Overview
Generally, the “Hybrid permissive overreaching transfer trip” scheme uses an overreaching zone 2 distance element to essentially compare the direction to a fault at all terminals of the line. The scheme is intended for three-terminal and two-terminal applications with weak-infeed conditions.
For more detailed information on “Hybrid permissive overreaching transfer trip” scheme, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.
To see other supported elements, click here.
Setting Parameters
Modbus memory map for Setting parameters
Products | Hex address | Register name | Range | Units | Step | Format | Default |
D60, L90 | 428A | Hybrid POTT 1P Scheme Function | 0 to 1 | — | 1 | F102 | 0 (Disabled) |
" | 428B | Hybrid POTT 1P Permissive Echo | 0 to 2 | — | 1 | F199 | 0 (Disabled) |
" | 428C | Hybrid POTT 1P Rx Pickup Delay | 0 to 65.535 | s | 0.001 | F001 | 0 |
" | 428D | Hybrid POTT 1P Trans Block Pickup Delay | 0 to 65.535 | s | 0.001 | F001 | 20 |
" | 428E | Hybrid POTT 1P Trans Block Reset Delay | 0 to 65.535 | s | 0.001 | F001 | 90 |
" | 428F | Hybrid POTT 1P Echo Duration | 0 to 65.535 | s | 0.001 | F001 | 100 |
" | 4290 | Hybrid POTT 1P Echo Lockout | 0 to 65.535 | s | 0.001 | F001 | 250 |
" | 4291 | Hybrid POTT 1P Seal In Delay | 0 to 65.535 | s | 0.001 | F001 | 0 |
" | 4292 | Hybrid POTT 1P Ground Directional Overcurrent Forward | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 4294 | Hybrid POTT 1P Gnd Directional Overcurrent Reverse | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 4296 | Hybrid POTT 1P Number of Communication Bits | 0 to 2 | — | 1 | F198 | 0 (1) |
" | 4297 | Hybrid POTT 1P Rx1 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 4299 | Hybrid POTT 1P Rx2 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 429B | Hybrid POTT 1P Rx3 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 429D | Hybrid POTT 1P Rx4 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 429F | Hybrid POTT 1P Target | 0 to 2 | — | 1 | F109 | 0 (Self-reset) |
" | 42A0 | Hybrid POTT 1P Event | 0 to 1 | — | 1 | F102 | 0 (Disabled) |
" | 42A1 | Hybrid POTT 1P Echo Condition | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 42A3 | Hybrid POTT 1P Weak Infeed | 0 to 2 | — | 1 | F199 | 1 (Enabled) |
" | 42A4 | Hybrid POTT 1P Weak Infeed Condition | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 42A6 | Hybrid POTT 1P Block | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 42A8 | Reserved (3 items) | 0 to 1 | — | 1 | F001 | 0 |
F102 | 0 = Disabled, 1 = Enabled | ||||||
F109 | 0 = Self-reset, 1 = Latched, 2 = Disabled | ||||||
F198 | 0 = 1, 1 = 2, 2 = 4 | ||||||
F199 | 0 = Disabled, 1 = Enabled, 2 = Custom | ||||||