Siemens / Fault locator plus _ Setting & highlights _ SI5052

Table of Contents

Overview

The “Fault locator plus” function is used for 2-sided measurement of the distance to the fault location. It also reliably detects the fault location in case of 2-sided infeed, ground faults, and in case of fault resistances and can be used for fault-location determination in case of non-homogeneous lines. The Fault locator plus function calculates the fault location with the measured values of both line ends.

For more detailed information on “Fault locator plus” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Fault locator plus Function

Setting Parameters


General setting parameters and parameters related to line data

Addr. Parameter C Setting Options Default Setting
Control
_:2311:1 General:Mode   off
on
test
off
_:2311:101 General:Start   with operate
with going pickup
with going pickup
Compensation
_:2311:102 General:Parallel-line compensat.   no
yes
no
_:2311:109 General:Gnd.curr.ratio( MutComp)   50 % to 95 % 85 %
_:2311:103 General:Load compensa- tion   no
yes
no
_:2311:104 General:Substitute for IF   3I2
3I0
3I0
_:2311:106 General:Comp. angle zero seq.   -40.00 ° to 40.00 ° 0.00 °
_:2311:107 General:Comp. angle neg. seq.   -40.00 ° to 40.00 ° 0.00 °
Line data 1
_:16921:112 Line section 1:C1 per length unit 1 A 0.000 °F/km to 100000.000
°F/km
0.010 °F/km
5 A 0.000 °F/km to 500000.000
°F/km
0.050 °F/km
_:16921:148 Line section 1:C0 per length unit 1 A 0.000 °F/km to 100000.000
°F/km
0.010 °F/km
5 A 0.000 °F/km to 500000.000
°F/km
0.050 °F/km
_:16921:113 Line section 1:X per length unit 1 A 0.0005 Ω/km to 9.5000 Ω/km 0.0525 Ω/km
5 A 0.0001 Ω/km to 1.9000 Ω/km 0.0105 Ω/km
_:16921:114 Line section 1:Line length   0.10 km to 1000.00 km 60.00 km
_:16921:108 Line section 1:Line angle   10.00 ° to 89.00 ° 85.00 °
_:16921:104 Line section 1:Kr   -0.33 to 11.00 1.00
_:16921:105 Line section 1:Kx   -0.33 to 11.00 1.00
_:16921:118 Line section 1:K0   0.000 to 11.000 1.000
_:16921:150 Line section 1:Angle (K0)   -180.00 ° to 180.00 ° 1.00 °
_:16921:106 Line section 1:KmR   0.00 to 8.00 1.00
_:16921:107 Line section 1:KmX   0.00 to 8.00 1.00
_:16921:124 Line section 1:Km0   0.000 to 8.000 1.000
_:16921:125 Line section 1:Angle (Km0)   -180.00 ° to 180.00 ° 0.00 °
_:16921:120 Line section 1:Blocking of the auto. recl.   no
yes
no

Setting parameters in the AWE

Addr. Parameter C Setting Options Default Setting
Blk by FtLc. #
_:102 Blk by FtLc. #:Min. dead time of blocking   0.00 s to 1800.00 s 0.50 s

Logic Diagrams & highlights


Routing Matrix for the Triggering of the Fault Locator via Binary Input

Routing Matrix for the Triggering of the Fault Locator via Binary Input

Voltage Curve, Calculated from Both Sides of the Line

Voltage Curve, Calculated from Both Sides of the Line

Routing in DIGSI

Routing in DIGSI