The “Instantaneous tripping at switch onto fault” function serves for immediate tripping when switching onto a fault. The function does not have its own measurement and must be linked to another protection function with the pickup (measurement).

For more detailed information on “Instantaneous tripping at switch onto fault” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Instantaneous tripping at switch onto fault Function

Setting Parameters


Setting parameters for Instantaneous tripping at switch onto fault

Addr. Parameter C Setting Options Default Setting
Stage 1
_:5941:1 Stage 1:Mode   off
on
test
off
_:5941:2 Stage 1:Operate & flt.rec. blocked   no
yes
no
_:5941:6 Stage 1:Operate delay   0.00 s to 60.00 s 0.00 s
_:5941:102 Stage 1:Configuration   Setting options depend on config- uration  

Logic Diagrams & highlights


Logic Diagram of the Stage Instantaneous Tripping at Switch onto Fault

Logic Diagram of the Stage Instantaneous Tripping at Switch onto Fault