GE / Field ground (ANSI 64F) _ Element settings & highlights _ GU8021

Table of Contents

Overview

For more detailed information on “Field ground” element of the “Field ground fault” protection, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
G60 5036 Field Ground Function 0 to 1 1 F102 0 (Disabled)
" 5037 Field Ground Injection Frequency 0.1 to 3 Hz 0.01 F001 100
" 5038 Field Ground Injection Connection Type 0 to 1 1 F613 0 (Single Point)
" 5039 Field Ground STG1 Pickup 1 to 500 kOhm 1 F001 20
" 503A Field Ground STG1 Delay 0.1 to 600 seconds 0.1 F001 100
" 503B Field Ground STG2 Pickup 1 to 500 kOhm 1 F001 5
" 503C Field Ground STG2 Delay 0.1 to 600 seconds 0.1 F001 30
" 503D Field Ground UC Pickup 0.05 to 100 mA 0.01 F001 100
" 503E Field Ground UC Delay 0.1 to 600 seconds 0.01 F001 100
" 503F Field Ground Block 0 to 4294967295 1 F300 0
" 5041 Field Ground Target 0 to 2 1 F109 0 (Self-reset)
" 5042 Field Ground Events 0 to 1 1 F102 0 (Disabled)
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F163 0 = Wye, 1 = Delta, 2 = Zig-zag

Logics & highlights


“FIELD GROUND INJECTION FREQUENCY” parameter

FIELD GROUND INJECTION FREQUENCY

Field ground fault detector function logic

Field ground fault detector function logic