GE / Field current _ Element settings & highlights _ GU8022

Table of Contents

Overview

For more detailed information on “Field current” element of the “Field ground fault” protection, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
G60 502C Field Current Function 0 to 1 1 F102 0 (Disabled)
" 502D Field Current Origin 0 to 48 1 F151 0 (NONE)
" 502E Field Current Over Current (OC) Pickup 0.05 to 1 pu 0.01 F001 80
" 502F Field Current Over Current (OC) Delay 0 to 600 seconds 0.01 F001 100
" 5030 Field Current Under Current (UC) Pickup 0.05 to 1 pu 0.01 F001 20
" 5031 Field Current Under Current (UC) Delay 0 to 600 seconds 0.01 F001 100
" 5032 Field Current Block 0 to 4294967295 1 F300 0
" 5034 Field Current Target 0 to 2 1 F109 0 (Self-reset)
" 5035 Field Current Events 0 to 1 1 F102 0 (Disabled)
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F151 0 = None, 1 = RTD 1, 2 = RTD 2, 3 = RTD 3, 4 = RTD 4, 5 = RTD 5, — , 45 = RTD 45, 46 = RTD 46, 47 = RTD 47, 48 = RTD 48

Logics & highlights


Field current fault detector function logic

Field current fault detector function logic