The “Hottest spot temperature” element provides a mechanism to detect abnormal winding hottest-spot temperatures inside the transformer. It can be set to alarm or trip in cases where the computed hottest-spot temperature is above the pickup threshold for a user-specified time (considered as transformer overheating).

For more detailed information on “Hottest spot temperature” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
G30, T35, T60 3E3E Transformer Hottest Spot Function 0 to 1 1 F102 0 (Disabled)
" 3E3F Transformer Hottest Spot Pickup 50 to 300 °C 1 F001 140
" 3E40 Transformer Hottest Spot Delay 0 to 30000 min 1 F001 1
" 3E41 Transformer Hottest Spot Block 0 to 4294967295 1 F300 0
" 3E43 Transformer Hottest Spot Target 0 to 2 1 F109 0 (Self-reset)
" 3E44 Transformer Hottest Spot Events 0 to 1 1 F102 0 (Disabled)
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled

Logics & highlights


Transformer hottest-spot temperature logic

Transformer hottest-spot temperature logic