault Detect 1 Pickup 0.01 to 0.5 pu 0.001 F001 50
" D9A8 Interturn Fault Detect 1 Pickup Delay 0.02 to 60 s 0.01 F001 20
" D9A9 Interturn Fault Detect 1 Block 0 to 4294967295 1 F300 0
" D9AB Interturn Fault Detect 1 Target 0 to 2 1 F109 0 (Self-reset)
" D9AC Interturn Fault Detect 1 Events 0 to 1 1 F102 0 (Disabled)
" D9AE …Repeated for Interturn Fault Detect 2          
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F167 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6
F690 0=XFMR, 1=XFMR 2
F691 0=NONE, 1=AUTO, 2=Manual

Logics & highlights


Transformer interturn fault detection logic

Transformer interturn fault detection logic