Overview

The “Impedance protection” function protects transformers as backup protection for transformer differential protection. It is used as a backup protection for the transformer, and the generator in the block units of power stations and functions as backup protection in the event of energy recovery to faults in the upstream electrical power system beyond a transformer.

For more detailed information on “Impedance protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Impedance Protection Function

Setting Parameters


Setting parameters for Impedance protection function

Addr. Parameter C Setting Options Default Setting
General
_:2311:1 General:Mode   off
on
test
on
_:2311:102 General:Loop selection   All loops
Current-dependent
All loops
_:2311:103 General:Min. phase- current thresh 1 A @ 100 Irated 0.030 A to 35.000 A 0.100 A
5 A @ 100 Irated 0.15 A to 175.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A
_:2311:104 General:Overcurrent threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.300 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.300 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.300 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.500 A
_:2311:105 General:Undervoltage seal in   no
yes
no
_:2311:106 General:V-seal-in threshold   0.300 V to 340.000 V 80.019 V
_:2311:107 General:Duration of V- seal-in time   0.00 s to 60.00 s 4.00 s
TZ 1
_:15301:1 TZ 1:Mode   off
on
test
on
_:15301:2 TZ 1:Operate & flt.rec. blocked   no
yes
no
_:15301:27 TZ 1:Blk. w. inrush curr. detect.   no
yes
no
_:15301:102 TZ 1:X reach (ph-g) 1 A 0.100 Ω to 600.000 Ω 2.500 Ω
5 A 0.020 Ω to 120.000 Ω 0.500 Ω
_:15301:103 TZ 1:X reach (ph-ph) 1 A 0.100 Ω to 600.000 Ω 2.500 Ω
5 A 0.020 Ω to 120.000 Ω 0.500 Ω
_:15301:104 TZ 1:R reach (ph-g) 1 A 0.100 Ω to 600.000 Ω 2.500 Ω
5 A 0.020 Ω to 120.000 Ω 0.500 Ω
_:15301:105 TZ 1:R reach (ph-ph) 1 A 0.100 Ω to 600.000 Ω 1.250 Ω
5 A 0.020 Ω to 120.000 Ω 0.250 Ω
_:15301:109 TZ 1:Directional mode   non-directional
forward
reverse
reverse
_:15301:6 TZ 1:Operate delay   0.00 s to 60.00 s; ∞ 0.30 s

Logic Diagrams & highlights


Transformation of a 2-Phase Short-Circuit Current

Transformation of a 2-Phase Short-Circuit Current

Transformation of a 1-Phase Short-Circuit Current

Transformation of a 1-Phase Short-Circuit Current

Impedance Measurement with a 2-Phase Short Circuit

Impedance Measurement with a 2-Phase Short Circuit

Impedance Measurement with a 1-Phase Short Circuit

Impedance Measurement with a 1-Phase Short Circuit

Effective Parameter for Loop Release for All Loops

Effective Parameter for Loop Release for All Loops

Effective Parameter in Current-Dependent Loop Release

Effective Parameter in Current-Dependent Loop Release

Direction-Characteristic Curve in the R-X Diagram

Direction-Characteristic Curve in the R-X Diagram

Operate Curve with Quadrilateral Characteristic

Operate Curve with Quadrilateral Characteristic

Example of a Network Protection Application

Example of a Network Protection Application

System Configuration and Possible Time Grading

System Configuration and Possible Time Grading

System Configuration and Possible Time Grading

System Configuration and Possible Time Grading