Table of Contents

GE / Frequency rate of change (ANSI 81R) _ Element settings & highlights _ GU8225

Table of Contents

Overview

The “Frequency rate of change” element responds to rate of change of frequency with voltage, current and frequency supervision.

For more detailed information on “Frequency rate of change” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
D30, D60, F60, G30, G60, L30, L90, N60, T60 6CAE Frequency Rate of Change 1 Function 0 to 1 1 F102 0 (Disabled)
" 6CAF Frequency Rate of Change 1 OC Supervision 0.02 to 30 pu 0.001 F001 200
" 6CB0 Frequency Rate of Change 1 Min 20 to 80 Hz 0.01 F001 4500
" 6CB1 Frequency Rate of Change 1 Max 20 to 80 Hz 0.01 F001 6500
" 6CB2 Frequency Rate of Change 1 Pickup Delay 0 to 65.535 s 0.001 F001 0
" 6CB3 Frequency Rate of Change 1 Reset Delay 0 to 65.535 s 0.001 F001 0
" 6CB4 Frequency Rate of Change 1 Block 0 to 4294967295 1 F300 0
" 6CB6 Frequency Rate of Change 1 Target 0 to 2 1 F109 0 (Self-reset)
" 6CB7 Frequency Rate of Change 1 Events 0 to 1 1 F102 0 (Disabled)
" 6CB8 Frequency Rate of Change 1 Source 0 to 5 1 F167 0 (SRC 1)
" 6CB9 Frequency Rate of Change 1 Trend 0 to 2 1 F224 0
(Increasing)
" 6CBA Frequency Rate of Change 1 Pickup 0.1 to 15 Hz/s 0.01 F001 50
" 6CBB Frequency Rate of Change 1 OV Supervision 0.1 to 3 pu 0.001 F001 700
" 6CBC Reserved (3 items) 0 to 1 1 F001 0
" 6CBF …Repeated for Frequency Rate of Change 2          
D60, F60, G30, G60, L90, N60, T60 6CD0 …Repeated for Frequency Rate of Change 3          
" 6CE1 …Repeated for Frequency Rate of Change 4          
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F167 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6
F224 0 = Increasing, 1 = Decreasing, 2 = Bidirectional

Logics & highlights


Frequency rate of change logic

Frequency rate of change logic

error: Content is protected !!