Table of Contents

GE / Frequency out of band accumulation _ Element settings & highlights _ GU8226

Table of Contents

Overview

The “Frequency out of band accumulation” element provides diagnostic information and alarms based on the accumulated off-nominal frequency operation time of a turbine over several frequency bands, that can then be used to schedule maintenance or other action.

For more detailed information on “Frequency out of band accumulation” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
G30, G60 3D37 Frequency Out-Of-Band Accumulation Block 0 to 4294967295 1 F300 0
" 3D39 Frequency Out-Of-Band Accumulation Events Enable 0 to 1 1 F102 0 (Disabled)
" 3D3A Frequency Out-Of-Band Accumulator Function Enable Array (7 items) 0 to 1 1 F102 0 (Disabled)
" 3D41 Frequency Out-Of-Band Accumulator Lower Frequency Array (7 items) 20 to 70 Hz 0.01 F001 6000
" 3D48 Frequency Out-Of-Band Accumulator Min Value V A 0.1 to 1.25 pu 0.01 F001 10
" 3D49 Frequency Out-Of-Band Accumulator Source 0 to 5 1 F167 0 (SRC 1)
" 3D4A Frequency Out-Of-Band Accumulator Target Messages Enable 0 to 2 1 F109 0 (Self-reset)
" 3D4B Frequency Out-Of-Band Accumulator Time Limit Array (7 items) 1 to 65535 sec 1 F001 200
" 3D52 Frequency Out-Of-Band Accumulator Time Preset Array (7 items) 0 to 65535 sec 1 F001 0
" 3D59 Frequency Out-Of-Band Accumulator Upper Frequency Array (7 items) 20 to 70 Hz 0.01 F001 6000
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F167 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6

Logics & highlights


Frequency out-of-band accumulation logic

Frequency out-of-band accumulation logic

error: Content is protected !!