Table of Contents

GE / Harmonic detection _ Element settings & highlights _ GU8235

Table of Contents

Overview

The “Harmonic detection” element monitors one of the selected quantities, including DC offset, 2nd to 5th harmonic, or Total Harmonics Distortion (THD), that are present in the phase currents and ground current. It adds delay or blocking to prevent undesired operation. Harmonics are calculated and presented as a percent value relative to the fundamental frequency
phasor magnitude.

For more detailed information on “Harmonic detection” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
C60, C95, D30, D60, F35, F60, G30, G60, L30, L90, N60, T35, T60 DB00 Harmonic Detection 1 Function 0 to 1 1 F102 0 (Disabled)
" DB01 Harmonic Detection 1 Source 0 to 5 1 F167 0 (SRC 1)
" DB02 Harmonic Detection 1 Harmonic 0 to 5 1 F682 1 (2nd)
" DB03 Harmonic Detection 1 Min Op Current 0.01 to 1 pu 0.01 F001 20
" DB04 Harmonic Detection 1 Max Op Current 1 to 30 pu 0.01 F001 500
" DB05 Harmonic Detection 1 Phases for Operation 0 to 3 1 F689 0 (ANY ONE)
" DB06 Harmonic Detection 1 Pickup 2 to 100 % 0.1 F001 200
" DB07 Harmonic Detection 1 Ground Min Op Current 0.1 to 1 pu 0.01 F001 20
" DB08 Harmonic Detection 1 Ground Max Op Current 1 to 30 pu 0.01 F001 100
" DB09 Harmonic Detection 1 Ground Max Op Current 0.1 to 100 % 0.1 F001 200
" DB0A Harmonic Detection 1 Pickup Delay 0 to 600 s 0.01 F001 0
" DB0B Harmonic Detection 1 Block 0 to 4294967295 1 F300 0
" DB0D Harmonic Detection 1 Events 0 to 1 1 F102 0 (Disabled)
" DB0E Harmonic Detection 1 Target 0 to 2 1 F109 0 (Self-reset)
" DB0F …Repeated for Harmonic Detection 2          
" DB1E …Repeated for Harmonic Detection 3          
" DB2D …Repeated for Harmonic Detection 4          
" DB3C …Repeated for Harmonic Detection 5          
" DB4B …Repeated for Harmonic Detection 6          
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F167 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6
F682 0 = DC, 1 = 2nd, 2 = 3rd, 3 = 4th, 4 = 5th, 5 = THD
F689 0 = ANY ONE, 1 = ANY TWO, 2 = ALL THREE, 3 = AVERAGE

Logics & highlights


Harmonic detection logic

Harmonic detection logic