Overview
The “Instantaneous tripping at switch onto fault” function serves for immediate tripping when switching onto a fault. The function does not have its own measurement and must be linked to another protection function with the pickup (measurement).
For more detailed information on “Instantaneous tripping at switch onto fault” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported functions, click here.
Structure/Embedding of the Function
Setting Parameters
Setting parameters for Instantaneous tripping at switch onto fault
Addr. | Parameter | C | Setting Options | Default Setting |
Stage 1 | ||||
_:5941:1 | Stage 1:Mode | off on test |
off | |
_:5941:2 | Stage 1:Operate & flt.rec. blocked | no yes |
no | |
_:5941:6 | Stage 1:Operate delay | 0.00 s to 60.00 s | 0.00 s | |
_:5941:102 | Stage 1:Configuration | Setting options depend on config- uration | ||