Overview

The “Loss of life” element detects the accumulated total consumed transformer life. This element can be set to issue an alarm or trip when the actual accumulated transformer life becomes larger than the user-specified loss of life pickup value.

For more detailed information on “Loss of life” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
G30, T35, T60 3E4C Transformer Loss of Life Function 0 to 1 1 F102 0 (Disabled)
" 3E4D XFMR LOL Initial Value 0 to 500000 hrs 1 F003 0
" 3E4F Transformer Loss of Life Pickup 0 to 500000 hrs 1 F003 180000
" 3E51 Transformer Loss Of Life Block 0 to 4294967295 1 F300 0
" 3E53 Transformer Loss of Life Target 0 to 2 1 F109 0 (Self-reset)
" 3E54 Transformer Loss of Life Events 0 to 1 1 F102 0 (Disabled)
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled

Logics & highlights


Transformer loss of life logic

Transformer loss of life logic