Siemens / “Generator diff” function group _ Setting & highlights _ SI5215

Table of Contents

Overview

The individual function-group types are stored in the “Generator diff” function group folder. The “Generator diff” function group contains the differential protection function and measured values relevant for protection functions. Device-specific protection and supervision functions can work in the “Generator side” function group. The scope depends on the selected type of protection concept. All of the functions needed for the protection and supervision of the generator are working in the “Generator stator” function group.

For more detailed information on “Generator diff” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported function groups, click here.


Generator Diff Function-Group Types

Generator Diff Function-Group Types

Function-Group Type Generator Differential Protection


Structure of the Generator Diff Function Group

Structure of the Generator Diff Function Group

Settings

Addr. Parameter C Setting Options Default Setting
General
_:91:149 General:Neutral point   grounded
isolated
grounded

Generation of Pickup Indication of the Generator Diff Function Group

Generation of Pickup Indication of the Generator Diff Function Group

Generation of Operate Indication of the Generator Diff Function Group

Generation of Operate Indication of the Generator Diff Function Group

Function-Group Type Generator Side


Structure of the Generator Side Function Group

Structure of the Generator Side Function Group

Write-Protected Settings

Addr. Parameter C Setting Options Default Setting
Rated values
_:1781:14671:101 General:Rated current   -1 A to -1 A 0 A
Side data
_:1781:14611:130 Further settings:Side number   not assigned
Side 1
Side 2
Side 3
Side 4
Side 5
not assigned
_:1781:14611:210 Further settings:MI3ph1 usesMeasP with ID   0 to 100 0
_:1781:14611:211 Further settings:MI3ph2 usesMeasP with ID   0 to 100 0
_:1781:14611:212 Further settings:MI3ph3 usesMeasP with ID   0 to 100 0
_:1781:14611:213 Further settings:MI3ph4 usesMeasP with ID   0 to 100 0
_:1781:14611:214 Further settings:M I-1ph uses MeasP with ID   0 to 100 0
_:1781:14611:215 Further settings:CT mismatch M I-3ph 1   0.000 to 100.000 0.000
_:1781:14611:216 Further settings:CT mismatch M I-3ph 1 IN   0.000 to 100.000 0.000
_:1781:14611:217 Further settings:CT mismatch M I-3ph 2   0.000 to 100.000 0.000
_:1781:14611:218 Further settings:CT mismatch M I-3ph 2 IN   0.000 to 100.000 0.000
_:1781:14611:219 Further settings:CT mismatch M I-3ph 3   0.000 to 100.000 0.000
_:1781:14611:220 Further settings:CT mismatch M I-3ph 3 IN   0.000 to 100.000 0.000
_:1781:14611:221 Further settings:CT mismatch M I-3ph 4   0.000 to 100.000 0.000
_:1781:14611:222 Further settings:CT mismatch M I-3ph 4 IN   0.000 to 100.000 0.000
_:1781:14611:223 Further settings:CT mismatch M I-1ph   0.000 to 100.000 0.000

Settings

Addr. Parameter C Setting Options Default Setting
Rated values
_:1781:14671:103 General:Rated apparent power   0.20 MVA to 5000.00 MVA 46.60 MVA
  General:Rated voltage   0.300 V to 340.000 V 1100.000 V
Measurements
_:1781:14611:158 Further settings:P, Q sign   not reversed
reversed
not reversed

Possible Operational Measured Values of Generator Side Function Group

Possible Operational Measured Values of Generator Side Function Group

Generation of Pickup Indication of the Generator Side Function Group

Generation of Pickup Indication of the Generator Side Function Group

Generation of Operate Indication of the Generator Side Function Group

Generation of Operate Indication of the Generator Side Function Group

Function-Group Type Generator Stator


Structure of the Generator Stator Function Group

Structure of the Generator Stator Function Group

Write-Protected Settings

Addr. Parameter C Setting Options Default Setting
Rated values
_:1781:14671:101 General:Rated current   1 A to 100 000 A 1000 A
Side data
_:1781:14611:130 Further settings:Side number   not assigned
Side 1
Side 2
not assigned
_:1781:14611:210 Further settings:MI3ph1 usesMeasP with ID   0 to 100 0
_:1781:14611:211 Further settings:MI3ph2 usesMeasP with ID   0 to 100 0
_:1781:14611:212 Further settings:MI3ph3 usesMeasP with ID   0 to 100 0
_:1781:14611:213 Further settings:MI3ph4 usesMeasP with ID   0 to 100 0
_:1781:14611:214 Further settings:M I-1ph uses MeasP with ID   0 to 100 0
_:1781:14611:215 Further settings:CT mismatch M I-3ph 1   0.000 to 100.000 0.000
_:1781:14611:216 Further settings:CT mismatch M I-3ph 1 IN   0.000 to 100.000 0.000
_:1781:14611:217 Further settings:CT mismatch M I-3ph 2   0.000 to 100.000 0.000
_:1781:14611:218 Further settings:CT mismatch M I-3ph 2 IN   0.000 to 100.000 0.000
_:1781:14611:219 Further settings:CT mismatch M I-3ph 3   0.000 to 100.000 0.000
_:1781:14611:220 Further settings:CT mismatch M I-3ph 3 IN   0.000 to 100.000 0.000
_:1781:14611:221 Further settings:CT mismatch M I-3ph 4   0.000 to 100.000 0.000
_:1781:14611:222 Further settings:CT mismatch M I-3ph 4 IN   0.000 to 100.000 0.000

Settings

Addr. Parameter C Setting Options Default Setting
Rated values
:103_:1781:14671 General:Rated apparent power   0.20 MVA to 5000.00 MVA 46.60 MVA
_:1781:14671:102 General:Rated voltage   0.300 V to 340.000 V 1100.000 V
_:1781:14671:101 General:Rated current   -1 A to -1 A 0 A
SGF3Har. conf.
_:1781:14671:105 General:V SGF connected to   neutr. transf.
broken-delta winding
not connected
neutr. transf.
Measurements
_:1781:14611:158 Further settings:P, Q sign   not reversed
reversed
not reversed
Add.Meas.Value
_:1781:18301:101 Add.Meas.Value:Synchro nous reactance   30.0 % to 300.0 % 180.0 %

Possible Operational Measured Values of Generator Stator Function Group

Possible Operational Measured Values of Generator Stator Function Group

Additional Measured Values

Additional Measured Values

Generation of Pickup Indication of the Generator Stator Function Group

Generation of Pickup Indication of the Generator Stator Function Group

Generation of Operate Indication of the Generator Stator Function Group

Generation of Operate Indication of the Generator Stator Function Group