Overview

The “Fault locator” function is used to determine the distance to the fault location. Quick determination of fault location and the associated rapid troubleshooting increase the availability of the line for the power transmission in the electrical power system. Fault-location determination is based on the determination of the reactance of the short-circuited measuring loops.

For more detailed information on “Fault locator” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Fault locator Function

Setting Parameters


Setting parameters for the Instantiation of the Fault Locator in the Line Function Group

Addr. Parameter C Setting Options Default Setting
Fault locator
_:1 Fault locator:Mode   off
on
test
off
_:101 Fault locator:Start   with operate
with going pickup
with going pickup
_:102 Fault locator:Parallel-line compensat.   no
yes
yes
_:103 Fault locator:Load compensation   no
yes
no
_:104 Fault locator:Substitute for IF   3I2
3I0
3I0
_:106 Fault locator:Comp. angle zero seq.   -40.00 ° to 40.00 ° 0.00 °
_:107 Fault locator:Comp. angle neg. seq.   -40.00 ° to 40.00 ° 0.00 °

Setting parameters for the Instantiation of the Fault Locator in the VI 3-Ph Function Group

Addr. Parameter C Setting Options Default Setting
Fault locator
_:1 Fault locator:Mode   off
on
test
off
_:101 Fault locator:Start   with operate
with going pickup
with going pickup
_:103 Fault locator:Load compensation   no
yes
no
_:122 Fault locator:Substitute for IF   3I2
3I0
3I0
_:124 Fault locator:Comp. angle zero seq.   -40.00 ° to 40.00 ° 0.00 °
_:125 Fault locator:Comp. angle neg. seq.   -40.00 ° to 40.00 ° 0.00 °
_:113 Fault locator:X per length unit 1 A 0.0005 Ω/km to 9.5000 Ω/km 0.0525° Ω/km
5 A 0.0001 Ω/km to 1.9000 Ω/km 0.0105 Ω/km
_:114 Fault locator:Line length   0.10 km to 1000.00 km 60.00 km
_:108 Fault locator:Line angle   10.00 ° to 89.00 ° 85.00 °
_:104 Fault locator:Kr   -0.33 to 11.00 1.00
_:105 Fault locator:Kx   -0.33 to 11.00 1.00
_:118 Fault locator:K0   0.000 to 11.000 1.000

Logic Diagrams & highlights


Routing Matrix for the Triggering of the Fault Locator via Binary Input

Routing Matrix for the Triggering of the Fault Locator via Binary Input

Determining the Measurement Window

Determining the Measurement Window

Short Circuit of a Phase-to-Phase Loop

Short Circuit of a Phase-to-Phase Loop

Short Circuit of a Phase-to-Ground Loop

Short Circuit of a Phase-to-Ground Loop

Fault Currents and Voltages of a Line Fed on Both Sides (1-Pole Display)

Fault Currents and Voltages of a Line Fed on Both Sides (1-Pole Display)

Calculations for Short Circuit of a Phase-to-Ground Loop

Short Circuit of a Phase-to-Ground Loop (part 1)
Short Circuit of a Phase-to-Ground Loop (part 2)
Short Circuit of a Phase-to-Ground Loop (part 3)
Short Circuit of a Phase-to-Ground Loop (part 4)

Short Circuit of a Phase-to-Phase Loop

Short Circuit of a Phase-to-Phase Loop

Ground Fault on a Double Line

Ground Fault on a Double Line

Routing in DIGSI

Routing in DIGSI