Table of Contents

GE / Instantaneous differential (ANSI 50/87) _ Element settings & highlights _ GU8062

Table of Contents

Overview

The “Instantaneous differential” element acts as an instantaneous overcurrent element responding to the measured differential current magnitude (filtered fundamental frequency component) and applying a user-selectable pickup threshold.

For more detailed information on “Instantaneous differential” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
T35, T60 3E74 Inst Differential Function 0 to 1 1 F102 0 (Disabled)
" 3E75 Inst Differential Pickup 2 to 30 pu 0.001 F001 8000
" 3E76 Inst Differential Block 0 to 4294967295 1 F300 0
" 3E78 Inst Differential Target 0 to 2 1 F109 0 (Self-reset)
" 3E79 Inst Differential Events 0 to 1 1 F102 0 (Disabled)
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled