Overview
For more detailed information on “Field current” element of the “Field ground fault” protection, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.
To see other supported elements, click here.
Setting Parameters
Modbus memory map for Setting parameters
Products | Hex address | Register name | Range | Units | Step | Format | Default |
G60 | 502C | Field Current Function | 0 to 1 | — | 1 | F102 | 0 (Disabled) |
" | 502D | Field Current Origin | 0 to 48 | — | 1 | F151 | 0 (NONE) |
" | 502E | Field Current Over Current (OC) Pickup | 0.05 to 1 | pu | 0.01 | F001 | 80 |
" | 502F | Field Current Over Current (OC) Delay | 0 to 600 | seconds | 0.01 | F001 | 100 |
" | 5030 | Field Current Under Current (UC) Pickup | 0.05 to 1 | pu | 0.01 | F001 | 20 |
" | 5031 | Field Current Under Current (UC) Delay | 0 to 600 | seconds | 0.01 | F001 | 100 |
" | 5032 | Field Current Block | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 5034 | Field Current Target | 0 to 2 | — | 1 | F109 | 0 (Self-reset) |
" | 5035 | Field Current Events | 0 to 1 | — | 1 | F102 | 0 (Disabled) |
F102 | 0 = Disabled, 1 = Enabled | ||||||
F109 | 0 = Self-reset, 1 = Latched, 2 = Disabled | ||||||
F151 | 0 = None, 1 = RTD 1, 2 = RTD 2, 3 = RTD 3, 4 = RTD 4, 5 = RTD 5, — , 45 = RTD 45, 46 = RTD 46, 47 = RTD 47, 48 = RTD 48 | ||||||