Table of Contents

GE / Instantaneous overcurrent (ANSI 50) _ Element settings & highlights _ GU8014

Table of Contents

Overview

The “Instantaneous overcurrent” element is used primarily for supervising main protection trip commands on a per-breaker basis (that is, differential, breaker failure, and end fault protection). It responds to a single-phase current. Instantaneous Overcurrent supervision can also be used to prevent tripping feeders with low currents or for definite time backup protection.

For more detailed information on “Instantaneous overcurrent” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To view other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
B90 5137 Instantaneous Overcurrent 1 Function 0 to 1 1 F102 0 (Disabled)
" 5138 Instantaneous Overcurrent 1 CT 0 to 23 1 F400 0
" 5139 Instantaneous Overcurrent 1 Pickup 0.005 to 30 pu 0.001 F001 1200
" 513A Instantaneous Overcurrent 1 Pickup Delay 0 to 65.535 s 0.001 F001 0
" 513B Instantaneous Overcurrent 1 Reset Delay 0 to 65.535 s 0.001 F001 0
" 513C Instantaneous Overcurrent 1 Block 0 to 4294967295 1 F300 0
" 513E Instantaneous Overcurrent 1 Target 0 to 2 1 F109 0 (Self-reset)
" 513F Instantaneous Overcurrent 1 Events 0 to 1 1 F102 0 (Disabled)
" 5140 Reserved 0 to 65535 1 F001 0
" 5141 …Repeated for Instantaneous Overcurrent 2          
" 514B …Repeated for Instantaneous Overcurrent 3          
" 5155 …Repeated for Instantaneous Overcurrent 4          
" 515F …Repeated for Instantaneous Overcurrent 5          
" 5169 …Repeated for Instantaneous Overcurrent 6          
" 5173 …Repeated for Instantaneous Overcurrent 7          
" 517D …Repeated for Instantaneous Overcurrent 8          
" 5187 …Repeated for Instantaneous Overcurrent 9          
" 5191 …Repeated for Instantaneous Overcurrent 10          
" 519B …Repeated for Instantaneous Overcurrent 11          
" 51A5 …Repeated for Instantaneous Overcurrent 12          
" 51AF …Repeated for Instantaneous Overcurrent 13          
" 51B9 …Repeated for Instantaneous Overcurrent 14          
" 51C3 …Repeated for Instantaneous Overcurrent 15          
" 51CD …Repeated for Instantaneous Overcurrent 16          
" 51D7 …Repeated for Instantaneous Overcurrent 17          
" 51E1 …Repeated for Instantaneous Overcurrent 18          
" 51EB …Repeated for Instantaneous Overcurrent 19          
" 51F5 …Repeated for Instantaneous Overcurrent 20          
" 51FF …Repeated for Instantaneous Overcurrent 21          
" 5209 …Repeated for Instantaneous Overcurrent 22          
" 5213 …Repeated for Instantaneous Overcurrent 23          
" 521D …Repeated for Instantaneous Overcurrent 24          
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F300 0 : Off (This is boolean FALSE value), 1 : On (This is boolean TRUE value)
F400 0: Card 1 Contact 1 to 4, 1: Card 1 Contact 5 to 8, 2: Card 2 Contact 1 to 4, 3: Card 2 Contact 5 to 8, 4: Card 3 Contact 1 to 4, 5: Card 3 Contact 5 to 8

Logics & highlights


Instantaneous overcurrent logic

Instantaneous overcurrent logic

error: Content is protected !!