Overview
For more detailed information on “Field ground” element of the “Field ground fault” protection, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.
To see other supported elements, click here.
Setting Parameters
Modbus memory map for Setting parameters
Products | Hex address | Register name | Range | Units | Step | Format | Default |
G60 | 5036 | Field Ground Function | 0 to 1 | — | 1 | F102 | 0 (Disabled) |
" | 5037 | Field Ground Injection Frequency | 0.1 to 3 | Hz | 0.01 | F001 | 100 |
" | 5038 | Field Ground Injection Connection Type | 0 to 1 | — | 1 | F613 | 0 (Single Point) |
" | 5039 | Field Ground STG1 Pickup | 1 to 500 | kOhm | 1 | F001 | 20 |
" | 503A | Field Ground STG1 Delay | 0.1 to 600 | seconds | 0.1 | F001 | 100 |
" | 503B | Field Ground STG2 Pickup | 1 to 500 | kOhm | 1 | F001 | 5 |
" | 503C | Field Ground STG2 Delay | 0.1 to 600 | seconds | 0.1 | F001 | 30 |
" | 503D | Field Ground UC Pickup | 0.05 to 100 | mA | 0.01 | F001 | 100 |
" | 503E | Field Ground UC Delay | 0.1 to 600 | seconds | 0.01 | F001 | 100 |
" | 503F | Field Ground Block | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 5041 | Field Ground Target | 0 to 2 | — | 1 | F109 | 0 (Self-reset) |
" | 5042 | Field Ground Events | 0 to 1 | — | 1 | F102 | 0 (Disabled) |
F102 | 0 = Disabled, 1 = Enabled | ||||||
F109 | 0 = Self-reset, 1 = Latched, 2 = Disabled | ||||||
F163 | 0 = Wye, 1 = Delta, 2 = Zig-zag | ||||||