GE / Ground time overcurrent (ANSI 51G, IEC PTOC) _ Element settings & highlights _ GU8025

Table of Contents

Overview

The “Ground time overcurrent” element can provide a required time-delay operating characteristic versus the applied current or be used as a simple definite time element. The ground current input value is the quantity measured by the ground input CT and is the fundamental phasor or RMS magnitude. Two methods of resetting operation are available: “Timed” and “Instantaneous”.

For more detailed information on “Ground time overcurrent” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
B30, C60, C70, C95, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60, T35, T60 3917 Ground Time Overcurrent 1 Function 0 to 1 1 F102 0 (Disabled)
" 3918 Ground Time Overcurrent 1 Signal Source 0 to 5 1 F167 0 (SRC 1)
" 3919 Ground Time Overcurrent 1 Input 0 to 1 1 F122 0 (Phasor)
" 391A Ground Time Overcurrent 1 Pickup 0.02 to 30 pu 0.001 F001 1000
" 391B Ground Time Overcurrent 1 Curve 0 to 16 1 F103 0 (IEEE Mod
Inv)
" 391C Ground Time Overcurrent 1 Multiplier 0 to 600 0.01 F001 100
" 391D Ground Time Overcurrent 1 Reset 0 to 1 1 F104 0
(Instantaneo us)
" 391E Ground Time Overcurrent 1 Block 0 to 4294967295 1 F300 0
" 3920 Ground Time Overcurrent 1 Target 0 to 2 1 F109 0 (Self-reset)
" 3921 Ground Time Overcurrent 1 Events 0 to 1 1 F102 0 (Disabled)
" 3922 Reserved (6 items) 0 to 1 1 F001 0
B30, C60, C70, C95, D30, D60, F35, F60, L30, L60, L90, M60, N60, T35, T60 3928 …Repeated for Ground Time Overcurrent 2          
B30, C60, C70, C95, D60, F35, F60, L90, M60, N60, T35, T60 3939 …Repeated for Ground Time Overcurrent 3          
" 394A …Repeated for Ground Time Overcurrent 4          
B30, C70, F35, N60, T35, T60 395B …Repeated for Ground Time Overcurrent 5          
" 396C …Repeated for Ground Time Overcurrent 6          
B30 397D …Repeated for Ground Time Overcurrent 7          
" 398E …Repeated for Ground Time Overcurrent 8          
" 399F …Repeated for Ground Time Overcurrent 9          
" 39B0 …Repeated for Ground Time Overcurrent 10          
" 39C1 …Repeated for Ground Time Overcurrent 11          
" 39D2 …Repeated for Ground Time Overcurrent 12          
" 39000 …Repeated for Ground Time Overcurrent 13          
" 39F4 …Repeated for Ground Time Overcurrent 14          
" 3A05 …Repeated for Ground Time Overcurrent 15          
" 3A16 …Repeated for Ground Time Overcurrent 16          
" 3A27 …Repeated for Ground Time Overcurrent 17          
" 3A38 …Repeated for Ground Time Overcurrent 18          
" 3A49 …Repeated for Ground Time Overcurrent 19          
" 3A5A …Repeated for Ground Time Overcurrent 20          
F102 0 = Disabled, 1 = Enabled
F103 0 = IEEE Mod Inv, 1 = IEEE Very Inv, 2 = IEEE Ext Inv, 3 = IEC Curve A, 4 = IEC Curve B, 5 = IEC Curve C, 6 = IEC Short Inv, 7 = IAC Ext Inv, 9 = IAC Inverse, 10 = IAC Short Inv, 11 = I2t, 12 = Definite Time, 13 = FlexCurve A, 14 = FlexCurve B, 15 = FlexCurve C, 16 = FlexCurve D
F104 0 = Instantaneous, 1 = Timed
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F122 0 = Phasor, 1 = RMS
F167 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6

Logics & highlights


Overcurrent curve types

Overcurrent curve types

IEEE curves

IEEE curve trip times (in seconds)
IEEE curve trip times (in seconds)

IEC curves

IEC curve trip times (in seconds)
IEC curve trip times (in seconds)

IAC curves

GE type IAC curve trip times
GE type IAC curve trip times

I2t curves


FlexCurves


Definite time curve


Ground TOC1 logic

Ground TOC1 logic